h= 2847 [mm]
Dimensionarea distribuitor-colectorului
Recipient de descarcare
VRD= 3.02 [m3]
ΔQ= Qsursa,c
Qsursa Qsursa. cumul Qcons Qcons. cumul
Ora 500ap. cumulat - Qcons, c
[%] [%] [kW] [kW] [kW] [kW] [kW]
1 5-6 2.8 2.8 466.61 466.6078 248.24 248.24 218.37
2 6-7 8.6 11.4 466.61 933.22 762.44 1010.67 -77.46
3 7-8 6.3 17.7 466.61 1399.82 558.53 1569.20 -169.38
4 8-9 4.7 22.4 466.61 1866.431 416.68 1985.88 -119.45
5 9-10 2.9 25.3 466.61 2333.039 257.10 2242.98 90.06
6 10-11 3.8 29.1 466.61 2799.647 336.89 2579.87 219.77
7 11-12 4.8 33.9 466.61 3266.255 425.55 3005.42 260.83
8 12-13 6.8 40.7 466.61 3732.863 602.86 3608.28 124.58
9 13-14 5.3 46 466.61 4199.471 469.87 4078.15 121.32
10 14-15 3.5 49.5 466.61 4666.078 310.29 4388.45 277.63
11 15-16 3.9 53.4 466.61 5132.686 345.76 4734.20 398.48
12 16-17 4.1 57.5 466.61 5599.294 363.49 5097.69 501.60
13 17-18 4.7 62.2 466.61 6065.902 416.68 5514.37 551.53
14 18-19 5.6 67.8 466.61 6532.51 496.47 6010.84 521.67
15 19-20 6.5 74.3 466.61 6999.118 576.26 6587.10 412.01
16 20-21 7.7 82 466.61 7465.725 682.65 7269.75 195.98
17 21-22 10.9 92.9 466.61 7932.333 966.34 8236.10 -303.76
18 22-23 5.4 98.3 466.61 8398.941 478.74 8714.83 -315.89
19 23-24 1.7 100 466.61 8865.549 150.71 8865.55 0.00
ΔQmin= -315.89 [kW]
ΔQmax= 551.53 [kW]
10000
9000
8000
7000
6000
5000 1
2
4000
3000
2000
1000
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
ΔQmin ΔQmax
Vrez= -2.91 9.48 [m3]
Rezervoare de acumulare A.C.M. (calorserv.ro)
ΔpCT=Δpcz1+Δp1.1+Δp1.2+Δp1.3+Δp1.4+Δp1.5+Δp1.6+Δp1.7+Δp1.10+ΔpD+ΔpC+Δp1.11+Δp1.8+Δp1.9
ΔpD= 960 [Pa]
ΔpC= 1440 [Pa]
Nr.
Q Q d l w R R*l Σξ z R*l+z Σ(R*l+z)
tronson
[kW] [kg/h] [mm] [m] [m/s] [Pa/m] [Pa] [Pa] [Pa] [Pa]
1 2 3 4 5 6 7 8 9 10 11
1.1 950 40842.6 108x4 2.76 1.5 200 552.00 11,2 12360.60 12912.60 12912.60
1.2 950 40842.6 219x4,8 1.6 0.5 9.81 15.70 1 122.63 138.32 13050.92
1.3 1900 81685.3 219x4,8 1.6 0.7 19.62 31.39 1.5 360.52 391.91 13442.83
1.4 2850 122527.9 219x4,8 1.6 1.1 44.145 70.63 1,5 #VALUE! #VALUE! #VALUE!
1.5 4300 184866.7 219x4,8 2.07 1.7 98.1 203.07 3.00 4252.64 4455.70 #VALUE!
1.6 4300 184866.7 219x4,8 9.79 1.7 98.1 960.40 3.00 4252.64 5213.03 #VALUE!
1.7 950 40842.6 108x4 5.14 1.5 200 1028.00 4.00 4414.50 5442.50 #VALUE!
1.8 4300 184866.7 245x8 4.32 1.7 98.1 423.79 3.00 4252.64 4676.43 #VALUE!
1.9 4300 184866.7 219x4,8 5.47 1.7 98.1 536.61 3.00 4252.64 4789.24 #VALUE!
cazan 1 950 42.43 [m3/h] Δpcz= 80 [mbar] = 8000 [Pa] ΔpCT= 49380.63
cazan 2 500 22.33 [m3/h] Δpcz= 60 [mbar] = 6000 [Pa]
1.10 500 21551.7 108x4 2.76 0.8 60 165.60 11.2 3515.90 3681.50
1.11 2400 103448.3 219x4,8 1.6 0.95 29.43 47.09 1.5 664.01 711.10
1.12 1450 62500.0 219x4,8 1.6 0.55 11.772 18.84 1.5 222.56 241.40
1.13 500 21551.7 219x4,8 1.6 0.5 9.81 15.70 1.5 183.94 199.63
1.14 500 21551.7 108x4 5.14 0.8 60 308.40 4.0 1255.68 1564.08
Nr.
