INTRODUCERE ........................................................................................................................... iv
CAPITOLUL 1. SISTEMELE CENTRALIZATE DE ALIMENTARE CU CLDUR
(SACET) DIN ROMNIA............................................................................................................ 1
1.1. Scurt introducere .................................................................................................................... 1
1.2. Tipurile SAC ............................................................................................................................ 2
1.3. Structura SAC .......................................................................................................................... 3
1.4. Reglajul termic practicat n instalaiile centralizate de distribuie energie termic ................. 3
CAPITOLUL 2. REABILITAREA TERMIC A CLDIRILOR RACORDATE LA
SISTEMUL CENTRALIZAT DE ALIMENTARE CU CLDUR ....................................... 9
2.1. Scurt introducere .................................................................................................................... 9
2.2. Considerente generale privind reabilitarea cldirilor ............................................................. 10
2.3. Caracteristici termoenergetice ale anvelopei cldirilor .......................................................... 11
2.4. Caracteristici reale ale anvelopei cldirilor ............................................................................ 26
2.5. Potenialul de eficientizare al cldirilor din Romnia ............................................................ 34
2.6. Termostatarea i echilibrarea hidraulic a instalaiei interioare ............................................. 37
2.7. Concluzii pariale ................................................................................................................... 41
CAPITOLUL 3. MODELAREA COMPORTAMENTULUI TERMIC DINAMIC AL
SISTEMULUI CLDIRE-INSTALAIE DE NCLZIRE. REGLAJUL TERMIC
CALITATIV CENTRALIZAT .................................................................................................. 43
3.1. Scurt introducere .................................................................................................................. 43
3.2. Stabilirea modelelor matematice ............................................................................................ 43
3.3. Validarea experimental a modelului matematic ................................................................... 50
3.4. Concluzii pariale ................................................................................................................... 52
3.5. Simularea comportamentului termic dinamic al cldirii. Programul utilizat i metoda
elaborat ........................................................................................................................................ 52
3.6. Reglajul termic calitativ pe circuitul secundar ....................................................................... 55
3.6.1. Cazul reglajului centralizat mixt ......................................................................................... 58
3.6.2. Fluctuaiile de puteri termice la consumatori datorit aporturilor interne i externe de
cldur ........................................................................................................................................... 61
3.7. Randamentul de reglare al instalaiilor interioare de nclzire central ................................. 63
3.7.1. Cazul cldirii nereabilitat pe parte de construcie i nemodernizat pe parte de instalaii
interioare........................................................................................................................................ 68
3.7.2. Cazul cldirii nereabilitat pe parte de construcie dar modernizat pe parte de instalaii
interioare........................................................................................................................................ 72
3.7.3. Cazul cldirii reabilit pe parte de construcie ns nemodernizat pe parte de instalaii
interioare........................................................................................................................................ 75
3.7.4. Cazul cldirii reabilit pe parte de construcie i modernizat pe parte de instalaii
interioare........................................................................................................................................ 77
i
CAPITOLUL 4. ACHIZIIA I PRELUCRAREA DATELOR EXPERIMENTALE ....... 81
4.1. Descrierea instalaiei de distribuie a agentului termic pe care s-a efectuat monitorizarea ... 81
4.1.1. Metodele de msurare i controlul procesului..................................................................... 83
4.1.2. Monitorizarea i achiziia datelor ........................................................................................ 85
4.1.3. Datele generale ale blocurilor monitorizate ........................................................................ 88
4.2. Cazul cldirii nereabilitat pe parte de construcie i nemodernizat pe parte de instalaii
interioare........................................................................................................................................ 93
4.3. Concluzii pariale ................................................................................................................... 96
4.4. Cazul cldirii nereabilitat pe parte de construcie dar modernizat pe parte de instalaii
interioare........................................................................................................................................ 96
4.5. Concluzii pariale ................................................................................................................. 105
4.6. Cazul cldirii reabilite pe parte de construcie ns nemodernizat pe parte de instalaii
interioare...................................................................................................................................... 106
4.7. Concluzii pariale ................................................................................................................. 118
4.8. Cazul cldirii reabilit pe parte de construcie i modernizat pe parte de instalaii interioare
..................................................................................................................................................... 119
4.9. Concluzii partiale ................................................................................................................. 126
CAPITOLUL 5. MSURI I SOLUII PRIVIND EFICIENTIZAREA ALIMENTRII
CU CLDUR A DIVERSELOR TIPURI DE CONSUMATORI RACORDAI LA
SISTEMUL CENTRALIZAT DE DISTRIBUIE A AGENTULUI TERMIC ................. 127
5.1. Scurt introducere ................................................................................................................ 127
5.2. Soluiile pentru creterea eficienei energetice la nivelul sursei .......................................... 127
5.2.1. Scheme constructiv-funcionale de staii termice compacte ............................................. 129
5.2.2. Structuri de baz bilanuri termice reprezentative.......................................................... 137
5.3. Soluii pentru creterea eficienei energetice la nivelul instalaiei de nclzire central din
cldiri........................................................................................................................................... 151
5.4. Soluii pentru creterea eficienei energetice la nivelul anvelopei cldirii........................... 153
CAPITOLUL 6. CONCLUZII GENERALE, CONTRIBUII ORIGINALE,
POSIBILITI DE VALORIFICARE A REZULTATELOR OBINUTE ..................... 158
6.1. Concluzii generale ................................................................................................................ 158
6.2. Contribuii principale ........................................................................................................... 163
6.3. Posibiliti de valorificare i continuare a cercetrilor n domeniu ...................................... 164
Bibliografie................................................................................................................................. 166
ANEXE ....................................................................................................................................... 169
ii
Mulumiri
Autorul
***
iii
Introducere
INTRODUCERE
Lucrarea este un studiu tiinific care are ca fundament cerinele Directivei
europene EC/91/2002 i a Legii 372/2005 privind performana energetic a cldirilor
precum i a Directivei EC/76/93 din septembrie 1993 referitoare la limitarea emisiilor de
CO2, creterea eficienei utilizrii energiei i protecia mediului.
Aceast tez propune o cercetare orientat asupra analizei impactului reabilitrii
i modernizrii cldirilor din ansamblurile de locuine colective alimentate centralizat
prin intermediul reelelor arborescente de distribuie energie termic, n scopul
mbuntirii performanelor energetice globale ale sistemelor complexe de producere i
utilizare a energiei termice. Se urmrete astfel rezolvarea conceptual a principalelor
probleme legate de exploatarea sistemelor termice, din punct de vedere al eficienei
energetice i al performanelor tehnice ale acestora.
Obiectivul materialului se nscrie astfel ntr-o aciune constnd n identificarea i
aprofundarea cunotinelor aspura factorilor care limiteaz randamentul de reglare al
instalaiilor de nclzire central n contextul reabilitrii la nivel de consumator final i
de identificare a cilor tiintifice reprezentative prin care poate fi analizat aceast
problematic precum i de a contribui la mbuntirea lor.
Reducerea consumurilor energetice la consumatorii urbani datorat att creterii
temperaturilor exterioare ca rezultat al nclzirii globale ct i a debranrilor, este
amplificat i de reabilitrile termice aprute la o serie de cldiri colective de locuit i
odat cu impunerea realizrii certificatelor de performan enegetic pentru cldirile noi
realizate.
Cu cca. 10 ani urm au nceput s apar primele reabilitri i modernizri
efectuate n cadrul instalaiilor interioare ale blocurilor de locuine. Ne referim la
montarea de contoare de ap la grupurile sanitare i la spltoarele de la buctrii, la
montarea de baterii noi la obiectele sanitare, la montarea de robinete termostatice i
repartitoare de costuri la corpurile de nclzire i o serie de alte msuri de acest gen. n
urma implementrii acestor msuri pe instalaiile interioare din cldirile colective, s-a
oferit o prghie important consumatorilor n ceea ce privete optarea pentru un consum
adecvat de energie termic cu necesitile efective i totodat cu posibilitile de plat.
A rezultat dup cum este cunoscut un consum de energie termic diminuat fa de
situaia anterioar implementrii reabilitrilor i destul de fluctuant n timp. Pentru ca
aceast diminuare de solicitare energetic s se transforme efectiv ntr-un consum redus
de combustibil fosil este ns necesar ca sistemul de alimentare centralizat cu cldur
s fie echipat i automatizat n mod corepunztor.
n teza de fa s-a realizat o analiz complet a funcionrii unui sistem de
alimentare centralizat cu cldur a unor blocuri de locuine, ncepnd cu punctul termic
de producere a agentului secundar i finaliznd cu consumatorii de cldur. Totodat, s-a
iv
Introducere
pus accentul pe analiza problematicii principalelor efecte ale reabilitrii la nivel de instalaie
interioar i a proteciei termice a cldirilor, care au implicaii asupra consumului energetic
pentru nclzire i asupra gradului de confort al ocupanilor din cldire.
Lucrarea i propune s prezinte informaiile tehnice i teoretice de utilizare ale
sistemelor de control pentru aceste obiective i prelucrarea i evaluarea analitic a
datelor achiziionate de la nivel de consumator final.
Lucrarea urmrete identificarea lipsurilor existente actualmente n ceea ce
privete echiparea corespunztoare a sistemelor de alimentare centralizat cu cldur i
de asemenea n reglajul termic calitativ sau cantitativ al consumatorilor finali de tipul
cldirilor colective, n perspectiva ntampinrii programelor de reabilitare aflate n plina
derulare. Totodat se vor face propuneri i recomandri n ceea ce privete
eficientizarea funcionrii sistemului de alimentare centralizat cu cldur n centrele
urbane n acest context. n cadrul lucrrii se va prezenta sintetic situaia existent n
sistemul de alimentare centralizat cu cldur, identificndu-se carenele n ceea ce
privete corectitudinea reglajului termic. Totodat se va prezenta prelucrarea i
evaluarea analitic a datelor achiziionate la nivel de consumator final, in diferite situaii
de reabilitare.
Cercetrile experimentale s-au efectuat n situ pe sistemul SACET al municipiului
Bucureti i au presupus prelevarea unui set de parametri termo-hidraulici pe perioada
sezoanelor reci 2007-2010.
Mai concret, n cadrul cerecetrilor experimentale a fost monitorizat un ansamblu
de 14 imobile de locuine, reprezentnd consumatorii finali alimentai cu energie termic
pentru nclzire i ap cald de consum de la un punct termic integral automatizat.
Monitorizarea s-a desfurat pe perioada a trei ierni succesive, reprezentnd perioadele
sezonului de nclzire pentru ntreg ansamblul menionat. Studiul s-a efectuat prin
prelucrarea bazei de date ce conine parametrii achiziionai la nivel de instalaie de
nclzire PT, reea secundar i consumatori.
Au fost analizate urmtoarele categorii de blocuri alimentate de la sistemul
centralizat:
- Blocuri nereabilitate att pe parte de construcie ct i pe parte de instalaii;
- Blocuri nereabilitate pe parte de construcie dar reabilitate parial pe parte de
instalaii;
- Blocuri reabilitate pe parte de construcie dar nereabiliate pe parte de instalaii;
- Blocuri reabilitate atat pe parte de construcie ct i pe parte de instalaii.
