Sunteți pe pagina 1din 30

INSTALAII PENTRU PROTECIA OMULUI MPOTRIVA

TENSIUNILOR ACCIDENTALE DE ATINGERE


Prof. dr. ing. Ioan BORZA . l. dr. ing. Barbu NICOAR
Universitatea "Politehnica" din Timioara

DEVICES TO PROTECT HUMANS AGAINST ACCIDENTAL


TENSIONS INDUCED BY TOUCH
Abstract
The paper presents the effects of the electrical current on the human
body and its possible consequences. Also, the paper present electrocution
cases induced by direct or indirect touch.
In the paper are presented protection measures against direct and
indirect touch, basic and supplementary methods to avoid accidents of this
type. In all cases is recommended to wear individual protection equipment:
electroinsulating gloves, boots and vests, as well as protection glasses.
The formulas indicate recommended values for the insulating
resistance (Riz)of the electrical system and for the dispersion resistance (Rp) of
the earth plug in the earth binding system.
In the table are presented the maximal touch tensions (Ua) and step
tensions (Upas) according to the use, equipment, and the type of electrical
current passing the system.

1.Probleme generale
Atunci cnd ntre dou puncte ale corpului exist o diferen de
potenial, prin corp va trece un curent electric. Corpul omenesc se
comport ca o impedan (fig. 1) a crei valoare este variabil, pentru
aceeai persoan, n funcie de:
poziia celor dou puncte de pe suprafaa corpului ntre care

exist diferena de potenial, deci de traseul curentului electric prin


corp;
de starea de sntate a acestuia. Un organism bolnav are o
impedana mai mic la trecerea curentului.
de umiditatea pielii corpului. Cu ct pielea este mai uscat cu
att Zt este mai mare, n caz contrar, valoarea Zt scade foarte mult. n
figura 2 se indic variaia, n procente, (dup norma CEI 479-1) a
impedanei corpului, n funcie de traseul curentului electric, n raport cu
impedana corpului pe traseul "mn-mn".
Cifrele fr paranteze corespund traseului curentului de la
mn, la partea considerat a corpului.
Cifrele n paranteze corespund traseului dintre ambele mini i
partea corespunztoare a corpului.
De exemplu: impedana dintre o mn i laba piciorului este
100 %, iar impedana dintre ambele mini i laba piciorului este 75 %
din impedana dintre cele dou mini. Totodat, impedana total a
corpului uman este mult influenat i de tensiunea de contact aa cum
se vede n figura 3. Cele trei curbe corespund procentelor de 5, 50 i,
respectiv, 95 % din numrul total al subiecilor pentru care nu se
depete valoarea impedanei din grafic.
Corpul omului poate ajunge sub tensiune prin atingerea unor
pri ale instalaiei electrice aflate sub tensiune.

Fig. 1 Impedana corpului uman:


Zp1, Zp2 a pielii; Zi intern; Zt total.

Atingerile pot fi:

directe, cnd omul vine n contact cu pri din instalaia


electric care, n regimul normal de funcionare, se afl sub tensiune;
indirecte, cnd omul vine n contact cu pri sau piese ale
unor echipamente sau instalaii care n mod normal nu se afl sub
tensiune, dar care au ajuns sub tensiune n urma unui defect sau a
altor cauze accidentale. Exemple de atingeri indirecte ar fi: atingerea
carcaselor metalice ale electromotoarelor, cutiilor metalice ale
tablourilor electrice, pupitrelor sau panourilor electrice, conducte de ap
etc. care, n mod accidental, ar putea ajunge sub tensiune.
Tensiunea la care este supus omul n cazul unor atingeri
indirecte se numete de atingere. n caz particular dac aceasta este
aplicat tlpilor omului (aflat n apropierea unei prize de pmnt sau
unui conductor al unei linii aeriene czute la pmnt) aceasta se
numete tensiune de pas.
2. Efectele curentului electric asupra corpului uman
Cele mai importante dintre efectele pe care le poate produce
curentul electric la trecerea lui prin corpul uman, atunci cnd se
depete o anumit valoare a curentului, sunt:

Fig. 2 Impedana corpului n funcie de traseul curentului


electrotraumatisme ce constau din arsuri sau metalizri ale
epidermei, prin ptrunderea stropilor de metal topit sub aciunea arcului
electric; Arsurile pot fi superficiale n locurile unde curentul electric intr
i iese din corp, dar pot fi i intense, atunci cnd ating organele interne
ale corpului. Acestea din urm pot provoca chiar ncetarea din via.
electroocurile (electrocutrile) ce se produc prin aciunea
curentului asupra sistemului nervos i pot avea diferite aspecte, n
funcie de intensitatea curentului, traseul prin corp i durata acestuia.
Electroocurile constau n:
zguduiri sau contracii;
pierderea temporar a auzului sau vocii;

paralizia temporar a centrilor nervoi respiratori (oprirea


respiraiei);
paralizia temporar a inimii i fibrilaia (contracia neregulat a
fibrelor musculare).
Prin acordarea unui ajutor adecvat:
respiraie artificial;
masaj cardiac,
victima poate fi reanimat, adesea, dup un timp ndelungat de la
producerea morii aparente.
Efectele cele mai periculoase le d curentul electric de
frecven industrial (40...60 Hz) la care se produc convulsii ce fac ca
omul s nu se poat elibera de sub aciunea curentului. La frecvene
foarte nalte (peste 400 Hz) nu se mai produc electrocutri, iar
electrotraumatismele sunt dependente de valoarea curentului. Limita
maxim a curenilor nepericuloi care pot trece prin corpul omului este
de 50 mA, n curent continuu, i 10 mA, n curent alternativ de 50 Hz.

