Sunteți pe pagina 1din 5

Instalatii Electrice

N 15

Sa Se Prezinte Schema Electrica De Alimentare A


Receptoarelor Si Sa Se Dimensioneze Circuitul De
Alimentare Din Elementele De Protectie Si Comutatie In
Urmatoarele ipostaze:
a) Cabluri Individuale Pozate In Aer Cu Conductor De Al Ѳma=30⁰

1 Cuptor Electric Cu Rezistente Trifazate + Contactor + Siguranta Fuzibila


Specificatii De Functionare :
Pn 27 [Kw]
cosϕn 0.95
Uf 400 [V]
Rezolvare: Ic 41.0223 [A]
Suprafata Conductor 10 [mm^2]
Ima 47 [A]
Conductor Cupru
2x6
Cyy
mm^2 + 1*6 mm^2
Conductor Aluminiu
2*10Acyy
mm^2 + 1*10 mm^2
Siguranta Fuzibila In-63 A/Ins-50 A
Contactor D 32/50/50
2 Incalzitor Electric Monofazat + Contactor + Siguranta
Pn 20.4 [Kw]
cosϕn 0.95
Uf 230 [V]
Rezolvare: Ic 93.3638 [A]
Conductor Cupru
2*25
Cyy
mm^2 + 1*16 mm^2
Conductor Aluminiu
2*35Acyy
mm^2 + 1*16 mm^2
Siguranta Fuzibila
In-100 A/Ins-100 A
Contactor D 80/125/125
3 Motor Asincron Trifazat
Pn 28 [Kw]
cosϕn 0.89
ηn 0.9 [%]
Uf 400 [V]
𝑰�/𝑰�= 6.8
Ic 50.4551 [A]
Rezolvare: Ip 343.095
Conductor Cupru Cyy 4*10 mm^2
Conductor Aluminiu Acyy
4*10 mm^2
Siguranta Fuzibila
In-160 A/Ins-160 A
Contactor Lc/D 65

b) 3 Cabluri Pe Traseu Montate In Tablou, Pe Perete Ѳma=40⁰ (Al)


Ip 343.095 [A]

}
s Cu 10 [mm^2]
s Cu ≥ 𝑰�⁄𝑰𝒗� s Cu ≥ 9.8027 [mm^2]
Iva Cu 35 [A/mm^2]

Vom Folosi Sectiune Conductorului De Cupru = 10 mm ^2


s Cu 10 [mm^2]
s Al ≥
} s Al ≥ 17.1547 [m^2]
𝑰�⁄𝑰𝒗�

Iva Al 20 [A/mm^2]
s Al 25 [mm^2]

Vom Folosi Sectiune Conductorului De Aluminiu = 25 mm ^2


Sa Se Dimensioneze Cablurile Electrice De Alimentare
Pentru Urmatoarele Receptoate Alimentate Dintr-un Tablou
De Distributie Prin Circuite Separate Montate Liber In Aer.
1. Receptor Rezistiv Monofazat
Pn 22 [kW]
cosϕn 1
Uf 230 [V]
Rezolvare: Ic = 95.6522 [A]
Conductor Cupru
2 x Cyy
25 mm^2+ 1 x16 mm^2
Conductor Aluminiu
2 x 35
Acyy
mm^2+ 1 x16 mm^2
2. Receptor Rezistiv Trifazat
Pn 22 [kW]
cosϕn 1
Uf 400 [V]
Rezolvare: Ic 31.7543 [A]
Conductor Cupru Cyy 4 x 4 mm^2
Conductor Aluminiu Acyy
4 x 6 mm^2
3. Receptor Monofazat Tip Motor Asincron
Pn 22.5 [kW]
cosϕn 0.83
ɳn 0.85
Uf 230 [V]
Ic 138.662 [A]
Ip/In 6
Ip 831.972 [A]
Iv/Jva Cu 23.7706 [mm^2]
Rezolvare: Iv/Jva Al 41.5986 [mm^2]
Conductor Cupru Cyy 3*2.5 mm^2
Conductor Aluminiu Acyy3*4 mm^2
4. Receptor Trifazat Tip Motor Asincron
Pn 22.5 [kw]
cosϕn 0.83
Uf 400 [V]
Ic 46.0325 [A]
ɳn 0.85
Ip/In 6
Ip 276.195 [A]
Iv/Jva Cu 7.89129 [mm^2]
Rezolvare: Iv/Jva Al =13.8098 [mm^2]
Conductor Cupru Cyy 4*1 mm^2
Conductor Aluminiu Acyy
4* 16 mm^2

Conductoare Montate In Pamant


1`. Receptor Rezistiv Monofazat
Pn 22 [kw]
cos(fi)n 1
Uf 230 [V]
Rezolvare: Ic 95.6522 [A]
Conductor Cupru
2*16
Cyymm^2 + 1*16 mm^2
Conductor Aluminiu
2*25Acyy
mm^2 + 1*16 mm^2
2`. Receptor Rezistiv Trifazat
Pn 22 [kW]
cosϕn 1
Uf 400 [V]
Rezolvare: Ic 31.7543 [A]
Conductor Cupru Cyy4 X 2.5mm^2
Conductor Aluminiu Acyy
4 X 4 mm^2
3`. Receptor Monofazat Tip Motor Asincron
Pn 22.5 [kW]
Rezolvare: Ic 138.662 [A]
Conductor Cupru
2x35
Cyy
mm^2 + 1*16 mm^2
Conductor Aluminiu
2*50Acyy
mm^2 + 1*25 mm^2
4` . Receptor Tip Motor Asincron Trifazat
Pn 22.5 [kW]
Ic 46.0325 [A]
Intensitati Maxim Admisibile Pentru Cabluri De Energie

Pozate In Aer (30 °C) Sectiunile Conductoarelor


Sectiun Sectiun L 1, L 2, N, Pe,
Cyy (A) e Acyy (A) e L3 Pen
(mm^2) (mm^2) (mm^2) (mm^2)
18 1.5 0 1.5 1.5 1.5 1.5
25 2.5 0 2.5 2.5 2.5 2.5
34 4 27 4 4 4 4
44 6 34 6 6 6 6
60 10 47 10 10 10 10
80 16 63 16 16 16 16
105 25 82 25 25 16 16
130 35 100 35 35 16 16
160 50 125 50 50 25 25
200 70 155 70 70 35 35
245 95 190 95 95 50 50
285 120 220 120 120 70 70
325 150 250 150 150 70 70
370 185 285 185 185 95 95
435 240 340 240 240 120 120
500 300 390 300 300 150 150
400 185 185

S-ar putea să vă placă și