Prin analiza teoretic s-a urmrit evidenierea situaiei alimentrii centralizate cu
cldur a blocurilor reabilitate i nereabilitate, alimentate de la acelai sistem unic
centralizat de alimentare cu cldur. Au fost vizate consecinele temperaturii unic reglate
dup blocurile nereabilitate, asupra tuturor consumatorilor alimentai.
Sunt detaliate astfel obiectivele tezei de doctorat:
n prima parte a lucrrii punerea n eviden a structurii sistemelor de alimentare
v
Introducere
vi
Introducere
vii
Lista de Notaii
viii
Va volumul interior al spaiului nclzit, (m3);
VPI volumul masivitii interioare, (m3);
VPE columul masivitii exterioare, (m3);
a densitatea aerului, (kg/m3);
PI densitatea masivitii interioare, (kg/m3);
PE densitatea masivitii exterioare, (kg/m3);
ca cldura specific a aerului, (J/kg.K);
cPI cldura specific a masivitii interioare, (J/kg.K);
cPE cldura specific a masivitii exterioare, (J/kg.K);
na numrul de schimburi de aer al volumului interior (sch/h);
NTU; NTUCI numrul de uniti de transfer termic al instalaiei de nclzire, (-);
k CI S CI 1 exp NTU CI
NTU CI ; ECI exp NTU CI ; FCI ;
G c NTU CI
CT constante de timp, (s).
ix
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
CAPITOLUL 1
SISTEMELE CENTRALIZATE DE ALIMENTARE CU
CLDUR (SACET) DIN ROMNIA
Din cele mai vechi timpuri, cea mai simpl metod de nclzire a fost cea a focului
liber de lemne, care transmitea mediului ambiant cldura prin radiaie i prin gazele de
ardere ce se amestecau cu aerul din ncpere.
Aceasta metod de nclzire a fost nlocuit mai trziu cu arderea de crbuni de
lemn n vase speciale, ns fr grtare. Dat fiind abundena pdurilor, acest sistem de
nclzire a fost destul de larg folosit vreme ndelungat; astfel, n 1970, Parlamentul din
Londra se mai nclzea cu vase cu mangal incandescent. Randamentul acestui fel de
nclzire era destul de ridicat, cci toata cldura produs se degaja n ncpere.
O nou etap de dezvoltare a tehnicii nclzirii o constituie arderea combustibilului
ntr-un fel de sobe sau cmine primitive, care serveau la prepararea hranei, la nceput cu
eliminarea produselor arderii direct n ncperi, iar mai tarziu (ncepnd cu secolul XI-lea
al erei noastre), cu evacuarea produselor arderii n exterior, prin burlane.
Prin mbuntirea continu a acestui sistem a aparut sistemul de nclzire cu
canale de aer cald. Sistemul era alcatuit dintr-un focar n care erau aezate blocuri de
granit ce se nclzeau pna la incandescen, dupa care aerul nclzit ce trecea peste
aceste blocuri se ridica n mod natural prin diverse canale n ncperile de nclzit.
nclzirea prin acest sistem a pereilor i a pardoselilor, care aveau o inerie termic mare,
asigura meninerea unei temperaturi corespunztoare pentru un timp mai ndelungat.
Acest sistem a fot folosit pan la sfritul secolului trecut.
Ctre sfritul secololui al XVIII-lea i nceputul secolului al XIX-lea sunt
menionate primele instalaii de nclzire cu abur (n Rusia i n Germania) [8].
Prima instalaie de nclzire central cu ap cald cunoscut (mai comod
pentru locuine) a fost aceea a arhitectului Bonnemain, la castelul Pecq (1777). Dup
1830 apar instalaii de nclzire cu ap cald n Rusia n anul 1832, n Anglia 1834, n
America n 1877 etc. [9].
Ca etap superioar a dezvoltrii tehnicii instalaiilor de nclzire trebuie privit
centralizarea aprovizinrii cu cldur i transportul ei la distan. La nceput s-a dezvoltat
1
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
2
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
3
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
4
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
Fig. 1.1 - Schema de reglare n trei trepte (surs, punctul termic i consumator) a
furnizrii cldurii pentru nclzirea cldirilor n sistemele de termoficare.
5
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
6
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
7
Capitolul 1 Sistemele centralizate de alimentare cu cldur (SACET) din Romnia
Avnd n vedere cele menionate anterior, cel puin din punct de vedere teoretic
apare c cele mai favorabile condiii de furnizare a cldurii le ofer reglarea mixt
(calitativ-cantitativ) care ar reprezenta soluia optim din punct de vedere tehnic i
economic.
Acest tip de reglare ar constitui metoda cea mai elastic de urmrire general i
local a variaiilor necesarului de cldur pentru nclzirea cldirilor. Aceast soluie de
reglare este mai indicat deoarece n sistemul de alimentare cu cldur sunt alimentai
consumatori difereniai att din punct de vedere al aparatelor de nclzire ct i din punct
de vedere al temperaturilor interioare i al ineriei termice.
Rezult deci c la acei consumatori la care temperatura din conduct de ducere
asigurat de surs nu corespunde cerinelor particulare, este necesar a se prevedea
posibilitatea modificrii debitului de agent termic.
Un avantaj deloc de neglijat al reglarii mixte este acela din punct de vedere
economic, ntruct prin reducerea temperaturii agentului termic pe conducta de ntoarcere
la central rezult o mbuntire a indicelui de termoficare.
Ceea ce este totui foarte important n aplicarea acestei modaliti de reglare a
furnizrii cldurii este faptul c pentru aplicarea n practic a acestei soluii este imperios
necesar intervenia unor bucle de reglare n surse (reglarea primar) ct i n instalaiile
consumatorilor (reglarea secundar), iar pentru obinerea unei eficiene maxime i
introducerea unor bucle de reglare teriare n ncperile nclzite, adic acolo unde este
resimit orice perturbare a bilanului local al schimbului de cldur care se repercuteaz
n modificarea temperaturii de confort termic interior.
Este posibil ca, innd seama de natura proceselor de alimentare prin sistemul de
termoficare s se impun, sub aspect tehnic, funcionarea cu debit variabil n circuitul
primar chiar n ipoteza unui grafic calitativ de reglare i apropiat de cel teoretic; n
aceast situaie variaiile de debit n reea ar fi generate, teoretic, numai de procesul de
preparare a apei calde de consum. n cazul alimentrii cu cldur pentru nclzire pe baza
unui grafic de reglare mixt, este ns posibil o variaie mai mare a debitului (de
exemplu ntre 0.45-1.0 Gn ).
n ceea ce privete fixarea (alegerea) temperaturii apei de reea la cererea RADET
de ctre fiecare surs, n funcie de temperatura aerului exterior se aplic msura de a
modifica acest parametru naintea fiecrui modul de timp, de 8-12 ore, caracterizat printr-
o temperatur medie ponderat a aerului exterior. Exist situaii, la temperaturi exterioare
foarte mici (-10...-15C) i cu calm atmosferic, n care temperatura agentului termic
primar pe conducta de ducere la surs, are o valoare fixat pentru 24 ore de funcionare.
Acest procedeu se justific prin variaia relativ redus a temperaturii aerului exterior, de
2...3C fa de temperatura medie zilnic [10].
8
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
CAPITOLUL 2
REABILITAREA TERMIC A CLDIRILOR RACORDATE LA
SISTEMUL CENTRALIZAT DE ALIMENTARE CU CLDUR
9
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Cldirile cu alt destinaie dect cea de locuire se mpart dup modul de ocupare n
cldiri cu ocupare continu i cu ocupare discontinu, iar dup clasa de inerie termic n
cldiri de clas de inerie mare, medie sau mic.
Elementele de construcie care alctuiesc anvelopa unei astfel de cldiri trebuie
astfel concepute nct s asigure n interiorul ncperilor condiii corespunztoare de
confort higrotermic, acustic, vizual-luminos, olfactiv-respirator.
Confortul higrotermic se traduce n nivele de temperatur i umiditate uor de
suportat. El se realizeaz cu consum de energie, fie pentru nclzirea spaiului utilizat
(iarna), fie pentru rcirea lui (vara). Din acest motiv, confortul higrotermic reprezint
10
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
11
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
1W 0.860kcal / h 1J / s
1m 2 K / W 1.163m 2 h C / kcal
1W /( m3 K ) 0.860kcal /( m3 h C )
1Wh 3600 J 0.860kcal
1Gcal 109 cal 106 kcal 1.163x103 kWh 1.163MWh
12
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
1 1 k
RPE Ri Re Rk (2.1)
k i e k k
unde:
2
[W/m K] coeficient de transfer termic convectiv la faa interioar a peretelui;
i
2
[W/m K] coeficient de transfer termic convectiv la faa exterioar a peretelui;
e
[m] grosimea stratului de perete k;
k
[W/mK] conductivitatea termic a stratului de perete k.
k
13
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
1 1 1 N lj
(2.2)
Re R S j 1 Rlj
CONDIIA 1:
ti te
RPE Ri (2.3)
t i t si
14
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
unde:
o
t temperatura aerului interior ( C);
i
o
t temperatura suprafeei interioare a peretelui ( C);
si
o
t temperatura aerului exterior ( C).
e
CONDIIA 2:
ti te
RPE Ri (2.4)
t i max
unde:
o
t [ C] diferena dintre temperatura aerului interior i temperatura suprafaei
i max
o
interioare a peretelui (n C). Valorile acestei diferene de temperatur sunt prezentate n
tabelul din ANEXA 1.
Cu ct rezistena termic a peretelui este mai mare, cu att i diferena dintre
15
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
CONDIIA 3:
16
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Astfel, dac n cazul unei uniformiti a peretelui avem un flux termic constant
(desenat cu verde n figura 2.1), atunci peste acest flux termic avem un flux suplimentar
ce urmrete forma geometric a punii termice. Observm n aceast figur reprezentarea
suplimentar a fluxului de cldur al punii termice lineare (desenat cu albastru n figura
2.1) i reprezentarea suplimentar a fluxului de cldur al punii termice locale de tip
agraf (desenat cu rou n figura 2.1).
17
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Astfel, fluxul pierdut prin acest perete exterior reprezint suma celor trei tipuri de
fluxuri:
Fluxul de cldur pierdut prin acest perete Q (W) se poate calcula (ecuaia 2.5 - 2.6)
PE
ca sum a celor trei fluxuri:
S PE S
t PE t ( l ) t ( ) t (2.6)
R' PE RPE
unde:
Straturi de aer neventilate. n realitate ntlnim fie pereii exteriori dubli care
confer o mai bun protecie termic a ncperilor, fie anvelope de tip cortin, ce conin
straturi de aer neventilat. Rezistenele termice normate ale acestor straturi de aer sunt
diferite n funcie de direcia i sensul fluxului de cldur i de grosimea stratului de aer
neventilat (ANEXA 3).
18
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
19
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Q Qi (2.7)
i
SE S
i (2.7a)
Rm i R'i
unde:
SE S i
Rm i
(2.8)
Si S
i R' i R'i
i i
2
O anvelop a crei rezisten medie este de proximativ 0,4-0,5 [m K/W]
corespunde cldirilor neizolate, sau slab izolate termic, n timp ce cldirile de referin
2
sunt caracterizate de rezistene de ordinul 0,6-0,7 [m K/W], iar eficiente energetic sunt
2
caracterizate de rezistene de ordinul 1-1,2 [m K/W].