Fig. 3. Valorile statistice ale impedanei totale a corpului omenesc,


valabile pentru subiecii vii, pe traseul mn-mn, n funcie de
tensiunea de contact
Efectele curentului electric depind de mai muli factori ca i de
simultaneitatea realizrii lor:
timpul ct trece curentul electric prin organism. n figura 4 se

indic probabilitatea ca inima s intre n fibrilaie n funcie de mrimea


curentului i durata trecerii acestuia prin corp.

Fig. 4. Zonele ce delimiteaz efectele patofiziologice la trecerea


curentului prin om (dup norma CIE 479-1):
zona 1 (n stnga dreptei a): n mod normal, nu se produce nici o reacie; zona
2 (ntre curbele a i b): n mod normal, nu se produce nici un efect fiziologic
periculos; zona 3 (ntre curbele b i c1): n mod normal, nici un pericol organic;
efectele (contraciile musculare) sunt reversibile ele fiind influenate de
intensitatea curentului i durata de trecere; zona 4 (la dreapta curbei c1):
fibrilaia inimii, este, probabil, n funcie de intensitatea curentului i durata lui
de trecere; de asemenea, este de prevzut s apar i efecte fiziopatologice
grave.

Curba C1 indic condiiile n care, la trecerea curentului, inima


nu intr n fibrilaie. Condiiile corespunztoare curbei C2 indic
probabilitatea de 5 % ca inima s intre n fibrilaie, iar curba C3,
condiiile pentru o probabilitate de 50 %.
De exemplu, un curent alternativ de peste 50 mA dac trece
prin organele vitale (inima) un timp mai mare de 0,1...0,2 s poate fi
mortal.
impedana total a corpului uman. Aceasta este compus din
rezistena la intrare i ieire din corp i rezistena organismului (fig. 1).

Primele dou sunt mult influenate de echipamentul omului n momentul


punerii sub tensiune. Cu ct este mai bine izolat cu att efectele
curentului electric vor fi mai reduse sau chiar nule. Impedana
organismului este format, n cea mai mare parte, din impedana pielii
ce are valori de 40...100 k. Dar conductivitatea epidermei poate
crete mult datorit umiditii de la suprafaa acesteia datorit
transpiraiei sau umiditii din atmosfer, strii febrile a organismului
etc. Astfel impedana organismului poate scdea la 600...1000 . La
strpungerea pielii cnd tensiunea depete 60...100 V) impedana
organismului scade i mai mult ajungnd la 200 . Rezult c n
situaiile defavorabile (ncperi cu pardoseal bun conductoare,
umiditate mare n aer, aer cu praf conductor etc.) se pot produce
accidente grave chiar la tensiuni de valoare mic (zeci de voli).
traseul curentului prin corpul omului (fig. 2);
factorii de natur personal, cum ar fi starea fizic a omului,
gradul su de atenie n momentul punerii sub tensiune etc.
3. Cazuri de electrocutare
Reelele electrice trifazate de joas tensiune pot fi:
legate la pmnt (fig. 5) sau
izolate fa de pmnt (fig. 6).

Fig. 5. Reea legat la pmnt


(PPE priza de pmnt de exploatare)

Fig. 6. Reea izolat fa de pmnt


Reelele legate la pmnt (fig. 5) sunt utilizate, practic, n
exclusivitate, n instalaiile de joas tensiune. Dup cum se va vedea,
aceste reele sunt deosebit de periculoase din punctul de vedere al
electrocutrii omului. Totui sunt foarte utilizate deoarece neutrul reelei
legat la pmnt ofer tensiune constant ntre fazele reelei si neutru,
indiferent de natura sarcinii echilibrat sau dezechilibrat.
Reelele izolate fa de pmnt (fig. 6) sunt utilizate rar, atunci
cnd este alimentat un receptor de putere mare sau un grup redus de
receptoare cu sarcinile identice pe faze. Indiferent de modul de
execuie a reelelor aerian, subteran sau conducte montate n tuburi
de protecie, ntre fiecare linie electric i pmnt, exist o impedana
ce poate fi mai mare sau mai mic, n funcie de caracteristicile
straturilor de izolaie dintre linie i pmnt (fig. 6). Astfel, nici reelele
izolate fa de pmnt nu sunt complet izolate fa de acesta.
Impedana dintre fiecare linie i sol este uniform distribuit n lungul
reelei. Pentru uurina explicaiilor acestea se vor considera
concentrate (fig. 6).
Cazuri de electrocutare prin atingere direct
Atingerea simultan a unei linii electrice i a pmntului sau a
dou dintre liniile reelei (fig. 7) provoac trecerea unui curent electric
prin om.
Indiferent de tipul reelei, dac omul intr n contact cu una din
fazele acesteia i se afl n legtur direct cu pmntul (fig. 7a i b),
prin corpul acestuia va trece un curent electric a crui valoare depinde
de impedana circuitului ce se formeaz. Deoarece rezistentele de
izolaie Ziz (fig. 7b) au, n general, valori mari, curentul prin om, n cazul
atingerii unei faze a unei reele izolate fa de pmnt, va fi mai mic
fa de curentul ce trece prin om la atingerea unei faze dintr-o reea
legat la pmnt (fig. 7a). Din punct de vedere al pericolului de
electrocutare rezult c reeaua legat la pmnt este mult mai
periculoas.