Σξ
tronson
armatura + buc ξ
Cot 90° = 2 1
1.1 Robinet cu ventil = 2 4
Clapeta de sens = 1 1.2
1.2 Cot 90° = 1 1
1.3 Teu de trecere la impreunare = 1 1.5
1.4 Teu de trecere la impreunare = 1 1
1.5 Teu de trecere la impreunare = 1 1
1.6 Teu de trecere la impreunare = 1 1
Teu de trecere la impreunare = 1 1
1.7
Cot 90° = 2 1
Cot 90° = 3 1
1.8
Curba = 1 0.3
Teu de separare = 1 0.5
1.9 Cot 90° = 4 1
Robinet cu ventil = 1 4
1.10 Cot 90° = 3 1
1.11 Cot 90° = 4 1
Determinarea pierderilor de sarcină pe circuitul primar al schimbătoarelor de căldură
Nr.
Q Q d l w R R*l Σξ z R*l+z Σ(R*l+z)
tronson
[kW] [kg/h] [mm] [m] [m/s] [Pa/m] [Pa] [Pa] [Pa] [Pa]
1 2 3 4 5 6 7 8 9 10 11
2.1 500 21551.7 95*3,5 15.6 1.1 120 1872 14,2 8427.77 10299.77 10299.77
2.2 250 10775.9 76*3,5 1.16 0.85 100 116 7 2480.70 2596.70 12896.47
2.3 250 10775.9 76*3,5 1.39 0.85 100 139 7 2480.70 2619.70 15516.18
2.4 500 21551.7 95*3,5 14.87 1.1 120 1784.4 5 2967.53 4751.93 20268.10
ΔpI= 2.89 [mH2O] = 28350.9 [Pa] ΔpCTcirc primar sch= 48619.0035
Nr.
Σξ
tronson
armatura + buc ξ
Cot 90° = 5 1
2.1 Robinet cu ventil = 2 4
Clapeta de sens = 1 1.2
Teu de trecere la separare = 1 1
2.2
Cot 90° = 2 1
Teu de trecere la impreunare = 1 1.5
2.3
Cot 90° = 2 1
2.4 Cot 90° = 4 1
HP=Δpcz1+Δp1.1+Δp1.2+Δp1.3+Δp1.4+Δp1.5+Δp1.6+Δp1.7+Δp1.8+Δp1.9
P1
DP=Qinst cz 1 / (c*Δt1)
HP=Δpcz2+Δp1.10+Δp1.5+Δp1.6+Δp1.11+Δp1.12+Δp1.13+Δp1.14
P2
DP=Qinst cz 2 / (c*Δt1)
HP=ΔpRE+ΔpRI+Δpap+ΔpD+ΔpC+Δp1.8+Δp1.9
P3
DP=Qinst R1 / (c*Δt1)
HP=ΔpRE+ΔpRI+Δpap+ΔpD+ΔpC+Δp1.8+Δp1.9
P4
DP=Qinst R2 / (c*Δt1)
DP = 42.32 m3/h
P1
Hp = 37514.96 Pa 3.82 mH2O
DP = 22.28 m3/h
P2
Hp = 22066.46 Pa 2.97 mH2O
DP = 63.49 m3/h
P3
Hp = 69465.67 Pa 7.08 mH2O
DP = 63.65 m3/h
P4
Hp = 64465.67 Pa 6.57 mH2O
Pompe pe circuitul primar al schimbătoarelor de căldură
HP=ΔpI+Δp2.1+Δp2.2+ΔpD+ΔpC+Δp2.3+Δp2.4+Δp1.8+Δp1.9
P5
DP=Qinst cz 2 / (c*Δt1)
DP = 22.28 m3/h
P5
Hp = 60484.67 Pa 6.17 mH2O
HP=ΔpII+Δp3,1-3,4
P6
DP=Qinst cz 2 / (c*Δt2)
HP=Δpcirculatie
P7
DP=Qinst cz 2 / (c*Δt2)
DP = 8.91 m3/h
P6
Hp = 25565.50 Pa 2.61 mH2O
DP = 8.91 m3/h
P7
Hp = 49050.00 Pa 5.00 mH2O
Pompa pe circuitul de adaos
HP=pi+Δp4.3+hg
P8
DP=VRD*0,5