20
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
unde:
21
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
3
densitatea aerului, egal cu 1,2 Kg/ m ;
aer
c cldura specific la presiune constant a aerului, egal cu 1005 j/kg/K;
p aer
o
t diferena de temperatur ntre aerul interior i cel infiltrat ( C).
t i t rxt
Sj
ti te
S j j
R'
R' j
G j 0.34 na 0.34 n (2.10)
a
V V
unde:
o
t temperatura interioar convenional de calcul ( C);
i
o
t temperatura exterioar convenional de calcul ( C);
e
o
t temperatura de la exteriorul peretelui ( C); poate fi temperatura unui subsol, unui
ext
pod, unei case de scar, sau a altui spaiu nenclzit.
22
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
N
K
E
(t
0
i t e )dx (2.11)
23
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
24
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
25
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Dac o cldire este reabilitat din punct de vedere termic, circa 30% din economia
total de energie se realizeaz datorit perioadei mai reduse de nclzire. Noua
temperatur de echilibru depinde de gradul reabilitrii i de starea fizico-termic iniial a
anvelopei cldirii. Influena aporturilor de cldur va crete semnificativ dup reabilitare.
C
T (2.13)
kS
C
T (2.14)
k j S j e ce L p
j
Dupa criza energetic din 1973, toate rile din Europa de Vest i n special rile
nordice, au trecut la efectuarea unor programe naionale de protecie termic, care au fost
realizate n etape progresive. n cadrul acestor programe s-au aplicat diferite soluii de
mbuntire a gradului de protecie termic beneficiindu-se de faciliti fiscale precum:
26
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
credite de stat cu dobnda mic, tarife difereniate la energia termic, scutirea de impozite
sau impozite difereniate etc. Ca urmare a acestor politici, a fost ncurajat perfecionarea
unor tehnologii i folosirea de materiale de construcii performante, pentru realizarea
elementelor exterioare de nchidere a cldirilor de locuit, asigurndu-se o cretere treptat
a rezistenelor termice ale acestora.
Conform datelor ultimului recensmnt din 2002, 52,5% din locuine sunt situate
n mediul urban.
Majoritatea locuinelor din Romnia sunt situate n cldiri cu vechime cuprins
ntre 15 i 55 ani, caracterizate printr-un grad redus de izolare termic i o uzur avansat.
Structura fondului locativ n funcie de vechime este prezentat n figura 2.6.
27
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
<10 ani
10 - 20 ani 3% >55 ans
7% >55 ani
25% 40 - 55 ans
20 - 40 ans
20 - 40 ani 10 - 20 ans
37% <10 ans
40 - 55 ani
28%
30 - 45 ans
<10 ans
30 - 45 ani
40%
n acelai timp, n medie 56% din cldirile rezideniale din UE sunt ocupate de
ctre proprietari. Acest aspect are o semnificaie particular n raport cu implicarea
proprietarilor (i a locatarilor n cazul Romniei) n activiti legate de economia de
energie n locuine [38].
28
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
n mod surprinztor, n anul 1973 sunt impuse valori diminuate pentru gradul de
protecie termic a elementelor de nchidere de aproximativ 26,4%, la o temperatur
interioar de referin ti = 20oC (figura 2.8).
1.8
1.6
1.4
1.2 zone climatique I
Ro,nec
1 zone climatique II
0.8
0.6 zone climatique III
0.4
0.2
0
Aceast situaie se explic prin ineria birocratic a sistemului care aplic norme
elaborate nainte de debutul crizei mondiale a petrolului, chiar dac realitatea era cu totul
alta.
Abia n anul 1978 n Romnia au fost modificate cteva reglementri. n acest
mod, temperatura interioar de referin a fost micorat la Ti = 18oC i valorile lui R 0
vor fi:
29
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
PERETI
4
3.5
avant oct.1975
3
2.5
Ro,nec
en 1976
2
1.5
recommand
1
0.5
0
Royaum
Russie
R.F.A
R.D.A
France
Norvge
Danemark
Sude
Italie
Roumanie
Pays-Bas
ACOPERISURI
5 avant oct.1975
4
Ro,nec
en 1976
3
2 recommand
1
0
Royaume
Russie
R.D.A
France
R.F.A
Norway
Sude
Italie
Roumanie
Pays-Bas
Danemark
30
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
31
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Not: datele statistice disponibile au fost publicate n 2003 i fac referin la 2002.
Fig. 2.11 - Evoluia consumurilor specifice de energie termic pentru nclzirea cldirilor
de locuit colective
32
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
70%
60%
50%
40%
30%
20%
10%
0%
Slovnie
Tchque Rp
Slovaquie
Roumanie
Lettonie
Estonie
Hongrie
Bulgarie
Lituanie
Pologne
33
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Cea mai rspandit metod de izolare termic a pereilor este acoperirea la exterior
cu un strat de polistiren. Polistirenul, ca toate materialele, este caracterizat de o
conductivitate termic (o constant a materialelor masurat n W/mK), care n general
este scris pe ambalaj. Aceast conductivitate termic, n raport cu grosimea, determin
coeficientul de transfer termic. ntre polistirenul expandat i cel extrudat, nu exist o
diferen considerabil a conductivitii termice [31].
Dup cum s-a artat, cldirile de locuit existente n Romnia au o izolare termic
sczut, inferioar cerinelor standardelor actuale, lucru ce conduce la consumuri mari de
energie n exploatare. Pentru a avea o imagine de ansamblu asupra performanelor
energetice ale cldirilor de locuit existente n Romnia, se arat n figura 2.13. graficul de
variaie a consumului specific anual de cldur pentru nclzire, pe tipuri reprezentative
de cldiri, n funcie de indicele de form (compactitate) al cldirii; indicele de form al
cldirii reprezint raportul dintre aria anvelopei cldirii, n m2 i volumul cldirii, n m3.
Fig. 2.13 - Consumul specific anual de cldur pentru nclzire al cldirilor de locuit din
Romnia
34
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
Desi s-ar prea ca ara noastr a atins un nivel performant n reglementrile aflate
n vigoare, la nivelul UE, se estimeaz c, pna n anul 2010, exist pentru cldiri un
potenial de economisire a energiei pentru nclzire, apa cald, aer-condiionat sau
iluminat de circa 22% din consumul prezent. Acest potenial de economisire este definit
ca reprezentnd investiiile n tehnologie eficient energetic avnd o perioad de
35
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
36
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
37
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
prezena persoanelor, etc.) pentru atingerea temperaturii dorite, fapt care conduce la
economisirea energiei termice date de calorifere.
Totodat se pot face adaptri ale cheltuielilor pentru nclzire la bugetul disponibil
prin limitri ale funcionrii caloriferelor n diverse ncperi i pe diverse perioade de
timp, fr a necesita debranri. Scderea temperaturii alese cu 1C duce la economii de
6% din costurile nclzirii. De asemenea, se poate alege un regim de funcionare a
caloriferelor cu protecia mpotriva ngheului, cu o importan deosebit pe perioada n
care nu se dorete nclzirea ncperilor respective.
Controlul consumului de cldur i obinerea n apartament a temperaturii de
confort, difereniat eventual pe ncperi, n funcie de destinaia fiecreia dintre acestea,
se realizeaz dotnd fiecare radiator cu cte un robinet termostatat, adic un robinet cu
dou ci pe care se monteaz un cap termostatic. Reglajul realizat este un reglaj de tip P,
adic proporional. Practic, este cea mai sigur i mai eficient soluie de reglare a
temperaturii camerei nclzit cu ajutorul radiatoarelor.
Avantajele majore ale utilizrii echipamentului sunt reprezentate de meninerea
temperaturii interioare de confort i realizarea unei foarte importante economii de energie
termic, prin nchiderea robinetului radiatorului, cnd temperatura interioar atinge
valoarea dorit. Deci nu este suficient doar repartitorul de costuri care ne indic consumul
ci mai este necesar i robinetul termostatat care controleaz temperatura i limiteaz
consumul.
Privit din punctul de vedere al pltitorului, putem spune c este chiar mai
important robinetul termostatat, pentru c de fapt acesta este elementul de limitare a
consumului din punct de vedere energetic i elementul de reglaj al temperaturii.
Cei mai importani parametri ai robinetului termostat, cei care difereniaz clar pe
caliti diferitele mrci, sunt hysteresis-ul, adic diferena de temperatur interioar ntre
deschiderea i nchiderea robinetului, timpul de reactive, cursa nominal a robinetului,
rezistena la ncovoiere, timpul de via, influena cderii de presiune pe robinet asupra
preciziei funcionrii acestuia, influena temperaturii agentului termic i ultimul dar nu i
cel din urm, zgomotul prin robinet, produs de un debit prea mare.
n momentul cnd avem de-a face cu un robinet termostatat care are hysteresis
mare, timp de reacie mare, influena mare asupra preciziei reglajului datorat presiunii i
temperaturii agentului termic, atunci controlul temperaturii interioare este alterat,
temperatura de confort se atinge foarte greu sau n anumite cazuri nu se atinge, echilibrul
termic n jurul temperaturii setate este prea fragil iar economia de energie nu se mai
realizeaz [32].
Robinetele cu reglaj termostatic modific debitul de agent termic care trece printr-
un corp nclzitor n funcie de temperatura aerului. Modificarea de debit aparut la unul
38
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
39
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
40
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
41
Capitolul 2 Reabilitarea termic a cldirilor racordate la sistemul centralizat de
alimentare cu cldur
42
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
CAPITOLUL 3
MODELAREA COMPORTAMENTULUI TERMIC DINAMIC AL
SISTEMULUI CLDIRE-INSTALAIE DE NCLZIRE.
REGLAJUL TERMIC CALITATIV CENTRALIZAT
43
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
o Bilanuri termice
S PE S
k CI S CI FCI t T i 2 e i FE t e i
R PE R FE
(3.1)
a ca d
n a Va t e i V PI PI c PI i
3600 d
d
i e 2 PE t e e VPE PE cPE e
S PE S
2 (3.2)
RPE RPE d
n relaia (3.1) apare factorul FCI care permite exprimarea fluxului termic livrat de
ctre instalaia de nclzire. Punerea n eviden a acestuia are la baz bilanul termic n
regim staionar a instalaiei de nclzire central [14].