Fig. 7. Cazuri de electrocutare prin atingere direct:


a unei faze dintr-o reea legat la pmnt; b unei faze dintr-o reea izolat
fa de pmnt; c a dou faze ale unei reele legate la pmnt; d a dou
faze ale unei reele izolate fa de pmnt.

n cazul atingerii simultane a dou dintre fazele reelei (fig. 7c i


d), indiferent de tipul reelei, curentul prin om este acelai. Reelele, n
acest caz, sunt la fel de periculoase pentru om.
Pentru a evita asemenea cazuri de electrocutare, omul trebuie
s utilizeze echipamentul special de protecie individual. Acesta este
format din mnui, cizme i or electroizolante care, n prealabil, au
fost verificate c au rezistena de izolaie corespunztoare. Utiliznd
acest echipament, omul va putea interveni n instalaiile electrice numai
sub supravegherea unui partener de lucru care i va dirija aciunile din
aproape n aproape.
Cazuri de electrocutare prin atingere indirect
Acestea se produc atunci cnd omul atinge pri metalice ale
unor utilaje, echipamente sau corpuri care au ajuns sub tensiune, n
mod accidental. De exemplu, stelajul metalic al unui tablou electric,

carcasa unui motor electric, carcasa unei maini de splat rufe etc.
care, n mod normal, nu se afl sub tensiune. Din cauza unui defect,
acestea pot ajunge sub tensiune i, la atingerea lor, de ctre un om
care are picioarele pe un suport bun conductor de electricitate i n
contact cu pmntul l vor pune pe acesta sub tensiune.
Defectele cele mai frecvente ce conduc la astfel de situaii sunt:
desprinderea uneia sau mai multor faze din circuitele
electrice, datorit unor solicitri mecanice dinamice sau accidentale;
defecte de izolaie ale conductoarelor de faz.
Acestea la rndul lor se pot datora: mbtrnirii izolaiei (fie
datorit mbtrnirii naturale, fie datorit suprasarcinilor repetate la care
a fost supus conductorul n timp, distrugerii izolaiei n unul sau mai
multe locuri (datorit unor fore mecanice: loviri, tasri ale construciei
etc. sau aciunii unor roztoare) sau chiar unor defecte de execuie a
izolaiei ce nu au fost observate la montare.
n figura 8 sunt prezentate cazurile frecvente de electrocutare
prin atingere indirect n reelele legate la pmnt.

Fig. 8. Cazuri de electrocutare prin atingerea indirect a carcasei:


a unui motor; b unei maini de splat rufe.

n cazurile prezentate, carcasele metalice ale celor dou


receptoare au ajuns sub tensiune datorit contactului electric cu una
din fazele reelei. Atunci cnd omul atinge o astfel de carcas i, n
acelai timp, o alt parte a corpului (cel mai adesea, picioarele) se afl
n contact cu solul, prin corpul omului va trece un curent. Traseul
acestuia (fig. 8) cuprinde: transformatorul de alimentare a reelei de
joas tensiune, faza defect, carcasa receptorului la care s-a produs
defectul, omul, elementele de construcie bune conductoare de
electricitate, solul, priza de pmnt de exploatare a transformatorului,
transformatorul (bobinajul fazei pe care s-a produs defectul). Cu ct
impedana acestui traseu este mai mic cu att curentul care trece prin
om va fi mai mare i efectele lui mai grave.
Dac reelele din figura 8 ar fi izolate fa de pmnt (ca n fig.
7b i d) circuitul electric s-ar nchide prin impedanele de izolaie ale
fazelor nedefecte.
Rezult c, indiferent de tipul reelei, pericolul de electrocutare,
la atingerea unor pri metalice ajunse accidental sub tensiune, exist.
4. Clasificarea ncperilor i receptoarelor din punct de
vedere al pericolului de electrocutare
Curentul care trece prin corpul omului depinde de impedana
circuitului ce se stabilete n cazul unei atingeri indirecte a reelei.
Impedana circuitului, la rndul su, este dependent att de contactul
dintre corpul omului i receptorul defect ct i de contactul dintre corpul
omului i prile bune conductoare ale construciei din ncperea n
care acesta se afl.
n funcie de pericolul de electrocutare, ncperile se clasific n
urmtoarele categorii:
puin periculoase acestea sunt ncperi uscate i nclzite,
cu pardoseala izolant i fr construcii metalice n apropierea
instalaiilor electrice. Exemple: camerele de zi i dormitoarele din
locuine, birourile din cldirile administrative etc.;
periculoase acestea sunt ncperile care ndeplinesc cel
puin una din urmtoarele condiii:
temperatura este n permanen ntre 20 i 30 C;
n ncpere exist permanent praf bun conductor de
electricitate;
n ncpere se afl construcii metalice n apropierea
instalaiilor electrice fr ecrane protectoare;

pardoseala este bun conductoare de electricitate (pmnt,


beton, crmid, metal, lemn umezit continuu din cauza procesului de
producie);
umiditatea este cuprins ntre 75 i 97 %;
n ncpere se manevreaz cu gaze sau lichide ce scad
rezistena electric a corpului uman;
suprafaa ncperii este acoperit, n proporie de sub 60 %,
cu mase metalice ce pot ajunge sub tensiune;
Exemple: laboratoare, hale industriale, vestiare, holuri etc.
foarte periculoase acestea sunt cele n care se realizeaz
cel puin una din urmtoarele condiii:
temperatura este n permanen peste 30 C;
umiditatea relativ a aerului este, n mod obinuit, peste 97 %
(exist permanent condensat pe suprafeele ncperii);
n ncpere exist permanent vapori sau gaze corosive;
suprafaa ncperii este acoperit n proporie de peste 60 %,
cu mase metalice ce pot ajunge sub tensiune.
Exemple: bile publice, spaii industriale etc. De asemenea, n
aceast categorie intr i rezervoarele metalice, cazanele de abur etc.
n care, n timpul execuiei, reviziei sau reparaiilor, pot lucra oameni.
Echipamentele electrice, la rndul lor, se clasific, din punctul
de vedere al electrocutrii n:
fixe au o poziie fix, funcioneaz permanent n acelai loc
i sunt amplasate n i pe elemente de construcie;
mobile au o poziie fix temporar, iar cnd sunt mutate
dintr-un loc n altul, sunt scoase de sub tensiune;
portative sunt construite special astfel nct n timpul
funcionrii se afl n contact cu corpul uman.
Instalaiile de protecie a omului mpotriva tensiunilor de
atingere trebuie s asigure tensiuni de atingere sau de pas ce s nu-l
pun n pericol, n caz de defect. Aceste tensiuni maxime, admisibile,
depind de categoria ncperii n care se afl omul i de tipul
echipamentului electric cu care lucreaz.
5. Metode de protecie
5.1. Metode de protecie mpotriva atingerilor directe
Acestea constau n:
msuri de protecie complet prin:
izolarea prilor aflate sub tensiune; De menionat c

