Documente Academic
Documente Profesional
Documente Cultură
SARCINA........................................................................................................................................3
ÎNTRODUCERE….........................................................................................................................6
1. CARACTERISTICA ÎNTREPRINDERII ŞI A SECŢIILOR EI........................................8
1.1. Caracteristica întreprinderii......................................................................................................8
1.2.Caracteristica generală a secţiilor principale.............................................................................8
2.CALCULUL SARCINILOR ELECTRICE A SECŢIILOR ŞI A
ÎNTREPRINDERII..........................................................................................................................9
2.1.Determinarea sarcinilor electrice a SRM...................................................................................9
2.2. Determinarea sarcinilor electrice a întreprinderii....................................................................11
3. ALEGEREA TENSIUNII DE ALIMENTARE DE LA SISTEM...........................................16
4.ALEGEREA NUMĂRULUI ŞI PUTERII NOMINALE A TRANSFORMA-
TOARELOR STAŢIEI PRINCIPALE ŞI A POSTURILOR DE
TRANSFORMATOARE DIN INCINTA INTREPRINDERII.....................................................19
5.AMPLASAREA STAŢIEI PRINCIPALE COBORÎTOARE, STAŢIILOR
DE DISTRIBUŢIE ŞI A POSTURILOR DE TRANSFORMARE…............................................23
6.ELABORAREA SCHEMEI DE MEDIE TENSIUNE DIN INCINTA
ÎNTREPRINDERII.........................................................................................................................24
6.1.Calculul tehnico-economic pentru varianta I............................................................................25
6.2.Calculul tehnico-economic pentru varianta II...........................................................................26
7.CALCULUL REŢELEI DIN SECŢIA DE REPARAŢII
MECANICE....................................................................................................................................30
7.1. Alegerea cablurilor de alimentare a nodurilor.........................................................................33
7.2 Alegerea dulapurilor de distribuţie din noduri.........................................................................34
8.CALCULUL CURENŢILOR DE CURTCIRCUIT...................................................................35
9.VERIFICAREA ELEMENTELOR ŞI A APARATAJULUI DIN
SISTEMUL DE AEE A ÎNTREPRINDERII LA ACŢIUNEA CURENŢILOR
DE
SCURTCIRCUIT….......................................................................................................................45
9.1.Alegerea echipamentului la partea de 110kV..........................................................................45
9.2.Alegerea şi verificarea întreruptorului liniei în cablu 10kV…................................................47
9.3.Alegerea şi verificarea liniei în cablu pe sectorul SPC-PT26….............................................48
9.4.Alegerea şi verificarea transformatorului de curent
la barele 10kV a SPC.....................................................................................................................48
9.5.Alegerea şi verificarea transformatorului de tensiune
la barele 10kV a SPC.....................................................................................................................50
9.6.Alegerea siguranţei fuzibile pentru protecţia transformatorului din PT-8
din SRM.........................................................................................................................................51
9.7.Alegerea şi verificarea separatorului de sarcină de 10kV…....................................................51
9.8.Alegerea conductorului de alimentare a receptorului electric.................................................52
10.ALEGEREA TIPULUI PROTECŢIEI PRIN RELEE ŞI REGLAJUL
TIMPULUI DE ACŢIONARE A LOR….....................................................................................53
10.1.Verificarea sensibilităţii între elementele protecţiei…..........................................................54
11. ALEGEREA SCHEMELOR DE AUOTAMITIZARE, SEMNALIZARE,
MĂSURĂ ȘI EVIDENȚĂ A ENERGIEI ELECTRICE..............................................................57
12.COMPENSAREA PUTERII REACTIVE..............................................................................61
ÎNCHEIERE…..............................................................................................................................64
BIBLIOGRAFIE….......................................................................................................................65
1
SARCINA nr.53
Tema: Alimentarea cu energie electrică a fabricii de aglomerare
a combinatului metalurgic
2
Receptoarele instalate în SRM Tabelul 2
Nr. RE pe planul Receptoare electrice, maşini, unelte,strunguri cos k Pi , kW
u
secţiei
1,3,27,28 Strung de găurit vertical 0,6 0,14 10
2,29 Calorifer 0,9 0,8 7
4 Strung de găurit radial 0,6 0,14 4,5
5,8,16 Presă 0,6 0,16 14
6,31,36 Ventilator 0,8 0,65 7
7,22 Cuptor de încălzire 0,85 0,5 20
9,10 Strung de bobinare 0,8 0,2 1,7
11,12 Ferestrău de retezare 0,65 0,17 10
13,18,19 Strung de strungit și filetat 0,6 0,14 7
14,23,24 Strung de frezat orizontal 0,6 0,14 10
15 Macara-grindă cu DA-50% 0,5 0,1 8,2
17,20 Strung de decojat și de ascuțit 0,65 0,17 7
21,26 Foarfecă de tăiat foi 0,5 0,12 14
25 Strung de îndoit țevi 0,6 0,12 4,5
30,32,33 Mașină de sudare cu DA-60% (kVA) 0,7 0,35 100
34,35 Bac de fierbere 0,85 0,5 20
3
ÎNTRODUCERE
4
Sarcina principală de optimizare a sistemului de AEE a întreprinderilor industriale, pe lîngă
cele enumerate mai sus, include şi alegerea secţiunilor conductoarelor şi cablurilor, a metodelor
de compensare a deficitului de putere reactivă, automatizării, sistemului de dispecer etc.
Deci, problema pusă în faţă este de a alimenta cu energie electrică a fabricii de aglomerare a
combinatului metalurgic.
5
1. CARACTERISTICA ÎNTREPRINDERII ŞI A SECŢIILOR EI
1.1. Caracteristica întreprinderii
Întreprinderea proiectată este o fabrică de aglomerare a combinatului metalurgic. Această
uzină lucrează în două schimburi cu timpul utilizării sarcinii maxime de 4335 h.
Capacitatea consumului de energie electrică a acestei uzine este reprezentată de sala de
mașini la JT și ÎT, secția mașinelor aglomerative, secţia de sarjă, staţia de pompare şi alţi
consumatori tehnologici. Receptoare electrice fac parte din categoria II-a şi a III-a. Teritoriul
uzinii ocupă o suprafaţă de circa 123000 m2.
Întreprinderea este alimentată cu energie electrică prin două linii de la sistemul energetic
poziţionat la o distanţă de 14,4 km de la uzină. Staţia raională a sistemului electroenergetic are
două transformatoare cu puterea 10000 kVA fiecare cu tensiunea primară 110 kV şi medie 35,
10 kV. Putera sistemului electroenergetic constitue 900 MVA, reactanţa lui la 110 kV raportate
la punerea sistemului fiind 0,4.
1.2. Caracteristica generală a secţiilor principale
Principalele activitati a uzinei constau în: primirea, asigurarea tranzitului materiilor prime
si producerea de aglomerat necesar la incarcatura tehnologica feroasa a furnalelor.
Materiile prime sosite pe calea ferata se descarca prin culbutoare. Descarcarea in port se face
prin 3 dane specializate pentru fondanti, minereu si carbune.
După sosire materiei prime la uzină, este transportată de la depozitul de materiale spre
secția mecanică, unde au loc primele etape de prelucrare a ei. Materia primă se macină și se
prelucrează chimic în secția mecanică cu spocul majorării concentrației minereului. Această
secție are mașini sincrone și asincrone de diferite puteri la alimentate la 0,4 kV și 10 kV. Secția
este caracterizată de mediu înconjurător prăfuit, ce face necesară preluare de mijloace de
protecție a sănătății muncitorilor.
Mașini aglomerative. Aceste mașini prelucrează materia primă sosită la uzină, deci are
loc sinterizarea lor.
Secţia de șarjă și alimentare cu șarjă. Această secţie este secţia de început al procesului
tehnologic din uzina dată. Aici se aduce materia primă, se prelucrează preventiv, sortânduse
toate tipurile de materii. Tot aici are loc verificarea calităţii materie. Ulterior materia este
transportată pe benzi rulante spre secţia de alimentare cu șarjă unde aceasta mai trece prin câteva
procese de sortare şi pregătire pentru faza ulterioară de producere. Consumatorii sunt de
categoriea a II şi a III. Podeaua este din beton armat.