44
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
sau:
tT t R
W c tT t R kCI SCI (3.4)
t t
ln T i
t R ti
Rezult de aici:
tT ti kCI SCI
ln NTU CI (3.5)
t R ti W c
t R ti
ECI exp NTU CI (3.6)
tT ti
t R 0 ti 0
ECI 0 exp NTU CI 0 (3.7)
tT 0 ti 0
unde:
tT 0 ti 0
NTU CI 0 ln (3.8)
t R 0 ti 0
Valorile curente pentru NTUCI i ECI se pot exprima n funcie de valorile lor nominale:
iar:
kCI kCI 0
k
CI k
CI 0
45
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
de unde:
n consecin rezult:
kCI kCI 0
1 E W W0
FCI CI 0
(3.13)
k k
NTU CI 0 CI CI 0
W W0
unde:
0.3
kCI tml
(3.14)
kCI 0 tml 0
n condiii nominale:
1
1 ECI 0 1 ECI 0 tT 0 t R 0 tT 0 ti 0
FCI 0 ln (3.15)
NTU CI 0 ln ECI 0 tT 0 ti 0 t R 0 ti 0
Revenind acum la relaiile (3.1) i (3.2), din prelucrarea acestora rezult sistemul de
ecuaii difereniale liniare de ordinul 1:
S PE S FE a ca
kCI SCI FCI 2 na Va i
di 1 RPE RFE 3600
(3.16)
d VPI PI cPI
2 S PE e kCI SCI FCI tT S FE a ca na Va te
R
RPE FE 3600
46
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
de 1 S PE S S S
2 2 PE e 2 PE i 2 PE te (3.17)
d VPE PE cPE RPE RPE RPE RPE
S S c
k CI S CI FCI tT 0 i 0 PE FE a a na Va i 0 t e 0 (3.18)
RPE RFE 3600
V PI PI c PI
CTi ;
S PE S FE a c a
k CI S CI FCI 2 n a Va
R PE R FE 3600
V PE PE c PE V c V c
CTe ; CTie PI PI PI ; CTici PI PI PI ; (3.19)
S S S k CI S CI FCI
2 PE 2 PE 2 PE
R PE R PE R PE
V PI PI c PI V c V c
CTite ; CTei PE PE PE ; CTete PE PE PE ;
S FE a c a S S
n a Va 2 PE 2 PE
R FE 3600 R PE R PE
d i 1 1 1 1
i e tT te ;
d CTi CTie CTici CTite
(3.20)
d e 1 1 1
e i te ;
d CTe CTei CTete
47
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
o Rezolvarea numeric
1 1 1 1
d i CTi CTie CTici CTite t
1 i T (3.21)
d e
1 e 0
1 te
CTei CTe CTete
Se fac notaiile:
1 1 1 1
CTi CTie C CTite
A ; B Tici ; (3.22)
1 1 1
0
CTei CTe CTete
d i i tT
A B (3.23)
d e e t e
i i tT tT
E F E A B I F A B
1 1
(3.24)
e j e i 1 t e j t e j 1
unde:
E exp A ;
F I E A 1 (3.25)
1 0
I
0 1
48
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Astfel:
S PE S
k CI S CI FCI tT i 2 e i FE t e i
RPE RFE
(3.27)
a ca
na Va t e i 0
3600
S PE S
2 i e 2 PE t e e 0 (3.28)
RPE RPE
S S c
k CI S CI FCI tT i PE FE a a na Va t e i 0 (3.29)
RPE RFE 3600
Rezult:
49
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
S S c
k CI S CI FCI tT PE FE a a na Va t e
i RPE RFE 3600 (3.30)
S PE S FE a c a
k CI S CI FCI n a Va
RPE RFE 3600
90
te (oC)
80 tT (oC)
ti (oC)
tp (oC)
70
tR (oC)
tis (oC)
60 tRs (oC)
tRe (oC)
50
40
30
20
10
-10
-20
0 200 400 600 800 1000 1200
50
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Vom trece n revist pe scurt liniile prezentate n fig. 3.1 pentru a putea comenta
comparativ rezultatele teoretice i experimentale - [25]; [26].
Linia roie linia temperaturilor agentului termic la intrarea n instalaia de
nclzire valorile prelevate din experiment i date de intrare pentru modelul teoretic;
Linia verde linia temperaturilor agentului termic la ieirea din instalaia de
nclzire valori prelevate din experiment;
Linia neagr (suprapus practic peste linia mov) linia temperaturilor agentului
termic la ieirea din instalaia de nclzire valori rezultate teoretic modelul
nestaionar;
Linia mov (suprapus practic peste linia neagr) linia temperaturilor agentului
termic la ieirea din instalaia de nclzire valori rezultate teoretic modelul staionar;
Linia neagr (suprapus peste linia galben) linia temperaturilor interioare
modelul teoretic nestaionar;
Linia galben (suprapus peste linia neagr) linia temperaturilor interioare
modelul teoretic staionar;
Linia verde linia temperaturilor reprezentative pentru masivitatea exterioar a
cldirii (modelul teoretic nestaionar);
Linia albastr linia temperaturilor exterioare (valori experimentale i date de
intrare pentru modelul teoretic).
Compararea rezultatelor teoretice cu cele experimentale trebuie fcut urmrind
liniile temperaturilor agentului termic la ieirea din instalaia de nclzire. Se observ
alura perfect asemntoare a celor dou linii, linia valorilor experimentale fiind puin
superioar celor teoretice (modelul staionar sau nestaionar). Diferena permite calibrarea
corect a modelului teoretic, mai precis identificarea valorii corecte pentru numrul de
uniti de transfer termic aferent instalaiei de nclzire a cldirii.
O a doua comparaie se poate face ntre liniile temperaturilor de ieire a agentului
termic din instalaia de nclzire, corepunztoare modelelor teoretice staionar i
nestaionar. Se observ practic o suprapunere a celor dou linii (mov i neagr). Acest
fapt atest posibilitatea utilizrii modelului teoretic de regim staionar n utilizarea unor
rezultate referitoare la instalaia de nclzire.
De asemenea o comparaie util se poate face ntre liniile temperaturilor interioare
aferente modelelor teoretice de regim staionar i nestaionar. Se observ c linia
temperaturilor interioare corespunztoare modelului teoretic staionar (linia galben)
atest fluctuaii mari, inexistente practic ntr-o cldire nclzit continuu pe perioada
sezonului rece. Linia temperaturilor interioare corespunztoare modelului teoretic
nestaionar (linia neagr) este o linie mult mai neted corepunztoare unui comportament
ntlnit frecvent n cldirile cu regim de nclzire continu [16].
51
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
52
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Date intrare:
- masivit. int.;
- masivit. ext.;
- ;
- ;
Date de ieire:
- ;
- ;
- .
53
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Date cldire:
- a = lungimea cldirii (m);
- b = laimea cldirii (m);
- h = nlimea unui nivel (m);
- n = numr niveluri (-);
- f_pe = procentul de perete exterior din totalul anvelopei (-);
- d_pe = grosimea medie a pereilor exteriori (m);
- aa = lungimea camerei (m);
- bb = limea camerei (m).
54
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
55
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
E
t T t e 1 B 2 t i 0 t e
E 1
(3.31)
1
t R t e 1 B 2 t i 0 t e
E 1
unde:
E exp B1 ti 0 te 1
1
1
G S 1 t
r r 0 te 0 1
1
B1 P (3.32)
G0 S0 tml 0
1
G t
B2 P r 0
G0 te 0
unde :
t 0 t T 0 t R 0
t e 0 t i 0 t e 0 (3.33)
tT 0 t R 0
t ml 0 t m 0 t i 0
t t
ln T 0 i 0
t R0 ti0
- P este un factor caracteristic al construciei prin care se ine seama de proporia ntre
capacitatea de transfer termic prin transmisie i cea prin infiltrare i exfiltrare de aer.
Pentru majoritatea construciilor colective factorul P ia valori n general n domeniul
0.80 0.90. Valoarea lui este funcie de ponderea infiltraiilor efective n raport cu
ponderea infiltraiilor considerate la dimensionare. n cazul studiului de fa s-a lucrat
cu P = 1.
- este un coeficient caracteristic corpurilor de nclzire, valoarea sa fiind ntre 0.28
si 0.33. Pentru acest studiu s-a adoptat valoarea = 0.3.
56
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
tT
Curbe Reglaj Termic Calitativ
tR
100
90
80
tT, tR (C)
70
60
50
40
30
20
-15 -10 -5 0 5 10
te (C)
Fig. 3.2 - Grafic reglaj termic calitativ pentru agentul termic secundar
tT temperaturile agentului termic pe tur; tR temperaturile agentului termic pe retur
Tab. 3.1
te (C) tT (C) tR (C)
-15 95.00 75.00
-10 86.27 69.13
-5 77.26 62.98
0 67.90 56.47
5 58.07 49.50
10 47.57 41.85
Cea mai important dintre cele dou curbe este curba temperaturii de tur a
agentului termic. Curba temperaturii de retur este realizabil mai mult sau mai puin, n
funcie de modul de funcionare al sistemului construcie instalaie n condiiile
solicitrilor variabile (fig.3.2).
Acordarea temperaturii agentului termic cu temperatura exterioar s-a considerat
c se face o singur dat pe zi, temperatura exterioar de reglaj fiind temperatura minim
a zilei, temperatura ce apare pe la ora 5-7 dimineaa.
n condiiile concrete de clim considerate pentru analiza pe care o ntreprindem n
cazul studiat, valorile temperaturilor de reglaj termic calitativ sunt cele prezentate n
tabelul 3.2:
57
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Tab. 3.2
Luna Temp. Temp. de Reglaj
Exterioar Calitativ (C)
Minim (C)
Octombrie 5.1 57.87
Noiembrie 1.3 65.40
Decembrie -1.6 70.94
Ianuarie -3.6 74.68
Februarie -4.1 75.61
Martie 0.3 67.33
Aprilie 6.5 55.01
58
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
tTS (oC)
Reglaj primar mixt
tRS (oC)
140
tTP (oC)
120 tRP (oC)
100
80
(oC)
60
40
20
0
-20 -15 -10 -5 te(oC) 0 5 10 15
59
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Tab. 3.3
o o o o o
Te ( C) tTS ( C) tRS ( C) tTP ( C) tRP ( C)
-15 90 70 130 80
-13 86.759 67.902 130 75.405
-11 83.482 65.767 130 71.23
-9 80.165 63.593 130 67.424
-7 76.805 61.376 130 63.939
-5.01 73.398 59.113 130 60.727
-4.99 73.398 59.113 101.97 66.255
-3 69.94 56.797 101.97 61.478
-1 66.425 54.425 101.97 57.295
1 62.845 51.988 101.97 53.593
1.99 61.029 50.744 101.97 51.89
2.01 61.029 50.744 81.601 55.886
4 57.337 48.195 81.601 50.955
6 53.556 45.556 81.601 46.828
6.99 51.627 44.198 81.601 44.993
7.01 51.627 44.198 66.484 47.913
8 49.669 42.812 66.484 45.226
9 47.679 41.393 66.484 42.862
10 45.653 39.939 66.484 40.758
rGS
Variatia Debitelor
rGP
1.1
0.9
0.8
(-)
0.7
0.6
0.5
0.4
-20 -15 -10 -5 0 5 10 15
te (0C)
60
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Tab. 3.4
o
te ( C) rGS rGP
-15 1 1
-13 1 0.864
-11 1 0.754
-9 1 0.662
-7 1 0.584
-5.01 1 0.516
-4.99 1 1
-3 1 0.811
-1 1 0.672
1 1 0.561
1.99 1 0.513
2.01 1 1
4 1 0.746
6 1 0.575
6.99 1 0.507
7.01 1 1
8 1 0.806
9 1 0.665
10 1 0.555
61
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
rGP=f(rGS)
1.2
1
0.8
rGP
0.6
0.4
0.2
0
0 0.2 0.4 0.6 0.8 1
rGS
Fig. 3.5 Influenta variatiei debitului agentului secundar asupra debitului de agent primar
Se observ din fig. 3.5 c modificrile de debit de agent termic secundar implic
modificri chiar ceva mai mari asupra debitului de agent termic primar. Aceste modificri
de debit se asociaz ns cu scderi ale temperaturii returului primar dup cum se observ
din fig. 3.6. Pe secundar temperaturile agentului termic rmn neschimbate, adic
conforme reglajului termic calitativ.