vopselele, lacurile, i varnishurile nu asigur o protecie adecvat.


folosirea de bariere sau carcase cu un grad de protecie egal
cu cel puin IP2X; Metoda este cel mai mult utilizat, echipamentele
electrice fiind montate n carcase (cutii), panouri de comand i tablouri
de distribuie. Este obligatoriu ca un element de deschidere a incintei
(u, panou, sertar etc.) s poat fi deschis, detaat sau extras numai:
* prin utilizarea unei chei sau scule special destinate acestui
scop sau
* dup completa izolare a prilor aflate sub tensiune din
incint;
utilizarea tensiunilor foarte joase; Metoda este utilizat pentru
alimentarea unor receptoare de mic putere (portative) i aflate n
ncperi foarte periculoase, din punct de vedere al pericolului de
electrocutare.
msuri de protecie parial prin:
protecia prin intermediul unor obstacole sau prin plasarea
prilor aflate sub tensiune n afara zonelor de accesibilitate normal; n
acest fel accesul la prile aflate sub tensiune va fi permis numai
personalului autorizat care va dispune de echipamentul individual de
protecie (mnui, cizme i or electroizolante i ochelari de protecie).
Metodele de mai sus au un caracter preventiv. Efectul de
protecie poate fi mult diminuat datorit uzurii normale a izolaiilor,
prezenei apei sau condensatului, impedanei utilizatorilor etc.
msuri adiionale de protecie prin:
utilizarea de dispozitive foarte sensibile i cu declanare
rapid, bazate pe detectarea curentului rezidual ctre sol indiferent
dac acesta trece sau nu prin corpul unui om.
5.2. Metode de protecie mpotriva atingerilor indirecte
Acestea pot fi de baz i suplimentare. Metodele din prima
grup pot s realizeze protecia omului n caz de defect. Cele din a
doua grup vor fi utilizate n paralel cu una din metodele de baz
pentru o siguran mai mare. Trebuie artat c, de foarte multe ori,
atunci cnd pericolul de electrocutare este foarte mare, ca metod
suplimentar, se folosete tot una din metodele de baz (alta dect cea
utilizat ca metod de baz).
Ca metod de baz se utilizeaz:
legarea la pmnt;
legarea la nulul de protecie;
utilizarea tensiunilor reduse;

separarea de protecie.
Ca metode suplimentare cele mai utilizate sunt:
izolarea suplimentar de protecie;
egalizarea i dirijarea potenialelor;
deconectarea automat de protecie:
la apariia unei tensiuni de atingere periculoase;
la apariia unui curent de defect periculos pentru om.
n toate cazurile se recomand utilizarea echipamentului
individual de protecie: mnui, cizme i or electroizolante i ochelari
de protecie mpotriva arcului electric.
Metodele menionate asigur protecia omului mpotriva
tensiunilor accidentale de atingere prin una sau mai multe din
urmtoarele msuri:
micorarea tensiunii de atingere pn la valori ce nu pun n
pericol omul (sub 50 V n c.a. i 120 V n c.c.);
micorarea duratei de trecere a curentului prin om prin
scoaterea de sub tensiune a sectorului defect;
mrirea impedanei echivalente a corpului omului sau a
circuitului defect astfel nct curentul prin om s fie nepericulos.
Metoda de legare la pmnt este o metod proprie reelelor
izolate fa de pmnt. Principiul metodei este ilustrat n figura 9.
Reeaua izolat fa de pmnt alimenteaz un motor trifazat a
crei faz L1 prezint un defect de izolaie astfel nct carcasa acestuia
este pus sub tensiune. Reeaua are, din punct de vedere
electrotehnic, ntre linii i sol, cte o impedan cu valori ce depind de
izolaia real a liniilor. Pentru simplificare, impedanele de izolaie au
fost nlocuite cu rezistene de izolaie, Riz.
Metoda de legare la pmnt presupune legarea la pmnt a
prilor metalice ce, n mod accidental, ar putea ajunge sub tensiune
(cum este carcasa i stelajul motorului). Legtura este materializat
prin rezistenta Rp (fig. 9) ce corespunde unei prize de pmnt i
elementelor metalice ce se leag la aceasta. Astfel de reele sunt
denumite IT; I indic faptul c reeaua este izolat fa de pmnt
printr-o impedan de mrime mare; T indic faptul c masele
metalice ce ar putea ajunge accidental sub tensiune sunt legate la
pmnt) i se reprezint ca n fig. 10.
Curentul de defect IL1 sensul indicat n figura 9, iar schema
electric corespunztoare reprezentat n figura 11.
Este important de determinat curentul prin om Ih, pentru a
aprecia factorii de care acesta depinde i modalitile n care poate fi
adus la valori nepericuloase pentru om.

Fig. 9. Principiul metodei de legare la pmnt

Fig. 10. Reele IT:


a fr neutru; b cu neutru.