Blocul administrativ. În direcţia se află contabilitatea, săli şi cabinete ale angajaţilor,
locurile de munca a personalului, oficii. Mediul ambiant normal, podeaua este din teracotă.
6
Secţia de reparaţii mecanice. În secţia de reparaţii mecanice are loc confecţionarea
pieselor nestandarde şi reparaţia instalaţiilor defectate. Instalaţiile de bază sunt strungurile de
prelucrare a metalelor. Întreruperea în alimentare cu energie electrică aduce la mărirea timpului
de reparaţie. Mediul ambiant normal, podeaua este din beton.
Cantina. Cantina este destinată pentru pregătirea bucatelor şi luarea mesei. Întreruperea
în alimentare cu energie electrică nu aduce la oprirea procesului de producere. Mediul ambiant
normal, podeaua este din teracotă.
Depozitele. Depozitele de materii prime pot stoca volume mari de: carbune, cocs,
minereu - bulgari, pelete, calcar, minereu – praf si fondanti. Facilitatile de depozitare sunt dotate
cu masini specializate in stivuirea si extragerea materiilor prime.
În depozite are mai are loc și păstrarea diferitor piese care sunt folosite la asamblarea diferitor
tipuri de aparate. La întreruperea alimentării cu energie electrică lucrările de încărcare şi
descărcare sunt stopate. În depozite mediul ambiant normal, podeaua este din beton.
Staţia de pompare. Staţia e destinată pentru alimentarea întreprinderii cu apă pentru
necesităţi tehnologice şi antiincendiare. Instalaţiile de bază sînt pompele de tensiune joasă şi
înaltă. Întreruperea în alimentare cu energie electrică poate aduce la nelivrarea producţiei. Pentru
rezervarea antiincendiară se foloseşte pompa cu motor dizel. Mediul ambiant umed, podeaua este
din beton.
Garaje. Aici se află autovehiculile şi electrocarele care sunt folosite la transportare. Aici
are loc încărcarea acumulatoarelor pentru electrocare. Instalaţiile de bază sînt aparatele de
încărcare şi redresoare. Întreruperea alimentării cu energie electrică nu aduce la oprirea
procesului tehnologic. Mediul ambiant normal, podeaua este din beton.
7
Tabelul 1.1. Caracteristica generală a secţiilor
grad.de cat.de
mediul cat. tip.
N pericol de incen.
Denumirea secției înconj. RE PT
electr. şi ex.
Cu pericol
Sala de mașini
1 Prăfuit II deosebit de - Interior
Sala de mașini (10kV)
ridicat
Cu pericol
2 Alimentarea cu șarjă Prăfuit II - -
ridicat
Cu pericol
3 Secția de șarjă Prăfuit III - Interior
ridicat
Cu pericol
4 Returnare Prăfuit III - Interior
ridicat
Cu pericol
5 Mașini aglomerative Prăfuit II deosebit de - Anexat
ridicat
Cu pericol
6 Dozatoare Prăfuit II - Interior
ridicat
7 Secția de probare Normal III Fără pericol - -
8 Blocul administrativ Normal III Fără pericol - Interior
9 Laboratoare Normal III Fără pericol - Interior
Cu pericol
11 Cantina Normal III П-II Interior
redus
Cu pericol
12 Stația de pompare Normal II П-IIa Interior
ridicat
Cu pericol
Secția de reparații
13 Normal III deosebit de П-IIa Interior
mecanice
ridicat
Cu pericol
14 Garaj Normal III - -
deosebit
8
2. CALCULUL SARCINILOR ELECTRICE A SECŢIILOR ŞI A ÎNTREPRINDERII
P
n
msi
Ku. i1
;
n
Pni
i1
unde Pms sunt puterile medii a receptoarelor electrice corespunzătoare nodului dat,
i
P Ku Pni ;
n
msi
i1 i1
K
i1
n
uai
Pni 2 (0, 65 7) 1(0,8 7) 2 (0, 5 20) 34, 7
Ku.a. 0, 57;
n 2 7 1 7 2 20 61
Pni
i1
n
9
Pms Pmsi Kuai Pni ;
i1 i1
10
n
Pms Kuai Pni 2 (0, 65 7) 1(0,8 7) 2 (0,5 20) 34, 7
kW;
i1
Deci:
Kma 1, 66;
Se determină puterea activă de calcul:
Pc P P ;
c
und Pc este puterea activă consumată de receptoarele electrice din nodul dat,
e
P K P 1, 6634, 7 57, 6 kW;
c ma ms
12
Sarcina activă de calcul a secţiei:
Pcalc Pinst Kc 260 0, 7 182 kW ;
unde
Pins este puterea instalată a secţiei nr.2;
t
K c - coeficientul de cerere.
Sarcina reactivă de calcul a secţiei:
Qcalc Pcalc tg 1821, 02 185, 64 kvar
; Sarcina de iluminat a secţiei:
Pil Kc,il Po,il S 1, 0 0, 017 1666 28,32 kW ;
S - aria secţiei.
Puterea activă sumară a secţiei:
P Pcalc Pil 182 28,32 210,32 kW;
Puterea de calcul totală:
13
Tabelul 2.1. Datele inițiale pentru calcularea sarcinilor electrice a S.R.M.
I Nr. | Nr. |Nr. de RE | Nr.* Pn | Ku | Cos(f) I
I nod. |grupului| in grupa | buc* kW | -- | --- I
14
Tabelul 2.2. Rezultatele calculării sarcinilor electrice a S.R.M
15
Tabelul 2.3. Datele inițiale pentru calculul sarcinilor electrice
16
3. ALEGEREA TENSIUNII DE ALIMENTARE DE LA SISTEM
Alegerea tensiunii se reduce la determinarea unei tensiuni care satisface toate cerinţele
tehnice şi perspectiva creşterii întreprinderii. Tensiunea aleasă trebuie să corespundă
minimumul cheltuielilor anuale de calcul. Alegerea tensiunii se efectuează prin compararea
tehnico-economică a două variante.
La compararea tehnico-economică a variantelor e considerat tariful mondial la energie
electrică Cd=0,05 $/kWh.
17
110 kV , 35 kV SPC 10 kV
LEA-110 kV, 35 kV
SEE
Varianta I – 110 kV
Determinăm curentul liniei aeriene la tensiunea 110 kV conform relației:
ILEA Sc ;
3Un n
unde Sc este puterea de calcul pe partea de tensiune înaltă SPC, kVA;
n - numărul liniilor ce vin la SPC, n = 2;
Un – tensiunea nominală, Un = 110 kV;
Deci:
und
e jec este densitatea economică a curentului,se alege din tab.4.5 [2, j e 1,1 A / mm2 ;
p.233],
Tmax - durata anuală de utilizare a puterii maxime, Tmax = 4880 h;
20, 01
Fec 18,19 mm2 ;
1,1
Conform tab.2.5.6 [7], diametrul minimal al conductorului la 110 kV este 70 mm2,
deci din tab.7.38 [5], se va alege conductorul de tip AC-70/11 pentru care
Iadm 265 A ,
având:
r0 – rezistența electrică specifică, r0=0,46 Ω/km;
x0 – reactanța electrică specifică, x0=0,42 Ω/km.
În regimul de avarie
ILEAav 2 ILEA 218,19
18
40, 02 A <
Iadm 265 A
Determinăm pierderile de tensiune în regim normal şi de avarie conform relației:
Pc R Qe1 X
U ;
Unom n
19
unde: R r0 L 0, 4614, 4 6, 62 Ω;
X x0 L 0, 4214, 4 6, 05Ω;
20
4. ALEGEREA NUMĂRULUI ŞI PUTERII NOMINALE A TRANSFORMATOARELOR
STAŢIEI PRINCIPALE ŞI A POSTURILOR DE TRANSFORMATOARE DIN
ÎNCINTA INTREPRINDERII
22
4.2. Alegerea numărului, puterii şi tipul transformatoarelor de putere la PT
Alegerea puterii nominale a transformatoarelor din secţii se efectuează din condiţiile
încărcării raţionale în regimul normal şi ţinînd cont de posibilităţile de rezervare în regim de
post-avarie.
Posturile de tansformare cu un transformator se recomandă pentru alimentarea
receptoarelor electrice care admit întreruperea alimentării cu energie electrică, atîta timp cît se
montează transformatorul de rezervă sau se realizează rezerva cu linii de joasă tensiune de la PT
vecin. La nivel de întreprindere se recomandă până la cinci tipuri de posturi de transformatoare.