Din fig. 3.6. se observ c scderea temperaturii returului agentului termic primar
nu este foarte accentuat, ea fiind limitat de valoarea temperaturii returului pe secundar.
n fig. 3.6 se exemplific acest lucru pentru temperaturile exterioare: -15 oC, 0 oC i +10
o
C.
te=-15
Temperaturi retur primar
te=0
90 te=+10
80
70
60
50
(oC)
40
30
20
10
0
0 0.2 0.4 0.6 0.8 1 1.2
rGS
62
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Tab. 3.5
rGS rGP tRP (oC)
te=-15 te = 0 te = +10
1 1 80 58.929 42.796
0.9 0.858 77.565 57.539 42.1
0.7 0.621 73.624 55.286 40.974
0.5 0.424 71.098 53.843 40.253
0.3 0.25 70.086 53.264 39.963
0.1 0.083 70 53.215 39.939
63
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
64
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
W c tT t R k S t ml (3.34)
unde, aici, cu W s-a notat debitul volumic de agent termic vehiculat (m3/s).
sau:
tT t R
W c t T t R k S
t ti (3.35)
ln T
t R ti
Rezult de aici:
tT t i k S
ln NTU (3.36)
t R ti W c
t R ti
E exp NTU (3.37)
tT t i
t R0 ti0
E0 exp NTU 0 (3.38)
tT 0 t i 0
unde:
tT 0 t i 0
NTU 0 ln (3.39)
t R0 ti0
Valorile curente pentru NTU i E se pot exprima n funcie de valorile lor nominale:
65
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k S k S k W0 k k0
NTU NTU 0 (3.40)
W c W0 c k 0 W W W0
iar:
k k
k k0
0
W W0
(3.41)
Factorul F se definete din exprimarea puterii termice emise de instalaia de nclzire sub
forma:
k S t ml k S F tT t i (3.42)
de unde:
t ml 1 E 1 E
F (3.43)
tT t i NTU ln E
n consecin rezult:
k k0
1 E W W0
F 0
(3.44)
k k0
NTU 0
W W0
unde:
0.3
k t ml
(3.45)
k 0 t ml 0
n condiii nominale:
1
1 E0 1 E0 t t t t
F0 T 0 R0 ln T 0 i 0 (3.46)
NTU 0 ln E0 tT 0 t i 0 t R0 ti0
66
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
W0 c tT 0 t R 0 k 0 S F0 tT 0 t i 0 V G t i 0 t e0 (3.47)
t i 0 t e0 V G t t t t G G
S i 0 e 0 ln T 0 i 0 V C1 V (3.48)
tT 0 t i 0 k 0 F0 tT 0 t R 0 t R0 ti0 k0 k0
ti 0 t e0 G G
W0 V C2 V (3.49)
tT 0 t R 0 c c
Reglajul termic calitativ are ca obiectiv stabilirea temperaturilor agentului termic: tTr
i tRr n funcie de temperatura exterioar te. Pornind de la bilanul termic n regim
staionar:
k S F tTr t i 0 V G t i 0 t e (3.50)
rezult:
V G V G
tTr 1 ti0 te (3.51)
kS F k S F
67
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k S F W0 c 1 E W0 c 1 E0k k0 (3.52)
V G V G
tTr 1 t te
W0 c 1
E 0
k k0 i 0
W0 c 1
E k k0
0 (3.53)
t Rr E0k k0 tTr 1 E0k k0 t i 0 (3.54)
V G t t
T 0 R0 (3.55)
W0 c t i 0 t e 0
Acesta este cazul majoritar al cldirilor din centrele urbane din Romnia racordate
la sistemul centralizat de alimentare cu cldur. Pentru ele instalaia de nclzire central
a fost dimensionat conform precizrilor fcute mai nainte, iar reglajul termic este cel
calitativ uzual prezentat de asemenea mai nainte.
Aa cum s-a precizat reglajul termic calitativ nu ine seama de aporturile de
cldur interioare (degajri de cldur interioare) i exterioare (datorit radiaiei solare),
aporturi care sunt aleatoare i diferite de la o categorie de spaii la alta. Acest fapt face ca,
de regul, pe ntrega cldire s apar o ridicare a temperaturii interioare, dat fiind c
instalaia nu este dotat cu robinete termostatice. Obiectivul principal urmrit n acest
paragraf este de a stabili valoarea la care se va ridica temperatura interioar n aceast
situaie.
68
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k S F tTr ti a V G ti te (3.56)
V G V G a
1 t i tTr te (3.58)
kS F k S F k S F
a
ti ti0 (3.59)
k S F V G
unde:
V G V G
t i 0 tTr t e 1 (3.60)
k S F kS F
V G t t 1
T 0 R0 (3.61)
k S F t i 0 t e 0 1 E k k0
k S F k S F
t R 1 tTr ti (3.62)
W0 c W0 c
69
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k S F
1 E0k k0 (3.63)
W0 c
Fig. 3.7 - Variaia temperaturilor de-a lungul celor 7 luni clasice de sezon de nclzire
pentru oraul Bucureti
70
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Fig. 3.8 - Variaia temperaturilor de-a lungul celor 7 luni clasice de sezon de nclzire
pentru oraul Bucureti
n situaia n care reglajul termic calitativ se face dup cldirile din categoria 1,
consumul de cldur este maxim dat fiind c blocul este nereabilitat pe parte de
construcie i pe parte de instalaii. Din punct de vedere al evalurii teoretice, trebuie spus
c reglajul termic centralizat este potrivit situaiei ns nu se profit de aporturile
exterioare i interioare dat fiind existena vechilor robinete netermostatice, rezultnd o
ridicare a temperaturilor interioare.
Temperaturile exterioare prezentate n grafic reprezint valori convenionale
standardizate ce se gsesc n normativele n vigoare (STAS 4839) [10].
71
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k S F tTr t i 0 a V G t i 0 t e (3.64)
72
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k k0
W 1 E0
W W0 V G t t c t t (3.66)
i0 e a Tr i0
k S F k S F
t R 1 tTr ti0 (3.67)
W c W c
unde:
k k0
k S F
1 E0W W0 (3.68)
W c
73
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Fig. 3.9 - Diagram temperaturi pentru cldire reabilitat numai pe parte de instalaie
QCONS
QINC (3.69)
R
74
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k S F tTr ti a V G * t i t e (3.70)
75
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
a
t i t i* (3.72)
k S F V G*
unde:
V G* V G*
t i tTr
t e 1 (3.73)
k S F k S F
V G* V G G * tT 0 t R 0 1 G*
(3.74)
k S F k S F G t i 0 t e 0 1 E k k0 G
k S F k S F
t R 1 tTr ti (3.75)
W0 c W0 c
k S F
1 E0k k0 (3.76)
W0 c
76
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
Cldirile din aceast categorie sunt i mai puin numeroase. Aa cum s-a menionat
suprafaa de nclzire este excedentar iar reglajul termic este cel calitativ uzual. Dac i
instalaia de nclzire este modernizat i deci reglabil rezult o reducere important de
consum enegetic. Obiectivul urmrit este stabilirea debitului de agent termic necesar a fi
vehiculat prin instalaia de nclzire.
k S F tTr t i 0 a V G * t i 0 t e (3.77)
77
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
k k0
W 1 E0
W W0
V G * t t
i0 e a c t Tr t i 0 (3.79)
k S F k S F
t R 1 tTr ti0 (3.80)
W c W c
unde:
k k0
k S F
1 E0W W0 (3.81)
W c
78
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
*
QCONS
*
QINC (3.82)
R*
R* R (3.83)
*
QINC QCONS (3.84)
79
Capitolul 3 Modelarea comportamentului termic dinamic al sistemului cldire-instalaie de
nclzire. Reglajul termic calitativ centralizat
i de regul:
80
Capitolul 4 Achiziia si prelucrarea datelor experimentale
CAPITOLUL 4
ACHIZIIA I PRELUCRAREA DATELOR EXPERIMENTALE
81
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.1 - Schem de principiu instalaie punct termic cu o zon de presiune pentru ap
cald de consum i o zon pe nclzire
82
Capitolul 4 Achiziia si prelucrarea datelor experimentale
83
Capitolul 4 Achiziia si prelucrarea datelor experimentale
o Msurarea debitului
t down t up t
V K K
t up t down t2
(4.1)
t down = t A, B
t up = t B, A
V = Viteza medie a lichidului
t = Timpul de tranzit
K = Factorul de proporionalitate
o Msurarea temperaturilor
o Msurarea energiei
t t
E P(t ) dt K (TF ) DF (TF TR ) dt
0 0 (4.2)
84
Capitolul 4 Achiziia si prelucrarea datelor experimentale
unde:
E = energia
P(t) = puterea (ca funcie de timp)
K (TF ) = factorul de corecie al entalpiei (factorul K)
DF debit de agent pe tur
TF = Temperatura pe tur
TR = Temperatura pe retur
Pentru citirea datelor de la contoarele de energie termic din PT, este prevzut un
controller MBUS Link, de fapt un convertor extern de adaptare MBUS to RS232.
Utiliznd acest controller, datele transmise de contoarele legate n reeaua M-Bus pot fi
urmrite cu ajutorul unui calculator industrial ce dispune de un port serial RS232, la care
controller-ul este conectat. Citirea datelor se face la intervale periodice, n conformitate
cu setrile acceptate pentru calculatorul EAD [29].
Datele achizionate de la contoarele din PT au fost urmtoarele:
- Temperaturi (tur/retu primar PT, tur/retur INC, tur/retur ACM);
- Debite (circuitele primar PT, secundar INC, secundar ACM).
85
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Pentru citirea contoarelor de la blocuri este necesar o interfa serial RS232. Att
informaiile de la contoarele aflate n PT ct i informaiile achiziionate de la contoarele
scrilor de bloc, formeaz o baz de date distinct.
Prin intermediul comunicaiei MBUS, de la contoarele de energie au fost preluate
urmtoarele mrimi:
- Debitul proiectat;
- Index de energie;
- Index de volum;
- Putere termic instantanee;
- Valorile instantanee ale debitului i temperaturilor tur-retur;
- Diferena de temperatur;
- Timp de funcionare;
- Starea senzorilor de temperatur;
- Starea bateriei de alimentare.
86
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Mrimile achiziionate din proces prin intermediul reelei MBUS sunt procesate,
ordonate, arhivate i introduse ntr-o baz de date, pstrat local pe EAD (calculatorul
industrial al PT-ului). Pe baza valorilor n timp real ale mrimilor arhivate, s-au extras cu
ajutorul unui soft specializat (Net Bilan), datele de interes pentru ansamblul analizat,
acestea reprezentnd istoricul valorilor medii orare ale debitelor, temperaturilor tur/retur
i energia distribuit / consumat de sistem, pe perioada celor 3 sezoane de nclzire
succesive [28]. Aceste date s-au centralizat ntr-un fiier excel, un segment al acestuia
fiind prezentat n tab. 4.1.