Fig. 11. Schema electric corespunztoare circulaiei


curentului de defect IL1 din figura 9
Aplicnd legile lui Kirchhoff rezult, n complex:

U 10 U 20 = I L1 Re I L 2 Riz
,
U 10 U 30 = I L1 Re I L 3 Re

(1)

unde: U10, U20, U30 sunt tensiunile de faze, iar Re rezistena echivalent
pe faza L1:

1
1
1
1
=
+
+
Re Riz Rp Rh

(2)

tiind c:

U 10 + U 20 + U 30 = 0
I L1Re = I h Rh

(3)

rezult:

Ih =

3U
R R
3Rh + Riz + h iz
Rp

(4)

unde U este tensiunea ntre faze (380 sau 400 V). Relaia (4) indic
dependena valorii curentului prin corpul omului n funcie de valoarea
rezistenei prizei de pmnt, Rp.
Pentru Rp = , ceea ce nseamn lipsa prizei de pmnt,
curentul prin om are expresia:

Ih =

3U
3Rh + Riz

(5)

Admind c U = 380 V i Rh = 1000 , rezistenta de izolaie


trebuie s fie Riz > 63 k pentru ca prin om s treac un curent mai mic
de 10 mA. Rezistene de izolaie aa de mari se ntlnesc foarte rar n
exploatare. Chiar dac la darea n funciune Riz are asemenea valori,
n timp, valoarea ei scade foarte mult, pn la valori curente de 10...20
k. n aceste situaii curentul prin om ar fi de 28...50 mA ceea ce ar
duce la accidente deosebit de grave. Pentru o rezisten de legare la
pmnt ideal, Rp = 0 curentul prin om ar fi Ih = 0 A. n acest fel omul
ar fi protejat chiar i la pierderea rezistenei de izolaie (ceea ce ar
conduce la alte categorii de defecte n instalaie).
Normele republicane impun pentru rezistena prizei de pmnt
o valoare maxim de 4 . n acest fel prin om ar putea s treac un
curent periculos, peste 10 mA, numai dac rezistena de izolaie ajunge
sub 250 , ceea ce este puin probabil s se ntmple n condiiile n
care instalaia electric funcioneaz normal. Totui, pentru sigurana
exploatrii instalaiilor electrice, acestea sunt prevzute cu
echipamente de msur a rezistenei de izolaie. n acest fel, la
nceputul unui ciclu (zi, schimb de lucru de exploatare) se verific buna
funcionare a instalaiei de protecie prin msurarea rezistenei de
izolaie.
n practic, instalaia de legare la pmnt, dintr-o cldire,
cuprinde:
priza de pmnt, ce poate fi natural, atunci cnd este
utilizat armtura metalic a fundaiei cldirii, artificial, atunci cnd
rezistena prizei naturale are rezistena mai mare de 4 ;
reeaua general de legare la pmnt, format dintr-un
conductor metalic, amplasat n interiorul cldirii la care se leag prile
metalice (ale receptoarelor) ce accidental ar putea ajunge sub tensiune;
legturile (cel puin dou) dintre priza de pmnt i reeaua
general de legare la pmnt. Pe fiecare din aceste legturi se

monteaz piese de separaie cu rolul de a izola priza de pmnt de


restul instalaiei, pentru a da posibilitatea msurrii rezistenei de
dispersie a prizei;
ramificaiile conductoare ce asigur continuitatea electric
dintre reeaua general de legare la pmnt i prile metalice ce,
accidental, ar putea ajunge sub tensiune.
n figura 12 se prezint schema instalaiei de legare la pmnt
pentru dou corpuri de cldire apropiate care au o singur priz de
pmnt.

Fig. 12. Instalaia de legare la pmnt:


R ramificaii; RGLP reeaua general de legare la pmnt;
PP priza de pmnt; EV electrozi verticali uniform distribuii pe contur
nchis; EO electrozi orizontali, de legare a electrozilor verticali ntre ei; PS
piese de separaie; M, TE, SM carcase metalice legate la pmnt (ale unor
motoare, tablouri electrice, stelaje metalice) ce ar putea ajunge sub tensiune.

Reeaua general de legare la pmnt (RGLP) poate fi pe


contur nchis sau deschis. n acest ultim caz capetele se vor lega
obligatoriu la priza de pmnt (PP) (sau la alt reea general de legare
la pmnt).
Conductoarele ce formeaz reeaua general de legare la
pmnt se mai numesc i conductoare principale de legare la pmnt
i au seciunile minime de:

16 mm2 din cupru masiv (grosimea minim 2 mm) sau funie;


100 mm2 din oel (grosimea minim 3 mm).
Legturile la priza de pmnt se execut cu conductoare din
oel cu seciunea minim de 100 mm2, dar cu grosimea minim de 4
mm.
Ramificaiile se execut pe traseul cel mai scurt dintre masa
metalic a unui receptor legat la pmnt i reeaua general de legare
la pmnt. Nu este permis legarea n serie a maselor deoarece, n caz
de ntrerupere a legturii, un numr mai mare de receptoare vor fi
izolate fa de pmnt. Conductoarele ramificaiilor au seciunea
minim de:
10 mm2 dac sunt din cupru;
25 mm2 din aluminiu sau OL-AL;
50 mm2 din oel.
Legarea la pmnt a carcaselor metalice supuse vibraiilor se
face cu conductoare flexibile tip funie ce vor avea o lungime de cel
puin 30 cm.
Piesele de separaie reprezint legturile demontabile dintre
reeaua general i priza de pmnt. Acestea se pot monta:
n interiorul cldirii;
pe peretele exterior al cldirii:
aparent, la o distan de sol de 3 m (pentru a nu fi uor
accesibile);
ngropat, ntr-o ni special destinat, amplasat la mai mult
de 0,6 m de sol i prevzut cu u metalic cu cheie triunghiular sau
ptrat.
Piesa de separaie const ntr-o eclis prevzut cu 4 uruburi
de prindere (de cel puin 8).
Metoda de legare la nulul de protecie (conductorul de
protecie) este o metod proprie reelelor legate la pmnt, de tipul TN
n care neutrul reelei este legat la pmnt (fig. 7a i c) (la postul de
transformare) i masele metalice ce, accidental, ar putea ajunge
sub tensiune, sunt legate la acesta prin conductoare de
protecie.
Principiul metodei este prezentat n figura 13.