Analizînd sarcinile de calcul a tuturor secţiilor se vor utiliza tipuri de transformatoare cu
puterile standartizate de 160, 250, 400 și 630 kVA. Puterea transformatoarelor din secţii se
determină conform relaţiei:
Sc Pc
S ;
n n ki n ki cos
unde, Pc este puterea de calcul a secţiei, kW;
23
De exemplu, la coeficientul normativ kîn=0,7 pentru sarcinile de categoria II,
pentru secția Nr.5:
Locul de amplasare a SPC se alege din partea liniilor electrice aeriene 110 kV (LEA- 110
kV), dar şi cu deplasare spre centrul de sarcină. Posturile de transformare e de dorit să fie
apropiate la maxim de centrul sarcinilor electrice a secţiilor, ceea ce permite de a construi un
sistem de alimentare cu energie electrică mai economic şi fiabil , deoarece se micşorează
lungimea reţelelor de distribuţie, se micşorează pierderile de energie electrică.
Posturile de transformare 10/ 0,4 kV se admit de instalat în interiorul secţiei, cu scopul de
apropiere maximă de receptoare. Însă, în secţiile unde au loc degajări enorme de căldură, prafuri
conductoare sau substanţe chimice ce influenţează dăunător asupra regimului normal de
funcţionare a transformatorului, în acest caz transformatoarele se amplasează în exteriorul
secţiei, sau în interiorul lor îngrădit cu perete despărţitor şi se prevede separat pentru
transformator, ventilare forţată. Instalaţiile de distribuţie 10 kV se vor plasa în afara secţiilor.
Numărul şi puterile transformatoarelor din posturile de transformatoare se alege conform
recomandărilor [2].
25
6. ELABORAREA SCHEMEI DE MEDIE TENSIUNE DIN INCINTA
ÎNTREPRINDERII
La elaborarea schemei de alimentare cu energie electrică din incinta întreprinderii se
utilizează schema radială şi magistrală.
Posturile de transformare (PT) se alimentează de la SPC prin intermediul cablurilor
instalate în tranşee. Alegerea schemei raţionale de alimentare cu energie electrică se efectuează
prin metoda comparării tehnico-economice a variantelor. Pentru alegerea schemei optime se
efectuează un calcul tehnico-economic cu compararea a două variante.
Se vor analiza două variante de alimentare cu energie electrică a întreprinderii:
Se prezintă schemele de alimentare pentru varianta 1 şi 2.
ID-10 kV
a SPC Varianta 1
W5 W6
PT-6 PT-4
ID-10 kV
a PD
W 4W 2W 3
PT-1
W1
ID-10 kV
a SPC Varianta 2
W6
PT-6
ID-10 kV
a PD
W3 W4 W5
PT-1 PT-4
W1 W2
26
6.1. Calculul tehnico-economic pentru Varianta I.
Se determină secţiunile cablurilor conform densităţii economice de curent, utilizând
relaţia:
Fec Ic ,
jec
unde Ic
este curentul de calcul al cablului,
Pc
Ic ;
n 3 U n
Pc – puterea de calcul al cablului la 0,4 kV spre secții necesară a fi transportată prin cablul dat;
n – numărul de cabluri paralele;
Un
– tensiunea nominală a cablului, Un 10 kV ;
je
c
– densitatea economică a curentului, din [2, tab. 4.5], pentru Tmax 4335 h,
j 1, 4 A/mm2.
e
Pierderile de putere în liniile în cablu 10 kV se determină conform relaţiei:
P k 2 P l,
în 0
unde kin
este coeficientul de încărcare a liniei corespunzătoare,
Ic
kîn ;
Iadm
P0
– pierderile de putere în cablu la sarcina nominală, kW/km;
l – lungimea liniei în cablu, km.
Linia în cablu W1=W2:
PcID1 PcID1(10kV ) PcPT1 PcPT 3 PcPT 5 PcPT 9 PcPT10
3540 461, 3 272,1 408,1194,8 376, 4 210, 2 5462, 9 kW ;
IcW 1 PcID
5462,9 157, 7 A;
n 3 Un 2 3 10
1
IcW 1 157, 7
F 112, 64 mm2;
ecW 1
je 1, 4
c
27
Din [3, tab.П.9] se alege cablu de tip ААШв 3x150 Iadm 275 A. În regim de avarie
cu
PcID 5462,9
(deconectarea unui cablu) curentul va IcW 1 315, 4 A. Pentru a fi
1 3 10
fi
n 3 Un
respectat I , se vor deconecta unele sarcini de categoria III (PT10) pe perioada reparației.
adm
28
lw4 0, 225 km.
29
Costul cablului CW l C0W 0, 2251760 396 u.m.
Linia în cablu W5:
Pc5 836,9
P P 96 +57,8=572,25 kW;
P
cW 5 c7
c8
2 2
PcW 572,25
IcW 5 n 5 3 Un 3 10 33, 05 A;
IcW 5 33, 05
F 23, 61 mm2;
ecW 5
je 1, 4
c
30
Pierderile de putere
Exemplu pentru sectorul W3:
P n P k 2 l ,
W 0 î
unde ∆P0 sunt pierderile specifice de putere, ∆P0=39(kW/km) pentru AAШв-3х16 ;
kî - coeficientul de încărcare, kî 10, 25
Ic 0,14
Iadm 75
P n P k 2 l 139 0,142 0, 072 0, 05 kW
W 0 î
31
Tabelul 6.1. Datele obţinute în urma calculelor pentru varianta I
Fcalculat, Iadm, ∆P0, ∆PW, Costul
Sector Ic ,A Tipul cablului Iav,A l, km I0, u.m.
mm2 A kW/km kW
W1, W2 157,7 112,64 2xAAШв-3х150 275 315 56 9,06 0,246 1722
W3 10,25 7,32 AAШв-3х16 75 - 39 0,05 0,072 115,92
W4 26,9 19,21 AAШв-3х25 90 54,4 40 0,64 0,225 396
W5 33,05 23,61 AAШв-3х25 90 59,9 40 0,07 0,017 29,92
W6 27,49 19,64 AAШв-3х25 90 54,4 40 0,6 0,208 366,08
Cî ,r
pî ,r Ic ;
Cpierd P Cw ;
Cw – costul unui kW
de energie, Cw 0, u.m.
h kW h;
0467
RI – rata anuală de rambursare a creditului,
R I I E I ;
32
EI – coeficientul de rambursare a creditului, din [9], pentru i 10 şi Tsn 20 ani,
%
EI 0,1175;
I I I ;
ech
Iech P CP ;
CP – costul unui kW de putere instalată la centrala etalon, CP 1000 u.m./kW;
C Cî ,r Cpierd 46, 02
1363,36 u.m.
1317,34
Deci cheltuielile de calcul anuale pentru Varianta I vor constitui:
CAI C I EI 1363,36 12979,92 0,1175 2888,5 u.m.
IcW 1 PcID
6405,1 184,89 A;
n 1 3 Un 2 3 10
IcW 1 184,89
F 132, 06 mm2;
ecW 1
je 1, 4
c
lw1 0, 246 km;
34
respectat I , se vor deconecta unele sarcini de categoria III (PT3, Secțiile 7 și 10 a PT4 și
adm
IcW 4
PcW
34, 41 A;
n 4 3 Un
35
653,85
I 34, 413 10
F cW 4 24,57 mm2;
ecW 4
je 1, 4
c
36
Pc1(TMG 250) Pc5 Pc7 Pc10
IcW 4av 6 836,9 57,8 47,5 64, 65 A.
177,
3 Un 3 10
Pierderile de putere în cablu la sarcina
P0 40 kW/km.
nominală
PcW 96
IcW 6 5,54 A;
n 6 3 Un 3 10
IcW 6 5,54
F 3,96 mm2;
ecW 6
je 1, 4
c
38
Pierderile sumare în linii vor fi:
2
n
I
P I cWi P0i li 9, 65 0, 55 0, 44 0, 31 0, 004 10, 95 kW
i1 admi
Deci, vom alege varianta I, ca fiind mai economă cu chelueli anuale (CA) mai mici.