Centralizatorul este alctuit pentru perioadele de nclzire ale iernilor 2007 / 2008;
2008 / 2009 i 2009 / 2010. Pentru fiecare sezon de nclzire sunt prezentate pe coloane
consumurile orare pentru punctul termic dup cum urmeaz:
- debit de agent termic pentru nclzire (m/h);
- temperatura tur nclzire (C);
- temperatura retur nclzire (C);
- diferena de temperatur (C);
- consumul de energie termic nregistrat de contorul comun al punctului termic
(Gcal).
Pentru cele 14 blocuri, datele prezentate sunt:
- debit de agent termic pentru nclzire (m/h);
- temperatur tur nclzire (C);
- temperatur retur nclzire (C);
- diferena de temperatur tur-retur (C);
- consumul de energie termic nregistrat de contorul comun al blocului locativ
(Gcal).
87
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.1
88
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Cldirile din prima categorie sunt cele care se ncadreaz n normele de proiectare
iniiale, ele fiind din punctul de vedere structural i cel al instalaiei interioare
nemodificate fa de stadiul n care au fost construite.
O a doua categorie de cldiri este reprezentat de cldiri la care s-au efectuat o
serie de reabilitri i modernizri pe parte de instalaii interioare.
A treia categorie de cldiri este constituit de acele cldiri care au suferit n ultimii
ani reabilitarea prii de construcie nsa nu s-au operat reabilitri sau modernizri ale
instalaiilor interioare.
A patra i ultima clas de cldiri este constituit de cldirile reabilitate termic att
pe parte de construcie, ct i pe parte de instalaii interioare.
Toate cele 4 categorii de cldiri au instalaiile interioare de nclzire central
dimensionate n condiiile specificate pentru cldirile din prima categorie adic: necesarul
de caldur de calcul stabilit pentru construcia nereabilitat i parametrii termici nominali
cei menionai nainte [10]. De asemenea instalaiile interioare de nclzire central din
oricare din cldiri este alimentat cu agent termic caracterizat de parametrii termici
conformi graficului de reglaj termic calitativ corespunztor clasei majoritare.
89
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.2
n fig. 4.3 este prezentat distribuia reelei secundare prin intermediul creia cele
14 blocuri de locuine sunt alimentate cu agent termic de la PT. Pentru BL.A7, cnd
acesta a suferit modificri numai din punctul de vedere al reabilitrii anvelopei, fr s
suporte mbuntiri i pe parte de instalaie, a fost utilizat codul de culoare roz iar pentru
BL.A1 care a beneficiat de reabilitare numai la nivelul instalaiei, s-a folosit codul de
culoare bleu.
90
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tabelul de mai jos (tab. 4.3) prezint datele tehnice referitoare la toate blocurile
aferente punctului termic, cele marcate cu cod de culoare galben reprezentnd imobilele
ce nu au beneficiat de reabilitri la nivel structural sau al instalaiei interioare de
distribuie energie termic.
91
Capitolul 4 Achiziia si prelucrarea datelor experimentale
92
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.4
93
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Diferena consumului specific ntre cldiri variaz de la cel mai sczut, q = 105.89
kWh/man BL.A13, pn la o valoare aproape dubl de q = 199.65 kWh/man
BL.A5.
n tab. 4.4 se poate observa gruparea consumurilor specifice lunare de cldur
pentru ncalzirea spaiilor cldirii n dou categorii i anume, blocuri cu suprafaa
echivalent termic situat n jurul valorii de 800 m (BL.A1; A2; A3; A6; A7; A8; A11;
A12; A13; A14) i blocuri cu SET n jurul a 400 m (BL.A4; A5; A9; A10).
Fig. 4.5 - Diagrama consumurilor lunare specifice de energie pentru nclzire la toate
blocurile aferente PT-ului, in iarna 2007 - 2008
94
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.6 - Diagrama consumurilor anuale specifice de energie pentru nclzire la toate
blocurile aferente PT-ului, in iarna 2007 - 2008
Consumurile specifice anuale de cldur, sunt prezentate grafic n fig. 4.6. Graficul
valorilor totale ale consumurilor relev cele dou grupe de cldiri, difereniate de SET.
Fig. 4.7 - Cronograma temperaturilor tur / retur nclzire la BL.A7 nereabilitat n iarna
2007 - 2008, valori comparative teoretic / experimental
95
Capitolul 4 Achiziia si prelucrarea datelor experimentale
96
Capitolul 4 Achiziia si prelucrarea datelor experimentale
- comparaie BL.A1 (CNR / INR) nereabilitat n iarna 2008 / 2009 i BL.A1 (CNR /
IR) reabilitat numai pe parte de instalaie n iarna 2009 / 2010;
- comparaie n aceeai iarn 2009 / 2010, pentru dou blocuri cu SET aproximativ
egale i debit de proiect identice i anume BL.A11 (CNR/INR) nereabilitat din
niciun punct de vedere i BL.A1 (CNR/IR) reabilitat pe parte de instalaie.
Tab. 4.5
Din tabelul 4.5 se observ c diferena consumurilor specifice anuale ntre cele
dou situaii de reabilitare ale cldirii variaz de la valoarea mai sczut q = 87.71
kWh/man BL.A1 (CNR/IR) pn la valoarea q = 116.21 kWh/man BL.A1
(CNR/INR). Valorile cumulate ale consumurilor relev o reducere cu aproximativ 25%
n varianta n care instalaia blocului a fost dotat cu robinete termostatice.
Datele din tabelul 4.5 au condus la reprezentarea grafic a consumurilor specifice
lunare pentru imobilul aflat n cele doua situaii analizate (fig. 4.8).
97
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.8 - Diagram consum lunar specific de energie pentru nclzire la BL.A1
(CNR/INR) nov 08 mar 09 / BL.A1 (CNR/IR) nov 09 mar 10
98
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.9 - Diagram consum anual specific de energie pentru nclzire la BL.A1
(CNR/INR) nov 08 mar 09 / BL.A1 (CNR/IR) nov 09 mar 10
99
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.10 - Cronograma consumului orar de energie pentru nclzire i debite la BL.A1
(CNR/INR) nov 08 mar 09 / BL.A1 (CNR/IR) nov 09 mar 10
Vom trece n revist succint liniile prezentate n fig. 4.10, pentru a putea comenta
comparativ rezultatele experimentale obinute.
Linia albastr linia debitului orar de agent termic de nclzire la BL.A1
nereabilitat;
Linia roie linia debitului orar de agent termic de nclzire la BL.A1 reabilitat
numai pe parte de instalaie;
Linia bleu linia consumului orar de energie pentru nclzire la BL.A1 reabilitat
numai pe parte de instalaie;
Linia maro linia consumului orar de energie pentru nclzire la BL.A1
nereabilitat.
Compararea rezultatelor experimentale obinute trebuie fcut urmrind grupurile
de linii albastru / maro (BL.A1 nereabilitat) i rosu / bleu (BL.A1 reabilitat pe parte de
instalaie). Astfel, se poate observa c atunci cand instalaia blocului a fost dotat cu
robinete termostatice, debitul de agent termic s-a redus (linia roie) fa de situaia n care
blocul era nereabilitat (linia albastr). Odat cu reducerea debitului, se poate observa c
pe medie, s-au redus i consumurile orare de energie termic (curba bleu) n raport cu
situaia n care blocul era nereabilitat (curba maro). Se poate trage deci concluzia c prin
posibilitatea de reglaj cantitativ se ine seama i de aporturile interioare i exterioare,
acestea contribuind la diminuarea puterii termice necesare a fi livrat la consumator.
Avnd n vedere c pentru cazul anterior s-a comparat practic acelai bloc n
situaii diferite de reabilitare dar n ani diferii, pentru a se elimina una dintre variabile i
anume media temperaturilor exterioare orare pentru cele dou sezoane de nclzire, s-a
efectuat compararea parametrilor experimentali pentru dou blocuri cu SET foarte
apropiate i debit de proiect identice (tab. 4.6), n acelai sezon de nclzire.
100
Capitolul 4 Achiziia si prelucrarea datelor experimentale
n tabelul de mai jos sunt prezentate datele tehnice pentru cele dou blocuri
analizate.
Tab. 4.6
Tab. 4.7
Din compararea valorilor consumurilor specifice pentru ntreg sezonul (tab. 4.7) se
observ c acestea variaz de la valoarea mai sczut q = 87.71 kWh/man BL.A1
(CNR/IR) pn la valoarea q = 118.09 kWh/man BL.A11 (CNR/INR). i din aceast
situaie analizat se observ o reducere a consumului de energie cu aproximativ 26% n
varianta n care instalaia blocului a fost dotat cu robinete termostatice.
Datele din tab. 4.7 au condus la reprezentarea grafic a consumurilor specifice
lunare pentru cele dou blocuri (fig. 4.11).
101
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.11 - Diagram consum lunar de energie pentru nclzire la BL.A11 (CNR/INR)
nov 09 mar 10 / BL.A1 (CNR/IR) nov 09 mar 10
102
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.12 - Diagram consum anual de energie pentru nclzire la BL.A11 (CNR/INR)
nov 09 mar 10 / BL.A1 (CNR/IR) nov 09 mar10
103
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Din grafic se observ c dac blocul a fost dotat cu robinete termostatice, prin
reducerea debitului din instalaie, diferena de temperatur a crescut (BL.A1 linia roie)
n raport cu situaia BL.A11 nereabilitat (linia albastr), n consecin rezultnd
diminuarea consumului de energie termic la blocul reabilitat.
104
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.8
105
Capitolul 4 Achiziia si prelucrarea datelor experimentale
106
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.9
Fig. 4.15 - Diagram consum lunar de energie pentru nclzire la BL.A7 (CNR/INR) nov
07 mar 08 / BL.A7 (CR/INR) nov 08 mar 09
107
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.16 - Diagram consum anual de energie pentru nclzire la BL.A7 (CNR/INR) nov
07 mar 08 / BL.A7 (CR/INR) nov 08 mar 09
108
Capitolul 4 Achiziia si prelucrarea datelor experimentale
109
Capitolul 4 Achiziia si prelucrarea datelor experimentale
110
Capitolul 4 Achiziia si prelucrarea datelor experimentale
n tab. 4.10 sunt prezentate datele tehnice pentru cele dou blocuri analizate.
Tab. 4.10
Tab. 4.11
111
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.19 - Diagram consum specific de energie pentru nclzire comparativ la BL.A2
(CNR/INR) si BL.A7 (CR / INR) - nov 08 / mar 09
112
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.20 - Diagram consum anual de energie pentru nclzire comparativ la BL.A2
(CNR/INR) si BL.A7 (CR / INR) - nov 08 / mar 09
113
Capitolul 4 Achiziia si prelucrarea datelor experimentale
114
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Din figura 4.22 se observ c n situaia n care BL.A7 a fost reabilitat pe parte de
construcie, diferena de temperatur (curba maro) s-a redus n raport cu cea a blocului
nereabilitat BL.A2 (curba bleu), debitul rmnd acelai pentru cele dou blocuri.