Fig. 13. Principiul metodei de legare la nulul de protecie:


RM receptor monofazat; RT receptor trifazat.

Neutrul reelei este legat la pmnt printr-o priz de pmnt de


exploatare (PPE). Reeaua cuprinde, n afara conductoarelor active
(L1, L2, L3), conductoarele legate la neutrul acesteia:
conductorul de neutru (N sau nul de lucru) necesar
racordrii receptoarelor monofazate i
conductorul de protecie (PE sau nulul de protecie) care se
distribuie la masele metalice ce accidental ar putea ajunge sub
tensiune.
n cazul n care, la unul din receptoare, are loc un defect ce ar
putea pune sub tensiune masele metalice ale acestuia (cu care omul ar
putea intra n contact n timpul exploatrii), rezult un curent pe traseul:
faza defect (L1), masa metalic a receptorului, conductorul de
protecie (PE), neutrul reelei, faza defect (L1) (fig. 14). Acest curent
de defect are valoarea:

Id =

Uf
RL1 + RC + RPE

(6)

unde: RL1, RPE sunt rezistenele liniei (L1) i a conductorului de


protecie (PE), iar RC rezistena de contact n locul defect.
Cum rezistenele RL1, RPE i RC au valori foarte mici, curentul
de defect Id ajunge la valori mari, comparabile cu cele ale curentului de
scurtcircuit. n acest fel echipamentul de protecie aflat pe linia defect

(siguran fuzibil, releu electromagnetic sau echipament diferenial)


acioneaz i scoate de sub tensiune receptorul. Carcasa metalic a
acestuia este scoas de sub tensiune i omul nu se mai afl n pericol.
Dac omul s-ar afla n contact cu carcasa metalic, chiar n momentul
punerii acesteia sub tensiune, pericolul este redus deoarece aparatele
de protecie acioneaz ntr-un timp de ordinul milisecundelor.

Fig. 14. Traseul curentului de defect ntr-o reea legat la pmnt


n care s-a utilizat metoda de legare la nulul de protecie
Metoda prezint dezavantajul c n cazul ntreruperii
conductorului de protecie (fig. 15) exist pericolul ca omul s fie supus
unui oc electric n cazul n care, la unul din receptoare, masa sa
metalic a fost pus sub tensiune datorit unui defect. n figura 15
conductorul de protecie (PE) este ntrerupt n punctul A.

Fig. 15. Evidenierea pericolului de oc electric n


cazul ntreruperii conductorului de protecie
Deci toate receptoarele aflate ntre transformator i punctul A
au conductorul de protecie continuu i legat la neutrul reelei, ca n
figura 14, astfel c, orice punere sub tensiune a uneia dintre mase,
duce la scoaterea de sub tensiune a receptorului unde s-a produs
defectul. Un defect la unul din receptoarele aflate n aval de punctul A,
ce ar duce la punerea sub tensiune a prilor metalice ale acestuia (de
exemplu, receptorul R2 din figura 15) are ca efect punerea sub
tensiunea fazei defecte a conductorului de protecie PE, pe toat
lungimea sa, ca i a prilor metalice legate la acesta. Astfel, dac un
om se afl n contact cu carcasa receptorului R3 (la care nu exist nici
un defect) acesta va fi supus unui oc electric datorit curentului ce se
instaleaz pe traseul: faz defect (L1), carcasa metalic a receptorului
R2, conductorul de protecie PE , carcasa metalic a receptorului R3,
corpul omului, pmnt, neutrul reelei, faza defect (L1). Dac
rezistena traseului este sub 22 k curentul care va trece prin om va fi
mai mare de 10 mA i omul se afl n pericol.
Pentru a reduce la minimum pericolul de punere sub tensiune,
metoda de legare la nulul de protecie este completat cu una sau mai
multe metode cum ar fi: legarea la pmnt i/sau deconectarea
automat de protecie.
Reelele legate la pmnt sunt utilizate, aproape n
exclusivitate, n alimentarea receptoarelor de joas tensiune. n funcie
de modul n care sunt distribuite conductorul neutru (N) i, respectiv,

conductorul de protecie (PE) reelele legate la pmnt sunt de


urmtoarele tipuri:
TN-S, n care se folosesc conductoarele distincte pentru
neutru (N) i pentru conductorul de protecie (PE) pentru ntreaga reea,
aa cum se arat n figura 14.
TN-C n care funciile celor dou conductoare sunt ndeplinite
de un singur conductor (PEN) pentru ntreaga reea, ca n figura 16.
-TN-C-S n care funciile celor dou conductoare sunt
ndeplinite de un singur conductor numai pe o poriune a reelei. O
astfel de reea se compune dintr-o reea de tip TN-C i una TN-S
(numai n aceast ordine) figura 17.
TT n care neutrul reelei este legat la pmnt i prile
metalice (masele) ale receptoarelor ce, accidental, ar putea ajunge sub
tensiune sunt, de asemenea, legate la pmnt, independent, de neutrul
reelei, figura 18.