Calculul şi alegerea cablurilor de alimentare din incinta întreprinderii sînt prezentate în
tabelul 6.4:
Tabelul 6.4. Alegerea LEC 10 kV din incinţa întreprinderii
Sectorul Pc ,kW In ,A Fec ,mm2 Conductor Iadm ,A
SPC-ID1 5462,9 157,7 112,64 2xААШВ 3x150 275
ID1-PT1 177,6 10,25 7,32 ААШВ 3x16 75
SPC-PT6 572,25 33 23,61 ААШВ 3x25 90
SPC-PT4 465,95 26,9 19,21 ААШВ 3x25 90
PT6-PT4 476,25 27,49 19,64 ААШВ 3x25 90
SPC-PT8 863,2 49,83 35,59 ААШВ 3x35 115
PT8-PT2 605,2 34,94 24,96 ААШВ 3x25 90
39
Sectorul Pc ,kW In ,A Fec ,mm2 Conductor Iadm ,A
PT2-PT7 338 19,51 13,93 ААШВ 3x16 75
ID1-PT5 528,1 15,24 10,88 2xААШВ 3x16 75
ID1-PT3 933,3 53,88 38,48 ААШВ 3x50 140
PT3-PT9 661,2 38,17 27,26 ААШВ 3x35 115
PT9-PT10 466,4 26,93 19,23 ААШВ 3x25 90
Din [1, tab.П.4.8] se alege cablu tip АBВГ 4x25 Iadm 115 A.
cu
Tabelul 6.5. Alegerea LEC 0,4 kV din incinţa întreprinderii
Sectorul Sc ,kVA In ,A Conductor Iadm ,A
PT4-D7 65,12 93,99 АBВГ 4x25 115
PT4-D10 48,38 69,83 АBВГ 4x10 70
PT5-D2 (120kW) 160 230,94 АBВГ 4x95 255
PT7-PT9 215,22 310,64 АBВГ 4x150 335
PT8-D14 38,92 56,18 АBВГ 4x10 70
PT10-D2 (90kW) 119,09 171,89 АBВГ 4x50 175
40
7. CALCULUL REŢELEI DIN SECŢIA DE REPARAŢII MECANICE
41
Tabelul 7.1 Datele initiale pentru alegerea parametrilor retelei 0.4 kV
───────────────────────────────────────────────────────────────
| Nr. | P nom | CosF | Conditii | I nom | I porn |
| R/E | kW | | de pornire | A | A |
───────────────────────────────────────────────────────────────
| 1 | 10.00 | 0.60 | Usoare | 24.06 | 120.28 |
| 2 | 7.00 | 0.90 | Ip=Inom | 11.23 | 11.23 |
| 3 | 10.00 | 0.60 | Usoare | 24.06 | 120.28 |
| 4 | 4.50 | 0.60 | Usoare | 10.83 | 54.13 |
| 5 | 14.00 | 0.60 | Usoare | 33.68 | 168.39 |
| 6 | 7.00 | 0.80 | Grele | 12.63 | 63.15 |
| 7 | 20.00 | 0.85 | Ip=Inom | 33.96 | 33.96 |
| 8 | 14.00 | 0.60 | Usoare | 33.68 | 168.39 |
| 9 | 1.70 | 0.80 | Usoare | 3.07 | 15.34 |
| 10 | 1.70 | 0.80 | Usoare | 3.07 | 15.34 |
| 11 | 10.00 | 0.65 | Usoare | 22.21 | 111.03 |
| 12 | 10.00 | 0.65 | Usoare | 22.21 | 111.03 |
| 13 | 7.00 | 0.60 | Usoare | 16.84 | 84.20 |
| 14 | 10.00 | 0.60 | Usoare | 24.06 | 120.28 |
| 15 | 8.20 | 0.50 | Grele | 23.67 | 118.36 |
| 16 | 14.00 | 0.60 | Usoare | 33.68 | 168.39 |
| 17 | 7.00 | 0.65 | Usoare | 15.54 | 77.72 |
| 18 | 7.00 | 0.60 | Usoare | 16.84 | 84.20 |
| 19 | 7.00 | 0.60 | Usoare | 16.84 | 84.20 |
| 20 | 7.00 | 0.65 | Usoare | 15.54 | 77.72 |
| 21 | 14.00 | 0.50 | Usoare | 40.41 | 202.07 |
| 22 | 20.00 | 0.85 | Ip=Inom | 33.96 | 33.96 |
| 23 | 10.00 | 0.60 | Usoare | 24.06 | 120.28 |
| 24 | 10.00 | 0.60 | Usoare | 24.06 | 120.28 |
| 25 | 4.50 | 0.60 | Grele | 10.83 | 54.13 |
| 26 | 14.00 | 0.50 | Usoare | 40.41 | 202.07 |
| 27 | 10.00 | 0.60 | Usoare | 24.06 | 120.28 |
| 28 | 10.00 | 0.60 | Usoare | 24.06 | 120.28 |
| 29 | 7.00 | 0.90 | Ip=Inom | 11.23 | 11.23 |
| 30 | 100.00 | 0.70 | Grele | 206.20 | 1030.98 |
| 31 | 7.00 | 0.80 | Grele | 12.63 | 63.15 |
| 32 | 100.00 | 0.70 | Grele | 206.20 | 1030.98 |
| 33 | 100.00 | 0.70 | Grele | 206.20 | 1030.98 |
| 34 | 20.00 | 0.85 | Ip=Inom | 33.96 | 33.96 |
| 35 | 20.00 | 0.85 | Ip=Inom | 33.96 | 33.96 |
| 36 | 7.00 | 0.80 | Grele | 12.63 | 63.15 |
───────────────────────────────────────────────────────────────
42
Tabelul 7.2 Parametre retelei 0.4 kV
───────────────────────────────────────────────────────────────
| Nr. |Tipul conductor| Fuzibila |Demarorul|Releul termic |
───────────────────────────────────────────────────────────────
| 1 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/25 |
| 2 | APV 4*2.5 | PN2-100/30 | PME-122 | TRN- 16/10 |
| 3 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/25 |
| 4 | APV 4*2.5 | PN2-100/30 | PME-122 | TRN- 16/10 |
| 5 | APV 3*8+1*6 | PN2-100/80 | PMA-322 | TRN- 40/32 |
| 6 | APV 4*2.5 | PN2-100/40 | PME-122 | TRN- 16/10 |
| 7 | APV 3*8+1*6 | PN2-100/50 | PMA-322 | TRN- 40/32 |
| 8 | APV 3*8+1*6 | PN2-100/80 | PMA-322 | TRN- 40/32 |
| 9 | APV 4*2.5 | PN2-100/30 | PME-122 | TRN- 16/5 |
| 10 | APV 4*2.5 | PN2-100/30 | PME-122 | TRN- 16/5 |
| 11 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/20 |
| 12 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/20 |
| 13 | APV 4*2.5 | PN2-100/40 | PME-222 | TRN- 25/16 |
| 14 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/25 |
| 15 | APV 4*4 | PN2-100/80 | PME-222 | TRN- 25/20 |
| 16 | APV 3*8+1*6 | PN2-100/80 | PMA-322 | TRN- 40/32 |
| 17 | APV 4*2.5 | PN2-100/40 | PME-122 | TRN- 16/16 |
| 18 | APV 4*2.5 | PN2-100/40 | PME-222 | TRN- 25/16 |
| 19 | APV 4*2.5 | PN2-100/40 | PME-222 | TRN- 25/16 |
| 20 | APV 4*2.5 | PN2-100/40 | PME-122 | TRN- 16/16 |
| 21 | APV 3*10+1*8 | PN2-100/100 | PMA-422 | TRN- 60/40 |
| 22 | APV 3*8+1*6 | PN2-100/50 | PMA-322 | TRN- 40/32 |
| 23 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/25 |
| 24 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/25 |
| 25 | APV 4*2.5 | PN2-100/40 | PME-122 | TRN- 16/10 |
| 26 | APV 3*10+1*8 | PN2-100/100 | PMA-422 | TRN- 60/40 |
| 27 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/25 |
| 28 | APV 4*4 | PN2-100/50 | PME-222 | TRN- 25/25 |
| 29 | APV 4*2.5 | PN2-100/30 | PME-122 | TRN- 16/10 |
| 31 | APV 4*2.5 | PN2-100/40 | PME-122 | TRN- 16/12.5 |
| 34 | APV 3*8+1*6 | PN2-100/50 | PMA-322 | TRN- 40/32 |
| 35 | APV 3*8+1*6 | PN2-100/50 | PMA-322 | TRN- 40/32 |
| 36 | APV 4*2.5 | PN2-100/40 | PME-122 | TRN- 16/10 |
───────────────────────────────────────────────────────────────
43
7.1. Alegerea cablurilor de alimentare ale nodurilor
Iadm Imax,calc ;
Imax,calc Sc ;
3 Un
c 62, 4
Imax,calc S 3 0, 4 90, 06 A.