Procesul detaliat este prezentat n graficul de mai jos (fig. 4.23), graficul fiind
realizat pe baza temperaturilor retur nregistrate i a consumurilor rezultate pentru cele
dou blocuri.
115
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.12
n fig. 4.24 sunt prezentate grafic valorile consumurilor specifice lunare din tabel.
Din diagram se poate observa facil c BL.A7 care a beneficiat de reabilitare constructiv
(linia roz) a avut consumul specific lunar cel mai sczut n raport cu toate celelalte
blocuri.
116
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.24 - Diagrama consumului lunar de energie pentru nclzire la toate blocurile PT
ului - BL.A7 (CR/INR) - nov 08 / mar 09
Fig. 4.25 - Diagrama consumului anual de energie pentru nclzire la toate blocurile PT
ului - BL.A7 (CR/INR) - nov 08 / mar 09
117
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.13
118
Capitolul 4 Achiziia si prelucrarea datelor experimentale
neizolate. Acest lucru are consecine asupra temperaturii agentului retur secundar
nclzire care este mai ridicat la blocurile reabilitate fa de valorile de referin teoretice
impuse prin diagrama de reglaj. Acest fapt conduce la creterea temperaturii interioare n
blocurile reabilitate i care nu au n dotare robinete termostatice, instalaia fiind deci
supradimensionat. Consumul de energie termic se reduce (tab. 4.13) dar este evident
necesitatea robinetelor termostatice ce permit reglajul instalaiei funcie de temperatura
interioar.
119
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Tab. 4.14
Fig. 4.27 - Diagram consum lunar de energie pentru nclzire la BL.A7 (CNR/INR),
BL.A7 (CR/INR) si BL.A7 (CR/IR)
120
Capitolul 4 Achiziia si prelucrarea datelor experimentale
n figura 4.27 sunt prezentate consumurile specifice lunare pentru cele trei situaii
prezentate, pe baza valorilor din tab. 4.14.
Asfel, n ordine de sus n jos sunt reprezentate: linia consumurilor specifice lunare
la BL.A7 cnd acesta nu a fost reabilitat (linia galben), linia consumurilor specifice
lunare la BL.A7 cnd acesta a fost reabilitat numai pe parte constructiv (linia roz) i linia
consumurilor specifice lunare la BL.A7, cnd acesta a fost reabilitat din ambele puncte de
vedere (linia crem). n abscisa diagramei este timpul exprimat n luni iar n ordonat sunt
consumurile specifice exprimate n kWh/m.lun.
Dup cum se observ, consumurile specifice lunare au sczut treptat, n raport
direct cu diferitele grade de reabilitare la nivelul blocului analizat.
121
Capitolul 4 Achiziia si prelucrarea datelor experimentale
vedere.
n abscis este timpul exprimat n zile, n ordonat (stnga) este temperatura
exprimat n C iar n ordonat (dreapta) este debitul exprimat n m/h.
Compararea rezultatelor experimentale trebuie fcut urmrind perechile de linii
albastru / bleu (BL.A7 CR / INR) i rou / maro (BL.A7 CR / IR). Din cronogram se
observ c pentru cazul cldirii reabilitat din ambele puncte de vedere, odat cu
reducerea debitului de agent termic vehiculat n instalaie (linia maro) scade i
temperatura returului nclzire (linia roie).
Dac n cazul cldirii reabilitat numai pe parte constructiv debitul de agent nu s-
a modificat (linia bleu), singura diferen regsindu-se n creterea temperaturii returului
pe nclzire (linia albastr), situaie prezentat n subcapitolul anterior, n situaia cldirii
reabilitat din ambele puncte de vedere debitul este mult redus (linia maro), returul avnd
valori apropiate de temperaturile pe retur ale celorlalte blocuri (linia roie).
Cazul II: - comparaie a consumurilor specifice pentru toate blocurile n iarna 2009
2010 (sezon n care BL.A1 a fost reabilitat numai pe parte de instalaie iar BL.A7 a
beneficiat de reabilitare att pe parte de instalaie ct i pe parte de construcie, toate
celelalte blocuri fiind nereabilitate).
Tab. 4.15
122
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Din tabel se poate observa c cele mai sczute valori ale consumurilor specifice
pentru ntreg sezonul sunt la BLA7 (CR/IR) q = 57.69 kWh/man, urmnd n ordine
cresctoare BL.A1 (CNR/IR) - q = 87.71 kWh/man, consumul celorlalte categorii de
cldiri fiind maxim, ele nefiind reabilitate.
n tab. 4.16 se prezint distinct consumurile pentru BL.A1 (CNR/IR) i BL.A7
(CR/IR). Din consumurile specifice pentru toat perioada de nclzire, se observ c
BL.A7 reabilitat din ambele privine a avut un consum mai redus cu aproximativ 34%, n
comparaie cu BL.A1 reabilitat numai pe parte de instalaie.
Tab. 4.16
Consumurile specifice pentru cele dou situaii de reabilitare ale cldirii variaz
de la valoarea mai sczut q = 57.69 kWh/man BL.A7 (CR/IR) pn la valoarea q =
87.71 kWh/man BL.A1 (CNR/IR). Se observ c pentru acelai sezon de nclzire, n
situaia n care imobilul a fost reabilitat din ambele puncte de vedere, consumul anual de
nclzire s-a redus cu aproximativ 34% comparativ cu situaia n care cldirea a beneficiat
de reabilitare numai pe parte de instalaie.
Fig. 4.29 - Cronograma consumuri energie i debite nclzire la BL.A1 (CNR / IR) - nov
09 / mar 10 i BL.A7 (CR / IR) - nov 09 / mar 10
123
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Astfel, n grafic sunt figurate n ordine de sus n jos curbele de variaie pentru
urmtorii parametri:
Linia albastr linia debitului nclzire la BL.A1 reabilitat numai pe parte de
instalaie;
Linia roie linia debitului nclzire la BL.A7 reabilitat att pe parte de
construcie ct i pe parte de instalaie;
Linia bleu linia consumului orar de energie pentru nclzire la BL.A1 reabilitat
numai pe parte de construcie;
Linia maro linia consumului orar de energie pentru nclzire la BL.A7 reabilitat
din ambele puncte de vedere.
n abscis este timpul exprimat n zile, n ordonat (stnga) este energia exprimat
n Gcal/h iar n ordonat (dreapta) este debitul exprimat n m/h.
124
Capitolul 4 Achiziia si prelucrarea datelor experimentale
Fig. 4.30 - Diagram consum lunar de energie pentru nclzire la 2 blocuri la BL.A1
(CNR / IR) - nov 09 / mar 10 i BL.A7 (CR / IR) - nov 09 / mar 10, comparativ cu toate
celelalte blocuri ale PT-ului (CNR / INR)
Fig. 4.31 - Diagram consum anual energie pentru nclzire la 2 blocuri la BL.A1 (CNR /
IR) - nov 09 / mar 10 i BL.A7 (CR / IR) - nov 09 / mar 10, comparativ cu toate celelalte
blocuri ale PT-ului (CNR / INR)
125
Capitolul 4 Achiziia si prelucrarea datelor experimentale
n fig. 4.31 este reprezentat consumul anual de energie pentru nclzire la toate
blocurile ce sunt alimentate de PT, pentru iarna 2009-2010, aceasta dnd o imagine
general a reducerii consumului de energie termic pe tot sezonul de nclzire pentru
variantele de reabilitare studiate, BL.A1 (CNR/IR) i BL.A7 (CR/IR) avnd cele mai mici
consumuri n raport cu celelalte blocuri.
Tab. 4.17
126
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
CAPITOLUL 5
MSURI I SOLUII PRIVIND EFICIENTIZAREA
ALIMENTRII CU CLDUR A DIVERSELOR TIPURI DE
CONSUMATORI RACORDAI LA SISTEMUL CENTRALIZAT
DE DISTRIBUIE A AGENUTLUI TERMIC
127
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
exterioare;
- Avariile afecteaz o zon deservit mai mic;
- Cheltuieli de exploatare reduse;
- ntreinere mai puin specializat;
- Construcia compact permite amplasarea n spaii mici.
128
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
129
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Fig. 5.1 - Staie termic compact cu schimbtor de cldur pentru nclzire i prepararea
apei calde n boiler cu serpentina nclzitoare legat n paralel cu nclzirea
Fig. 5.2 - Staie termic compact cu legare serie-paralel pentru prepararea agentului
termic de nclzire i a apei calde ntr-o treapt fr acumulare
130
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Fig. 5.3 - Staie termic compact cu schimbtor de cldur pentru nclzire i legarea n
paralel a unui al doilea schimbtor de cldur pentru prepararea apei calde cu acumulare
Fig. 5.4 - Staie termic compact cu schimbtor de cldur pentru nclzire i legarea n
paralel cu nclzirea a unui al doilea schimbtor de cldur pentru prepararea apei calde
cu acumulare; varianta cu robinet cu 3 ci
131
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Fig. 5.5 - Staie termic compact cu legare serie-paralel pentru prepararea agentului
termic de nclzire i a apei calde de consum, n dou trepte, fr acumulare
Fig. 5.6 - Staie termic compact cu schimbtor de cldur pentru nclzire i boiler legat
n paralel pe primar pentru prepararea apei calde
132
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Fig. 5.7 - Staie termic compact cu schimbtor de cldur pentru nclzire i boiler legat
n paralel pe secundar pentru prepararea apei calde
Fig. 5.8 - Staie termic compact pentru prepararea apei calde n 2 trepte fr acumulare
legate serie-paralel cu instalaia de nclzire care este alimentat direct din circuitul
primar
133
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Fig. 5.9 - Staie termic compact cu legturi serie-paralel pentru prepararea agentului
termic de nclzire i a apei calde n 2 trepte fr acumulare
Fig. 5.10 - Staie termic compact cu legturi serie-paralel pentru prepararea agentului
termic i a apei calde ntr-o treapt cu acumulare
134
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Fig. 5.11 - Staie termic compact pentru prepararea apei calde n 2 trepte cu acumulare,
legate serie-paralel pe primar cu instalaia de nclzire
Fig. 5.12 - Staie termic compact cu legaturi serie-paralel pentru prepararea agentului
termic de nclzire i a apei calde n 2 trepte cu acumulare
135
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Fig. 5.13 - Staie termic compact pentru prepararea apei calde cu 2 rezervoare de
acumulare
136
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Staiile termice compacte pot fi clasificate n 2 grupe mai importante, fiecare din
ele coninnd mai multe tipuri de scheme.
Vom prezenta i analiza pe rnd, n continuare, fiecare din tipurile de staii termice
compacte menionate.
137
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Din fig. 5.15 se observ c sistemul este compus din dou seciuni: seciunea de
nclzire i seciunea de preparare a apei calde, seciuni care sunt legate n paralel i
independente din punct de vedere funcional.
Descrierea relaiilor corespunztoare de bilan termic pe componentele sistemului:
nclzire i apa cald, se va face n ipoteza c debitul pe circuitul de amestec al nclzirii
este nul i la fel debitul de ap cald pe circuitul de recirculare este i el nul. Se adopt
aceste simplificari pentru a nu introduce posibile confuzii n bilanurile termice ale celor
dou componente principale: nclzirea i apa cald.