Fig. 16 Reea tip TN-C

Fig. 17. Reea tip TN-C-S

Fig. 18. Reea tip TT:


Rp1 priza de pmnt de exploatare a transformatorului reelei;
Rp2 priza de pmnt la care se leag masele metalice ale consumatorului.

Este de precizat c, n acest ultim caz, curenii de defect, de


valori mai mici, ca cele ale curenilor de scurtcircuit, pot provoca
apariia unei tensiuni de atingere periculoase pentru om (ntre carcasa
receptorului defect i pmnt). Se recomand utilizarea n paralel cu
legarea la conductorul de protecie i a altor metode, cum ar fi izolarea
suplimentar de protecie i/sau deconectarea automat de protecie.
Metoda utilizrii tensiunilor reduse const n alimentarea
receptoarelor la tensiuni sub valorile tensiunilor de atingere i pas,
maxime admise. Acestea sunt indicate n tabelul 1, n funcie de locul

de utilizare, de categoria echipamentului (receptorului), felul curentului,


periculozitatea mediului i timpul de deconectare a echipamentelor de
protecie n caz de defect.
Tensiunile de atingere i de pas maxim admise n funcie de locul
de utilizare, categoria echipamentului i felul curentului
Tabelul 1
Tensiuni de atingere i
de pas, maxime admise [V]
Locul de
utilizare

Categoria
echipamentului

Fixe i mobile
La suprafa
Portabile
Sub nivelul
solului

Toate

Felul curentului

c.a.
c.c.
c.a.
c.c.
c.a.
c.c.

Loc
"periculos"
Loc "puin
i foarte
periculos"
puin
"periculos"
Timpul de deconectare [s]
>3
>3
3
3
65
50
65
50
120
65
120 65
65
50
65
50
120
65
120 65
24
24
24
24
-

Tensiunile reduse se pot obine cu transformatoare


cobortoare sau cu grupuri motor-generator. Circuitele de tensiune
redus vor avea trasee distincte de cele de tensiune normal. Prizele
nu vor fi prevzute cu contact de protecie, iar masele metalice ale
receptoarelor alimentate din astfel de circuite nu este necesar a fi
legate la pmnt sau la un conductor de protecie.
Metoda separrii de protecie const n utilizarea unui
transformator, de regul, cu raportul de transformare 1:1, pentru
alimentarea receptoarelor. n acest fel, receptoarele sunt alimentate
dintr-o reea izolat fa de pmnt, mai puin periculoas, dect dintr-o
reea legat la pmnt (fig. 19).

Fig. 19. Receptor alimentat printr-un


transformator de separare
Metoda se folosete pentru alimentarea sculelor portabile de
putere mare, cnd nu pot fi alimentate cu tensiuni reduse, sau a unor
receptoare de putere mic, utilizate n medii foarte periculoase din
punct de vedere al pericolului de ocuri electrice. n acest ultim caz,
transformatorul este inclus n receptor de exemplu, priza din
camerele de baie pentru alimentarea mainilor electrice de ras.
Transformatorul de separare va avea nfurrile distincte i
prevzute cu izolaie ntrit. Tensiunea primar nu poate depi 1000
V, iar cea secundar 500 V.
Circuitul separat (al secundarului) nu va avea nici un punct
comun cu alt circuit i nici un punct legat la pmnt sau la alte mase.
Un circuit separat poate alimenta mai multe receptoare dac:
alimentarea se face n cablu;
masele receptoarelor sunt legate printr-un conductor de
egalizare a potenialelor. Acesta nu se leag la pmnt sau alt
conductor de protecie sau mas a altor circuite. Conductorul de
egalizare a potenialelor este inclus n cablul de alimentare;
prizele vor avea contact de protecie legat la conductorul de
egalizare a potenialelor;
pe circuit se va prevedea un dispozitiv de protecie care s
semnalizeze primul defect de izolaie la mas i care s deconecteze
dup maximum 5 s de la apariia celui de al doilea defect de izolaie la
alt mas.
Metoda izolrii suplimentare de protecie presupune acoperirea
cu o izolaie suplimentar realizat ca un nveli izolant pe toate prile
echipamentului. Acesta trebuie s ofere un grad de protecie de cel
puin IP2X, s suporte toate solicitrile mecanice, termice i electrice
din funcionarea normal i s nu fie traversat de elemente

conductoare electric. Astfel de echipamente nu se leag la pmnt


(marcajul de legare la pmnt va fi anulat vizibil dac exist pe borne)
i nici la conductorul de protecie.
Metoda este utilizat ca metod suplimentar a unei metode de
baz.
Metoda egalizrii i dirijrii potenialelor const n a dirija
potenialele cu care omul poate intra n contact potenialul minilor i
potenialul picioarelor astfel nct acestea s aib valori, dac nu
egale, cel puin apropiate, astfel ca tensiunile de atingere i de pas s
fie, practic, neglijabile i omul protejat.
n mod teoretic, aceasta se poate realiza executnd, la
suprafaa solului, o priz de pmnt dintr-o plac metalic de
dimensiunea suprafeei pe care se afl masele metalice ce accidental
ar putea ajunge sub tensiune, (fig. 20). Toate masele metalice s-ar lega
la aceast priz.
n cazul unui defect la unul din utilaje 4 (fig. 20) stelajul metalic
al acestuia ar fi pus sub tensiune i, odat cu el, placa 1, prin
intermediul legturii metalice 5. n acest fel, potenialele punctelor A, B,
C vor fi egale. Dac omul atinge o astfel de mas metalic pus sub
tensiune, tensiunea de atingere (ntre mna, A i picior, B) i
tensiunea de pas (ntre picior, B i picior, C) vor fi nule. Va exista un
pericol numai dac omul se afl pe sol, n afara plcii, i atinge un
element metalic aflat n contact cu placa.