3 Un
nodul 1’:
Sc Sc1' 15,5 kVA;
15,5
c
Imax,calc S 22,37A.
3 Un 3 0, 4
Din [1, tab.П.4.8] se alege cablu tip АBВГ 4x4 Iadm 27 A.
cu
nodul 2, 3 și 4:
Sc Sc2 107, 4 kVA;
Din [1, tab.П.4.8] se alege cablu tip АBВГ 4x95 Iadm 170 A.
cu
nodul 5:
Sc Sc5 86, 6 kVA;
86, 6 124,99 A.
c
Imax,calc S
3 Un 3 0, 4
44
Alegem bare conductoare de tip ШРА4-250-32-1У3 cu In=250 A, IP32.
45
După curentul de lungă durată egal cu 125 A instalăm conductorul АBВГ 4x70 cu
Iadm 140 A. ales din [1, tab.П.4.8].
nodul 6:
Sc Sc6 43 kVA;
c 43
Imax,calc S 3 0, 4 62, 06 A.
3 Un
nodul 7:
Sc Sc7 24,9 kVA;
24,9
c
Imax,calc S 35,94 A.
3 Un 3 0, 4
Din [1, tab.П.4.8] se alege cablu tip АBВГ 4x10 Iadm 42 A.
cu
46
8. CALCULUL CURENŢILOR DE SCURTCIRCUIT
Calculul curenţilor de scurtcircuit este necesar pentru verificarea elementelor şi
aparatajului din sistemul de alimentare cu energie electrică a întreprinderii la acţiunea acestor
curenţi de scurtcircuit. La fel calculul curenţilor de scurtcircuit este necesar pentru a elabora
protecţia prin relee a elementelor sistemului de alimentare cu energie electrică.
Pentru calculul curenţilor de scurtcircuit se elaborează schema electrică monofilară
începînd cu staţia sistemului electroenergetic şi terminînd cu receptorul din secţia de reparaţii
mecanice. Pe schemă se indică toţi conductorii de curent, aparatajul de comutaţie şi protecţie, iar
apoi se stabilesc punctele de scurtcircuit pentru care se calculează curenţii de scurtcircuit. Dacă
există motoare sincrone şi asincrone de puteri mari, ele trebuie să fie indicate pe schemă întrucît
au influenţă asupra curenţilor de scurtcircuit. Se determină în general curenţii de scurtcircuit
trifazat, iar pentru linia ce alimentează receptorul cel mai îndepărtat din secţia de reparaţii
mecanice, se determină deasemenea curentul de scurtcircuit monofazat la sfîrşitul liniei (la
bornele receptorului). Toate calculele se înfăptuiesc cu ajutorul unui program special la
calculator.
Se alcătuieşte schema echivalentă pentru calculul curenţilor de scurtcircuit.
47
Ss=900 MVA 9
SE Xs=0,4
QF1 VA 55-41
E 115 kV Inom=1000 A
1 LEA AC-70/11 10
l= 14,4 km Bară A(60x8)
l=5 m;
Iadm=910 A;
TMН -6300/110 11
2 Usc=10,5%
Psc=44 kW VA 55-37
QF2
SPC Po=10 kW Inom=160 A
11 kV
12
LEC 2xAAШB
3 TOП-0,66
3x150 TA2 150/5
l=0,246 km
Iadm=275 A 13
LEC ABBГ 4x35
4 L=35,5 m
LEC AAШB 3x50 Iadm=90 A
l=0,038 km 14
Iadm=140 A
LEC ABBГ 4x35
L=24 m
5 Iadm=27 A
LEC AAШB 3x35 15
l=0,088 km
Iadm=115 A QF3 BA 51-33
Inom=16 A
6 16
LEC AAШB 3x25
l=0,057 km LEC ABBГ 5x2,5
Iadm=90 A L=1,5 m
Iadm=19 A
7 17
ТМГ21-630/10 ПМЕ - 122
Usc=5,5% TRN - 16/12,5
20 A
0,4 kV
18
8 Bară A(60x8) Pnom=7 kW
l=4 m; cosφnom=0,8
Iadm=910 A; M ηnom=0,87
48
Figura 8.1. Schema pentru calculul curenţilor de scurtcircuit
49
9
rS*=0 r1=r0=0,25 mΩ
xS*=0,4
x1=x0=0,1 mΩ
1 10
r0=0,46 Ω/km
r(1)=r(0)=0,074 mΩ/m
x0=0,42 Ω/km
x(1)=x(0)=0,163 mΩ/m
2 11
rT=14,7 Ω
r1=r0=1,2 mΩ
xT=220,4 Ω
x1=x0=0,6 mΩ
3 12
r0(1)=0,206 Ω/km
r1=r0=0,75 mΩ
x0(1)=0,079 Ω/km
x1=x0=1,2 mΩ
4 13
r0(1)=1,1 mΩ/m,
r0(1)=0,59 Ω/km x0(1)=0,068 mΩ/m
x0(1)=0,09 Ω/km r0(0)=2,97 mΩ/m,
x0(0)=1,241 mΩ/m
5 14
r0(1)=9,61 mΩ/m,
r0(1)=0,84 Ω/km x0(1)=0,098 mΩ/m
x0(1)=0,095 Ω/km r0(0)=11,71 mΩ/m,
x0(0)=2,11 mΩ/m
6 15
7 16
r0(1)=9,61 mΩ/m,
r1=r0=3,4 mΩ
x0(1)=0,098 mΩ/m
x1=x0=13,5 mΩ
r0(0)=11,71 mΩ/m,
x0(0)=2,11 mΩ/m
9 17
r(1)=r(0)=0,074 mΩ/m r1=r0=1,8 mΩ
x(1)=x(0)=0,163 mΩ/m x1=x0=0 mΩ
9 18
50
Se aleg parametrii elementelor schemei echivalente.
Sistemul electroenergetic.
Ss 900 MVA, xs 0, 4 ;
Sectorul 1-2
Linia electrică aeriană de alimentare cu energie electrică a întreprinderii tip AC-70/11
ro 0, 46 / km , xo 0, 42 / km , l 14, 4 km ;
Sectorul 2-3
Transformator de putere din staţia principală coborîtoare, tip ТMН-6300/110.
Snomtr 6300 KVA, U 10,5%;
sc
Psc 44 kW P0 10 kW .
,
Sectorul 3-4.
Linia electrică în cablu, tip. 2xААШв 3x150,
Iadm 275 A,
l 0, 246 km ;
ro 0, 206 /
xo 0, 079 / km,;
km,
Sectorul 4-5.
Linia electrică în cablu, tip. ААШв 3x50,
Iadm 140 A, l 0, 038 km ;
ro 0,59 / xo 0, 09 / km ;
km,
Sectorul 5-6.
Linia electrică în cablu, tip. ААШв 3x35,
Iadm 115 l 0, 088 km ;
A, ro 0,84 / xo 0, 095 / km
km,
Sectorul 6-7.
Linia electrică în cablu, tip. ААШв 3x25,
Iadm 90 A, l 0, 057 km ;
ro 1,17 / xo 0, 099 / km
km,
Sectorul 7-8.
Transformatorul de putere din secţie.
Din [19] se alege transformatorul de tip ТМГ12-630/10 У1 (ХЛ1) cu parametrii:
Sn 630 kVA, Usc 5.5%, U1n 10,5 kV
U2n 0, 4 kV ;
, ;
51
P0 0,8 kW , Psc 6, 75 kW.
Se determină parametrii pasivi ai transformatorului din tab.1 [10]:
r1 r0 3, 4 m; x1 xo 13,5 m..