Bilanul termic pe partea de nclzire conduce la:
unde:
E I exp( NTU I )
138
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
(kS) I
NTU I
G P _ INC c
(1 y) E S 1 ES
t RP _ ACM tTP t AR
1 yE S 1 yE S
(5.2)
(1 E S ) y 1 y
t AC tTP t AR
1 yE S 1 yE S
unde:
(kS) S
NTU S (5.3)
GP _ ACM c
GCONS
y
G P _ ACM
GP _ INC GP _ ACM
t RP t RP _ INC t RP _ ACM (5.4)
GP GP
unde:
GP GP _ INC GP _ ACM
139
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
140
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
dt AC
GP _ ACM c (tTP t RP _ ACM ) d _ GCONS c (t AR t AC ) d V c d (5.6)
d
Fcnd notaia:
sau:
dt AC 1 1
t AC t (5.9)
d CT CT
unde:
V
CT
GP _ ACM (1 E S ) GCONS
141
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
1
t AC t (t AC0 t ) exp
CT
1
sau fcnd notaia: E exp
CT
rezult:
t AC E t AC0 (1 E ) t (5.10)
unde:
QACM _ C GCONS c (t AC t AR )
142
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Puterea termic acumulat este diferena ntre cele dou puteri termice
menionate mai nainte;
(1 y) E S 1 ES
t RP _ ACM tTP t AC
1 yE S 1 yE S
(5.11)
(1 E S ) y 1 y
tTS _ ACM tTP t AC
1 yE S 1 yE S
unde:
143
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
(kS) S
NTU S (5.12)
GP _ ACM c
GS _ ACM
y
G P _ ACM
dt AC
GS _ ACM c (tTS _ ACM t AC ) d GCONS c (t AR t AC ) d V c d (5.13)
d
nlocuind n (5.13) expresia lui tTS _ ACM din relaia (5.12) se obine ecuaia
diferenial liniara de ordinul I:
y (1 E S ) y (1 E S )
GS _ ACM GCONS GS _ ACM
dt AC 1 yE S 1 yE S G
t AC tTP CONS t AR (5.14)
d V V V
y (1 E S )
GS _ ACM tTP GCONS t AR
1 yE S
t
y (1 E S )
GS _ ACM GCONS
1 yE S
V
CT
y (1 E S )
GS _ ACM GCONS
1 yE S
dt AC 1 1
t AC t
d CT CT
144
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
cu soluia:
t AC E t AC0 (1 E ) t
1
unde: E exp , constanta de timp CT avnd noua expresie.
CT
Utiliznd relaiile (5.12) i (5.11) se stabilesc temperaturile tTS _ ACM i t RP _ ACM i
mai departe t RP folosind temperatura de ntoarcere pe partea de nclzire.
Furnizat la consumator:
QACM _ C GCONS c (t AC t AR )
Acumulat n rezervor este diferena dintre cele dou mai sus menionate.
Fig. 5.18 - Schem cu conectare indirect a nclzirii i preparare instantanee a apei calde
145
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Pe seciunea de nclzire:
Bilanul termic n regim staionar al schimbtorului de cldur conduce la:
unde:
(kS) S _ INC
NTU S _ INC (5.16)
GP _ INC c
GS
y INC
G P _ INC
t RS E I tTS (1 E I ) t i (5.17)
unde:
E I exp( NTU I )
(kS) I
NTU I
GS c
146
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
Se obine:
E S _ INC (1 y INC ) 2
( y INC E S _ INC ) E I
(1 E S _ INC ) y INC (1 E I )(1 E S _ INC )
t RP _ INC tTP ti
(1 E S _ INC ) y INC (1 E I )(1 y INC ) (1 E S _ INC ) y INC (1 E I )(1 y INC )
147
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
(1 yTR 2 ) E S _ TR 2 1 E S _ TR 2
t RP _ TR 2 tTP t AI
1 yTR 2 E S _ TR 2 1 yTR 2 E S _ TR 2
(5.18)
(1 E S _ TR 2 ) yTR 2 1 yTR 2
t AC tTP t AI
1 yTR 2 E S _ TR 2 1 yTR 2 E S _ TR 2
148
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
GP _ TR 2 GP _ INC
tTP _ TR1 t RP _ TR 2 t RP _ INC (5.19)
GP GP
149
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
150
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
i n cadrul acestei scheme cele dou seciuni sunt independente din punct de
vedere al analizei i fiecare dintre ele a fost tratat n cadrul schemelor anterioare. Astfel
nclzirea n cadrul schemei 5.18 i prepararea apei calde n cadrul schemei 5.17, unde se
gsesc i expresiile corespunztoare ale puterilor termice.
O analiz interesant care trebuie efectuat i acest lucru este posibil pe baza
relaiilor de lucru prezentate, vizeaz schemele cu acumulare pe partea de ap cald i se
refer efectiv la proporia optim ntre mrimea schimbtorului de cldur i volumul de
acumulare.
151
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
cauze permanente
- evi parial obturate cu nmol sau tartru;
- reea de distribuie i corpuri de nclzire prost dimensionate;
- consecina unei reabilitri termice (pe parte de construcie);
- consecina montrii robinetelor cu termostat pe corpurile de nclzire;
152
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
153
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
154
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
155
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
156
Capitolul 5 Msuri i soluii privind eficientizarea alimentrii cu cldur a diverselor tipuri
de consumatori racordai la sistemul centralizat de distribuie a agentului termic
157
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
CAPITOLUL 6
CONCLUZII GENERALE, CONTRIBUII ORIGINALE,
POSIBILITI DE VALORIFICARE A REZULTATELOR
OBINUTE
Tab. 6.1
158
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
Tab. 6.2
Din tab. 6.1; 6.2 se observ c, la o cldire colectiv, un efect benefic important n
sensul economiei energetice se obine dac se reabiliteaz modernizeaz instalaiile
interioare. Nu este deloc de neglijat importana creterii gradului de izolare termic al
cldirii, ns dac nu se opereaz i reabilitarea modernizarea instalaiilor, rentabilitatea
soluiilor de izolare termic este periclitat.
Fig. 6.1 - Consumul specific anual de cldur pentru nclzire prelevat din experiment,
pentru toate variantele de reabilitare
159
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
160
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
161
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
162
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
163
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
164
Capitolul 6 Concluzii generale, contribuii originale, posibiliti de valorificare a
rezultatelor obinute
165
Bibliografie
166
[15] Iordache F., Baltaretu F., Modelarea i simularea proceselor termice, dinamice. Editura
Conspress, 2005;
[16] Iordache F., Pun V., The thermal dynamic behaviour of a building - Scientific Journal
Mathematical Modelling in Civil Engineering. UTCB - 2011 (in curs de publicare);
[17] Iordache F., Ionescu M., Paun V., Efficiency of a districtual central heating system -
Scientific Journal Mathematical Modelling in Civil Engineering, UTCB - 2011 (in curs de
publicare);
[18] Istoria casei. Disponibil pe - http://www.incasa.ro/Istoria_casei_2977_581_1.html.
[19] Istoria locuinelor ecologice. Disponibil pe -
http://www.scritube.com/stiinta/arhitectura-constructii/ISTORIC-LOCUINTELE-
ECOLOGICE92863.php.
[20] Mateescu Th., Consideraii privind eliberarea hidraulic a buclelor de reglaj n
instalaiile de nclzire cu corpuri statice. Revista INSTALATORUL nr. 5 /2004.
[21] Metodologie de calcul al performanei energetice a cldirilor partea a II-a. Disponibil pe -
http://www.scribd.com/doc/24413852/Mc-001-1-2-3-Metodologie-Calcul-Performanta-
Energetica.
[22] Mladin E.C., Georgescu M., Duianu D., Eficiena energiei n cldiri Situaia n
Romnia i acquis-ul comunitar, Bucureti 2004;
[23] Pavel V., Vasilache M., Cherches M., Consideraii asupra economiei de energie n
cldirile din Romnia (1974-2004);
[24] Pun V., Modelarea proceselor termohidraulice care au loc n punctele termice i reele
de distribuie Raport cercetare doctorat 1 - 2008;
[25] Pun V., Cercetri experimentale privind comportamentul termic dinamic al sistemelor de
nclzire districtual. Raport cercetare doctorat 2 2009;
[26] Pun V., Reglajul calitativ i cantitativ n cadrul sistemelor de nclzire districtual.
Cercetri teoretice i experimentale. Raport cercetare doctorat 3 2009.
[27] Pun V., Iordache F., Performana energetic a cldirilor - A VIII-a conferin naional
de echipament termomecanic clasic i nuclear i energetic urban&rural - UPB - 2009;
[28] Pun V., Iordache F., Prelevarea i prelucrarea datelor n sistemele centralizate de
alimentare cu cldur - A XIV-a conferin de confort, eficien, conservarea energiei i
protecia mediului - UTCB - 2007;
[29] Pun V., Iordache F., Prelucrarea numeric a parametrilor achiziionati de la un sistem
de nclzire districtual - A XV-a conferin de confort, eficien, conservarea energiei i
protecia mediului - UTCB - 2008;
[30] Pun V., Iordache F., Reglajul calitativ i cantitativ n cadrul sistemelor de nclzire
districtual. Cercetari teoretice i experimentale - A XVI-a conferin de confort, eficien,
conservarea energiei i protecia mediului - UTCB - 2010;
167
[31] Pierderi de cldur prin perei exteriori. (17.03.2010). Disponibil pe - http://blog.solutii-
eco.ro/pierderi-de-caldura-prin-pereti-exteriori/.
[32] Popescu I., Echilibrarea hidraulic i termostatarea, elemente vitale n contorizarea
cldurii. Tehnica instalaiilor. Editura Minos 2006. Disponibil pe -
http://www.tehnicainstalatiilor.ro/articole/nr_05/nr05_art.asp?artnr=06.
[33] Program de dezvoltare a Municipiului Bucureti, 2008 2009; (pag. 104-105).
Disponibil pe
http://www.pmb.ro/primarul/prioritati_proiecte/proiecte_2000_2008/docs/90-111.pdf.
[34] Regulamentul pentru furnizarea i utilizarea energiei termice, aprobat prin Hotararea
Guvernului nr. 425/1994. Disponibil pe - http://www.legestart.ro/Decizia-213-2001-referitoare-
exceptia-neconstitutionalitate-dispozitiilor-art-29-Regulamentul-furnizarea-utilizarea-energiei-
termice-aprobat-prin-Hotararea-Guvernului--(NDUwNTE-).htm.
[35] Romanian statistical yearbook, 2003;
[36] Rotaru C., Preda M., Eficiena energetic un element al dezvoltrii durabile,
Simpozionul: Energia Sursa de dezvoltare economic, Bucureti 2004;
[37] Sarbu I., Kalmar F., Efectele reabilitrii termice a cldirilor. Consideraii teoretice.
Disponibil pe - http://tehnicainstalatiilor.ro/articole/pdf/nr_55/04.pdf.
[38] Vasilache M., Contribuii la modernizarea fondului construit existent prin creterea
performanelor higrotermice, Tez de doctorat, Iai 1997.
168
ANEXE
169
ANEXA 1
170
ANEXA 2
171
ANEXA 3
172
ANEXA 4
173
ANEXA 5
2
Rezistene termice specifice R[m K/W] pentru elemente de construcii vitrate