Fig. 20. Principiul metodei egalizrii i dirijrii potenialelor:


1 plac metalic; 2 dulap metalic cu echipament electric; 3 carcasa
metalic a unui motor; 4 stelaj metalic al unui utilaj electric; 5 legturi de
egalizare a potenialelor.

n practic, placa este nlocuit cu o reea metalic din fier


beton inclus n placa din beton a construciei. Potenialul la suprafaa
plcii, pe care se afl masele metalice ale utilajelor (ce accidental ar

putea ajunge sub tensiune), nu va mai fi constant ci va avea o variaie


de tipul celei din figura 21.

Fig. 21. Variaia potenialului la suprafaa plcii pe care se afl masele


metalice ce, accidental, ar putea ajunge sub tensiune
Tensiunile de atingere Ua i de pas Upas nu vor mai fi nule.
Valorile acestora vor depinde de distana dintre conductoarele metalice
(d) ce nlocuiesc placa. La distana d sub 30 cm tensiunile de atingere
i de pas sunt sub valorile ce ar putea duce la cureni periculoi pentru
om.
Metoda este aplicat n industrie, dar are dezavantajul c, pe
lng o cheltuial mare, oblig la o bun coordonare a lucrrilor de
construcii cu cele de instalaii, pentru a realiza continuitatea electric a
reelei metalice din plac. Totodat trebuie s se ia msuri ce s nu
permit, n nici un fel, ca un om ce s-ar putea afla n afara zonei de
protecie s poat intra n contact cu un element metalic aflat n zona
de protecie i pus sub tensiune (evi metalice, corniere etc.).
Metoda deconectrii automate la apariia unei tensiuni de
atingere periculoase const n aceea c, la apariia unei astfel de
tensiuni ntre masa metalic a unui utilaj i pmnt, utilajul respectiv
este scos de sub tensiune. Principiul metodei este prezentat n figura
22. Motorul M trifazat este alimentat de la reea, avnd pe circuit:
siguranele fuzibile F1, F2 i F3 pentru protecie la scurtcircuit, contactul
K1 pentru acionare (dar care poate funciona i ca releu de tensiunea
minim deconectnd alimentarea la o scdere a tensiunii sub 70 %
din valoarea nominal) i releul termic trifazat F4. S1 i S2 sunt butoane
cu revenire folosite pentru pornirea i, respectiv, oprirea motorului. S1

se afl n paralel cu contactul de automeninere K1 (2-4).

Fig. 22. Schema de principiu a proteciei mpotriva tensiunilor


accidentale de atingere prin deconectarea automat la apariia
tensiunii de atingere periculoas
Carcasa metalic a motorului este legat de pmnt (priza PP)
prin intermediul unui releu K2, sensibil la tensiuni de peste 50 V, ce ar
putea fi periculoase pentru om.
Dac la motor are loc un defect ce ar duce la punerea sub
tensiune a carcasei, releul K2 este excitat i contactul N-K2 (3-5) al
acestuia se deschide. n acest fel circuitul bobinei contactorului K1, ce
meninea n funciune motorul, este ntrerupt i astfel contactele
principale K1 revin n poziia deschis scond de sub tensiune motorul.

Butonul S3 (cu revenire) are rolul de a simula un defect de


punere sub tensiune a carcasei: releul K2 este conectat ntre una din
fazele de alimentare i pmnt. Conectarea se face n serie cu o
rezisten R dimensionat astfel nct cderea de tensiune pe releul K2
s fie de 50 V. Simularea defectului se face la fiecare nceput de ciclu
de activitate (schimb) a receptorului respectiv. Dac protecia
funcioneaz corect se poate pune n funciune receptorul. n caz
contrar, se identific locul defect, se nltur defeciunea i apoi se
pune n funciune, pentru lucru, receptorul.
Metoda deconectrii automate la apariia unui curent de defect.
Metoda utilizeaz un echipament de protecie diferenial de
sensibilitatea dorit. Acest echipament va scoate receptorul din
funciune la orice defect de izolaie sau de ntrerupere a unei faze
defecte ce ar putea s conduc la punerea sub tensiune a maselor
metalice ale acestuia. n acest fel omul nu este supus punerii sub
tensiune ca urmare a defectelor menionate.
Bibliografie
[1] Borza, I., Instalaii pentru construcii - Ghid de documentare, proiectare,
execuie i exploatare, Editura Politehnica, Timioara, 2003.
[2] Coliu, A., Chiri, Gh., ndrumtor pentru lucrrile de instalaii electrice
interioare, Editura Tehnic, Bucureti, 1963.
[3] Iliescu, C., Radu, O., Protecia mpotriva electrocutrilor la exploatarea i
executarea de lucrri n instalaiile electrice, Editura Tehnic, Bucureti, 1985.
[4] Manea, A., Scrltescu, M., Aparate electronice pentru protecia munci,
Editura Tehnic, Bucureti, 1976.
[5] Sufrim, M., Cum sa ne pzim contra electrocutrilor, Editura Tehnic,
Bucureti, 1978.
[6] Sufrim, M., .a., Mijloace moderne de protecie mpotriva tensiunilor
accidentale n instalaiile electrice de joas tensiune , Litografia Universitii din
Oradea, 2000.
[7] Vasilache, Gr., Sisteme de protecie mpotriva tensiunilor electrice
accidentale n instalaiile de joas tensiune, Editura Tehnic, Bucureti, 1980.
[8] *** Manual de instalaii - Instalaii electrice i de automatizare, Editura
Artecno, Bucureti S.R.L., 2002.

S-ar putea să vă placă și