52
Sectorul 8-9
Bara se alege conform următoarei condiţii:
Iadm Imax ;
Imax Int ,
und
e I este curentul maxim ce parcurge înfăşurarea primară a transformatorului de curent;
max
In,a In.t ;
In,dsdt I nt ;
Iregdsdt Idsdt ;
53
I ds 1,55 I nt ;
unde,
I este curentul nominal al transformatorului,
n.t
54
Int 910 A;
Inds
1 1 I 1000 A 910 A ;
I I
n,ds na n.t
Ina
Iregds
2 2 I 2 1000 2000A 1410,5 A ;
I I
regds nds ds
Inds
Iregdt
1, 25 1, 25 I 1, 251000 1250 A 1183 A ;
I I
regdt nds dt
Inds
În funcţie
de In,a 1000 A din [21,tab. A19.] se aleg parametrii întreruptorului automat:
r1 r0 0, 25 m;
x1 xo 0,1 m ;
Sectorul 10-11
Bara se alege din aluminiu A (60x8) cu
Iadm 910 l=5 m.
curentul Cu parametrii de mai sus a sectorului A;
8-9.
Sectorul 11-12
Întreruptorul automat QF2 ce alimentează nodul la care este conectat receptorul electric
cel mai îndepărtat.(nodul 5)
Se alege conform condiţiilor:
Un,a Uretea ,
In,a I max,l ,
In,dsdt I max,l ,
Iregdsdt Idsdt ;
unde,
55
I max,l curentul maximal de lucru, I Sc
este max,l 3 U n ;
c 86, 6
Imax,l S 3 0, 4 125 A ;
3 Un
56
Reglajul de curent al declanşatorului de secţionare al întreruptorului automat ce
alimentează un grup de receptoare electrice se calculează conform relaţiei:
I ds 1,5 I ' ,
P
n1
I P I P max ,
I
'
und calc,mi
e i1
n1
I
i1
calc,mi - este suma curenţilor receptoarelor electrice fără curentul nominal al
receptorului cu cea mai mare putere;
n1
Icalc,mi I I n max
i1
max,l
In max - curentul nominal al receptorului cu cea mai mare In max A , din tabelul
putere, 33,96
7.1 . (receptorul 34, 35);
n1
I
i1
calc,mi Imax,l In max 104, 41 33,96 70, 45 A ;
I P max - curentul de pornire al motorului cu cea mai mare IP max , din tabelul
putere, 63,15A
7.1 . (receptorul 31,36);
n1
I' I I 70, 45 63,15 133, 6 A ;
P
i1
calc,mi P max
57
A , vezi sectorul 11-12.
Din [22] se alege transformatorul de curent tip TOП-0,66 cu parametrii:
Un 0, 66kV
I1n 150 I2n 5 A ; clasa de precizie 0,5.
;
A;
În dependenţă
de KI 150 / 5 din [12,tab. 2.49.] se aleg parametrii pasivi:
58
r1 r0 0, 75 m;
x1 xo 1, 2 m ;
Sectorul 13-14
Cablul de alimentare al nodului 1 [vezi cap. 7.1].
Cablu de tip АВВГ 4x35
cu Iadm 90 A , cu parametrii:
Inom,ÎA Ilucru.max
und I
lucru.max Inom este curentul maximal de lucru, care se determină conform :
e
Pnom
Inom ;
3 cos Un
r1 r0 7 x1 x0 4,5 m.
m;
Sectorul 16-17
59
Conductor de alimentare a receptorului electric 31.
60
Iadm Inom31 ;
Inm31 14,52 A.
Din [1, tab.П.4.8] se alege cablu tip АВBГ 5x2,5 Iadm 19 l 1,5 m.
cu Din [21] se aleg parametrii pasivi: A;
r01 9, 61 x01 0, 098 r00 11, 71 x00 2,11 m/m.
m/m; m/m; m/m;
Sectorul 17-18
Contactorul se alege pentru
In 14,52 A Pnom 7 din catalogul IEK Moldova
şi kW
contactorul ПМE 122 în ansamblu cu releul termic TRN 16/12,5 cu parametrii:
r1 r0 1,8 m;
Datele pentru calculul curenţilor de scurtcrcuit în sistemul de alimentare cu energie
electrică şi rezultatele calculelor curenţilor de scurtcircuit sînt prezentate în tabelul 8.1
Tabelul 8.1. Datele pentru calculul curentilor de s.c. in sistemul de AEE
───────────────────────────────────────────────────────────────
| A | B | C | D | RNP | XNP | F | P | Q | E |
───────────────────────────────────────────────────────────────
| 0.000 .4000 900.0 115.0 0.000 0.000 0.000 0.000 0.000 0.000 |
| .4600 .4200 14.40 115.0 0.000 0.000 0.000 0.000 0.000 0.000 |
| 6300. 10.50 44.00 11.00 0.000 0.000 0.000 0.000 0.000 0.000 |
| .1030 .0380 .2460 11.00 0.000 0.000 0.000 0.000 0.000 0.000 |
| .5900 .0900 .0380 11.00 0.000 0.000 0.000 0.000 0.000 0.000 |
| .8400 .0950 .0880 11.00 0.000 0.000 0.000 0.000 0.000 0.000 |
| 1.170 .0990 .0570 11.00 0.000 0.000 0.000 0.000 0.000 0.000 |
| 3.400 13.50 0.000 .4000 3.400 13.50 0.000 0.000 0.000 0.000 |
| 9.000 .0740 .1630 4.000 .4000 .0740 .1630 0.000 0.000 0.000 |
| .2500 .1000 0.000 .4000 .2500 .1000 0.000 0.000 0.000 0.000 |
| .0740 .1630 5.000 .4000 .7400 .1630 0.000 0.000 0.000 0.000 |
| 1.200 .6000 0.000 .4000 1.200 .6000 0.000 0.000 0.000 0.000 |
| .7500 1.200 0.000 .4000 .7500 1.200 0.000 0.000 0.000 0.000 |
| 1.100 .0680 35.50 .4000 2.970 1.241 0.000 0.000 0.000 0.000 |
| 9.610 .0980 24.00 .4000 11.71 2.110 0.000 0.000 0.000 0.000 |
| 7.000 4.500 0.000 .4000 7.000 4.500 0.000 0.000 0.000 0.000 |
| 9.610 0.000 1.500 .4000 11.71 2.110 0.000 0.000 0.000 0.000 |
| 1.800 0.000 0.000 .4000 1.800 0.000 0.000 0.000 0.000 0.000 |
───────────────────────────────────────────────────────────────
61
9.VERIFICAREAELEMENTELOR ŞI A APARATULUI DIN SISTEMUL DE AEE
A ÎNTREPRINDERII LA ACŢIUNEA CURENŢILOR DE SCURTCIRCUIT
Elementele şi aparatajul care urmează să fie alese trebuie să satisfacă o serie de criterii,
adică se verifică la acţiunea curenţilor de scurtcircuit.
Snt 6300
Inorm 33, 06 A ;
3 Un 3 110
is 8, 085 kA;
Tabelul 9.1.
nr. Prametrii calculaţi Parametrii din catalog Condiţiile de alegere
1 Uretea 110 kV U n 110 kV U n Uretea
3, 55 kA2 s
ia.
0,06
2 IP0 e Ta 2 4,867 0.02 0,342 kA ;
e
I P, - valoarea eficace a componenţei periodice a curentului de scurtcircuit, kA.
Valoarea acestui curent se determină utilizînd curbele de tip. [2, fig.3.26].
Se observă că:
IP0 4,867
147, 21 8 ;
In 33, 06
Deci: 103
IP I p0 4,867 kA ;
n - componenta relativă a curentului aperiodic de scurtcircuit în curentul de rupere, din
[2,fig.4.54] pentru 0, 06s , n 15% ;
B - impulsul termic, kA2 s .
s
Tabelul 9.2
nr. Prametrii calculaţi Parametrii din catalog Condiţiile de alegere
1 Uretea 110 kV U n 110 kV U n Uretea
2 Icerut 46, 29 A I n 1000A I n Icerut
3 is 8, 085 kA ild 80 kA ild is
4 B 3,55 kA2 s I t 31,52 3 2977 kA2 s
2
I t B
2
sc T T T T sc
63
Din [5,tab.5.13] se alege transformatorul de tensiune НКФ-110-83У1, cu
U1n 110 kV U2n 100 V .
;
64
9.2. Alegerea şi verificarea întreruptorului liniei în cablu 10kV
Se determină curentul care circulă prin linie:
Pc
I max,l ;
3 U n
Pc PcID1(10kV ) PcPT1 PcPT 3 PcPT 5 PcPT 9 PcPT10
3540 461, 3 272,1 408,1194,8 376, 4 210, 2 5462, 9 kW ;
c
Imax,l 5462,9
P 157, 7 A .
3 Un 3 10
Curenţii de scurtcircuit determinaţi (punctul 3) sunt:
IP0 2,981 kA ;
is 7,376 kA ;
Deci, din [5, tab.9.5] se alege celula prefabricată tip interior КРУ D-12P, cu In 1000 A
cu întreruptor cu vid tip. BB/TEL 10-12,5 800, din [18] se aleg parametrii acestui întreruptor.
Verificarea se face în formă de tabel:
Tabelul 9.3.
nr. Prametrii calculaţi Parametrii din catalog Condiţiile de alegere
1 Uretea 10 kV U n 10 kV U n Uretea
2 Icerut 157, 7 A In 800A I n Icerut
3 is 7,376 kA ild 51 kA ild is
2 IP iai 2 2, 981 2 Irup 1 n 2 20 2 Irup 1 n
4
0, 313 4, 53 kA 1 0,15 32, 53 kA 2 IP,i ia,i
B I 2 t T
sc P0 dec a
0, 77 kA2 s
ia.
2 e Ta 2 2,981 0,052
0.01 0,313 kA ;
IP0 e
IP I p0 2,981 kA ;
n 15% ; din [2, fig.4.54].
9.3. Alegerea şi verificarea liniei în cablu pe sectorul SPC - PD-10kV
Linia electrică în cablu a fost aleasă în capitolul 6 [vezi tabelul 6.4], tip ААШb 3x150 cu
Iadm 275 A .
Cablu se verifică după secţiunea minimă:
qmin qmin
65
qales ,
Bsc
;
c
66
Bsc 0, 77 kA2 s , (vezi tabelul 9.3.);
C- coeficientul care depinde de caracteristica conductorului, valoarea căruia se alege din
1/ 2 2
[2, tab.3.14], C 100A s / mm ;
Bsc 0, 77 106 2
qmin 8, 77 mm ;
c 100
Se observă:
qmin 8, 77 mm2 150 mm2 , deci cablul va fi termic stabil.
a
q
Snt 6300
Imax 1, 4 1, 4 509, 22 A ;
3 10
3 Un
Din [5, tab.5.9] se alege transfomator de curent tip. ТШЛ-10-У3 cu parametrii nominali:
I1n 2000 A
I2n 5 r2n 0,8 , în clasa de precizie 0,5.
;
A;
Se verifică transformatorul de curent la sarcina secundară:
r2calc r2n ,
unde, r2n este sarcina nominală secundară admisibilă a transformatorului de r2n 0,8 .
curent,
r2calc - sarcina secundară de calcul a transformatorului de curent;
68
Se detremină secţiunea conductorului:
qcond lcalc ;
,
rcond
Tabelul 9.5
nr. Prametrii calculaţi Parametrii din catalog Condiţiile de alegere
1 Uretea 10 kV U n 10 kV U n Uretea
3 B 0, 77 kA2 s 2 2
I t 35 3 3675 kA s
2
I2t B
sc T T T T sc
69
S2n 120 VA ;
Transformatorul de tensiune se verifică la sarcina secundară:
S2nom S2calc ;
70
unde, S - este sarcina secundară nominală a transformatorului de S2nom 120 VA ;
2nom
tensiune,
S2calc - puterea consumată de toate aparatele de măsură, conectate la înfăşurarea secundară
a transformatorului de tensiune, VA.
Aparatele de măsură urmează a fi conectate la secundarul transformatorului de tensiune:
Tabelul 9.6
Aparatul Tipul Sarcina fazei
VA
Voltmetru Э – 335 2
Contor electronic de putere activă şi ALFA A1140 1,34
reactivă
Bilanţ 3,34
Deci, S 120 VA S
2n 2calc 3,34 VA , transformatorul de tensiune va funcţiona în clasa de
preczie 0,5.
Pentru protecţia transformatorului de tensiune împotriva curenţilor de scurtcircuit se
foloseşte siguranţa fuzibilă de tip ПКН001-10У1, din [5, tab.5.4].
unde,
I nf este curentul nominal al fuzibilului;
Snt 630
Int 36,37 A;
3 Un 3 10
Din [5, tab.5.4] se alege siguranţa fuzibilă tip ПКT103-10-100-12, БУ3 cu parametrii
prezentaţi în tabelul 9.7
Tabelul 9.7
nr. Prametrii calculaţi Parametrii din catalog Condiţiile de alegere
1 Uretea 10 kV U n 10 kV U n Uretea
71
9.7. Alegerea şi verificarea separatorului de sarcină de 10 kV
Imax c
S 630
3 10 36,37 A;
3 Un
Din [5, tab.5.3] se alege separator de sarcină tip ВНР-10/400-103 У3. Verificarea se face în
formă de tabel.
Tabelul 9.8
nr. Prametrii calculaţi Parametrii din catalog Condiţiile de alegere
1 Uretea 10 kV Un 10 kV U n Uretea
Inom
Pno 7
14,52 A; ;
3 cosm Un 3 0,8 0,87 0, 4
Din [1, tab.П.4.8] se alege conductorul de tip АBВГ 5x2,5 Iadm 19 A , şi l 1,5 m .
cu
Pentru pornirea receptorului electric a fost ales demarorul electromagnetic de tip
ПМE122. Protecţia motorului împotriva suprasarcinilor se realizează cu releul termic de tip
TRN 16/12,5. Aparatele pentru comutarea şi protecţia motorului electric M31, au fost alese
utilizînd programul de calcul (vezi tab. 7.2).
Întreruptorul automat la partea de joasă tensiune a PT10 din SRM (QF1) şi întreruptorul
automat ce alimentează nodul la care este conectat receptorul electric M31 (QF2) au fost alese în
capitolul 8, sectorul 9-10 și respectiv sectorul 11-12.
72
10. ALEGEREA TIPULUI DE PROTECŢII PRIN RELEE ŞI REGLAJUL TIMPULUI
DE ACŢIONARE A LOR
Alegerea tipului de protecţii prin relee şi coordonarea funcţionării lor se aplică în reţeaua
receptor electric de 0,4 kV (M31) – cablu 10 kV care alimentează PT10. Alegerea şi coordonarea
ia începutul de la receptorul electric din secţie trecînd treptat la elementele următoare a reţelei.
ID -10kV
ААЩB 3x150
ААЩB 3x50
ААЩB 3x35
ААЩB 3x25
FU1 ПКT103-10-100-11,BУ3
ТМГ 630/10
QF1 VA 55-41
Inom=1000 A;
QF2 VA 55-37
Inom=160 A;
ABВГ 4x35
QF3 BA 51-33
Inom=16 A;
ABВГ 5x2,5
ПМЕ 122
M31
73
10.1. Verificarea selectivităţii între elementele protecţiei
Verificarea selectivităţii între elementele protecţiei se începe de la cel mai îndepărtat
receptor electric (M 31) din SRM şi terminînd cu SPC.
Pentru protecţia receptorului electric nr.31 din SRM a fost aleas întreruptorul automat tip
BA51-33/16. Acest dispozitiv acţionează neselectiv şi timpul lui de acţionare se determină din
fig.11.3 [1] în funcţie de curentul de scurtcircuit monofazat la barele I Is 659A .
motorului,
Deci, din tab.A.1.3. [11] se alege timpul de acţionare al întreruptorului automat tip ВА 55-37,
tdQF 2 0,1 s .
und
e td1 şi td 2 sunt timpii de acţionare a întreruptoarelor automate instalate în amonte (QF1),
74
Timpul de topire al elementului fuzibil la un scurtcircuit la barele de 0,4 kV al siguranţei
fuzibile tip ПКТ 103-10-100, aleasă în paragraful 9.6, se determină din fig.4 [11] pentru
75
I ' I (3) 0, 4 10928 0, 4 437,12 A ;
sc scJT
10 10
Deci, t f 10 0, 4 s
.
tPMC t f 10 t ,
76
11. ALEGEREA SCHEMELOR DE AUTOMATIZARE, SEMNALIZARE, MĂSURĂ ŞI
EVIDENŢĂ A ENERGIEI ELECTRICE
77
Se prezintă schema D.A.A.R. cu întreruptor de secţionare:
ID-10 kV ID-10 kV
Q Q Q Q Q
TMН-6300/110
KV1 KV2
78
Fig.11.2. Schema reglării automate a puterii bateriilor de condensatoare într-o treaptă.
79
10 кV
Q2
AВС PА PIK
TV
a
c
n
KV
PV
80
12. COMPENSAREA PUTERII REACTIVE
unde Qt( pos) este puterea reactivă posibilă de transportat prin transformatorul postului de
transformare, kvar;
n – numărul de transformatoare din posturile de transformare;
kirec – coeficientul de încărcare recomandat al postului de transformare;
Snt
– puterea nominală a transformatorului, kVA;
Pc
– puterea de calcul al postului de transformare, kW.
Puterea necesară a bateriilor de condensatoare se determină cu relaţia:
Q Q
Qt
pos
BCcalc c ,
82
QtTMG 400 Ki.rec. n S
nt P 0, 7 1 400 2 283, 692 45, 61 kvar;
( pos) 2 2
cTMG 400
83
12.2. Consumul de putere reactivă
Puterea reactivă sumară consumată pe partea 0,4 kV constituie Qc0,4 2512, 2 kvar.
Rezerva de putere reactivă pentru regim după avarie se consideră 10% din puterea reactivă
sumară consumată:
QR 0,1Qcons. 0,15702, 2 570, 22 kvar;
În total putere reactivă necesară pentru consum la întreprindere va fi:
Qnecesar Q QR 5702, 2 570, 22 6272, 42 kvar.
und QM este puterea reactivă maximă care poate fi produsă de motoarele sincrone, kvar;
e S
– coeficient de suprasarcină admisibilă a motorului după puterea reactivă, din [18] se
m
alege m 1, 21;
tgnom
– corespunde valorii nominale admise a cosnom tgnom 0,593;
0,86
nom – randamentul motorului sincron, din [5] se alege nom 0,94;
m PnomMS tgnom 1, 21 400 0,593
Q MS 400 nom 305,33 kvar;
0,94
Deci puterea reactivă sumară produsă de motoarele sincrone va fi :
84
Q MS 9QMS 400 9305,33 2747,97 kvar
85
Tabelul 12.2. Bilanţul puterilor reactive la întreprinderea proiectată.
N d/o Compartimentele bilanţului de putere Q, kvar
I. Partea de cheltuieli a bilanţului:
1.1 Sarcina consumatorilor 0,4 kV 2512,2
1.2 Sarcina consumatorilor 10 kV 2655
1.3 Pierderi de putere în transformatoarele de secţie: 535
1.4 Total consum putere reactivă: 5702, 2
1.5 Rezervă pentru regimurile de postavarie 10%: 570, 22
1.6 Puterea cerută a surselor de compensare, kvar 6272,42
II. Livrarea puterii reactive:
2.1 Sistemul electroenergetic: 2056
2.2 Motoarele sincrone 10 kV: 2748
2.3 Bateriile de condensatoare 0,4 kV: 1740
2.4 Bateriile de condensatoare 10 kV: 0
2.5 Total livrat: 6544
III. Bilanţul: 271,58
86
ÎNCHEIERE
În proiectul a fost efectuată alimentarea cu energiei electrică a uzinei consturctoare de
tractoare. Alegerea tensiunii de alimantare a uzinei (110kV) a fost argumentată din punct de
vedere tehnic. Alegînd tensiunea de alimentare 110kV, a fost nevoie de instalarea pe teritoriul
întreprinderii a staţiei principale coborîtoare, cu două transformatoare de putere tip ТMН-
6300/110.
Pentru ridicarea fiabilităţii în alimentarea cu energie electrică a uzinii, instalaţia de
distribuţie - 10kV se secţionează cu întreruptorul de secţionare, care în regim normal de
funcţionare este deconectat. Pentru comutarea rapidă a consumatorilor la sursa de rezervă, în caz
de avarie, este folosit dispozitivul de anclanşare automată rapidă a rezervei.
Schema de alimentare a secţiilor uzinii a fost argumentată după analiza tehnico-economic a
două variante.
Toate posturile de transformare ale secţiilor au fost alese de tip interior, cu excepția PT-
ului 4 din cauza lipsei de teritoriu în secție. Secţiile cu sarcină mică au fost alimentate de la
posturi de transformare vecine prin cabluri de 0,4 kV.
Calculul curenţilor de scurtcircuit al reţelei în raport cu cel mai îndepărtat receptor electric
a fost nevoie pentru a realiza protecţia prin relee a elementelor sistemului, şi pentru verificarea
echipamentului sistemului de alimentare cu energie electrică.
Pentru a avea o compensare completă a puteri reactive, motoarele sincrone din secția
mecanică au fost considerate că funcţionează în regim de supraexcitare (de generare a puterii
reactive în reţea), generând în reţea o putere reactivă de 2748 kvar, folosind dispozitivul de
reglare a puterii reactive.
În fine toate deciziile luate în proiectul de an sunt argumentate prin calcule tehnoco-
economice luând în consideraţie cerinţele NAIE (Norme şi Amenajări în Instalaţiile
Electroenergetice).
87
BIBLIOGRAFIE
1. Федоров А.А.,Старкова Л.Е.Учебное пособие для курсового и дипломного
проектирования по электрснабжению промышленных предприятий. М.:
Энергоатомиздат,1987.
2. Рожкова Л.Д., Козулин В.С. Электрооборудование станций и подстанций. М.:
Энергоатомиздат, 1987.
3. Федоров А.А.,Каменева В.В. Основы электрснабжения промышленных
предприятий.М.:Энергоатомиздат,1984.
4. Romanciuc I. Alimentarea cu energie electrică a întrprinderilor.Îndrumar de
proiectare.U.T.M.Chişinău,1999.
5. Неклепаев Б.Н., Крючков И.П. Электрическая часть электростанций и подстанций.
Справочные материалы для курсового и дипломного проектирования. М.:
Энергоатомиздат, 1989.
6. Справочные материалы для курсового и дипломного проектирования систем
электроснабжения промышленных предприятий/Грейнер Г.Р.,Романчук И.В.Кишинев:
Ротапринт КПИ им.С.Лазо,1987.
7. Правила устройства электроустановок. М.: Энергоатомиздат, 1985.
8. Arion V. Costurile instalaţiilor electroenergetice. U.T.M.Chişinău,2002.
9. Arion V.Bazele calculului tehnico-econemic al sistemelor de transport şi distribuţie a
energiei electrice. U.T.M.Chişinău,1998.
10. Беляев А.В. Выбор аппаратуры, защит и кабелей в сетях 0,4 кВ. Л.:
Энергоатомиздат, 1988.
11.Stanciu T., Rudei I. Protecţia prin relee în sisteme electroenergetice. Îndrumar metodic
pentru lucrarea de curs.U.T.M. Chişinău, 2001.
12. Справочник по проектированию электроснабжения/ Под ред. Барыбина Ю.Г. и
др. М.: Энергоатомиздат, 1990.
13. Киселев Ю.Я.,Красножан Л.С. Расчет токов коротково замыкания для релейной
защиты и системой автоматики. М.: Энергия.
14. Справочник по электроснабжению и электрооборудованию. Т.1./ Под общ. ред.
Федорова А.А. М.: Энергоатомиздат, 1986.
15. Stanciu T., Rudei I. Protecţia prin relee în sisteme electroenergetice. Îndrumar metodic
pentru lucrări de laborator.U.T.M. Chişinău, 2002.
16. Андреев В.А. Релейная защита и автоматика систем электроснабжения. М.:
Высшая школа, 1991.
17. Stanciu T., Rudei I. Automatizări Protecţie prin relee în instalaţii energetice. Îndrumar
metodic pentru lucrarea de curs.U.T.M. Chişinău, 2003.
18. http://www.tavrida.ru/
19. http://www.rec.su/catalog/?SECTION_ID=197&ELEMENT_ID=772
20. https://www.iek.ru/
21. Pogora V., Procese tranzitorii în sistemele de alimentare cu energie electrică. U.T.M.
Chişinău 2013.
22. https://www.iek.ru/products/catalog/detail.php?ID=155310
23. http://www.nucon.ru/Reactive-power-compensation/adjustable-capacitors.php
88